Glow Brand · Boiler · Other

Anti-legionella cycle

B85/B120/B160

What happens, in order

  1. Applies to DHW mode 1 (indirect tank with sensor) with parameter 2.206 enabled
  2. Control checks that the unit reached the control temperature at least once every 7 days
  3. If not, it fires and starts the pump to push the tank over the control temperature
  4. Display shows ALEg with the DHW sensor temperature and the faucet icon blinks
  5. Boiler does not answer normal CH or DHW demands while the special operation runs

Timings and thresholds

ItemValue
Check interval168 h (7 days)

Applies to: B85, B120, B160

Models

B85B120B160

More Glow Brand boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Glow Brand B85/B120/B160 Installation and Operating Manual (sections 10.2, 11.7, 11.8, 11.10, 12.1). Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.