Glow Brand · Boiler
Loc 5 Fan not running for more than 60 seconds
What the control is telling you
The measured fan speed never reached the target within 60 seconds.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Loose or poor line, neutral or ground connection to the boiler, or a bad internal ground
- Loose fan wiring at the fan or ICB
- Damaged harness
- Failed fan
Test and repair steps
- Check line, neutral and ground to the boiler and internal grounds.
- Check the fan connector at the fan and at the ICB.
- Replace the harness.
- Replace the fan.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Models that show this code
3 models in Glow B85/B120/B160
Other codes on the same units
- Loc 3 Safety relay fault
- Loc 33 Low water cut-off circuit open
- Loc 38 Blocked flue switch tripped more than 3 times in 24 h
- Loc 4 Blocking error lasted over 20 hours
- Loc 6 Fan running too slow for more than 60 seconds
- Loc 7 Fan running too fast for more than 60 seconds
- Loc 8 Internal software fault
- Loc 9 EEPROM contents out of date
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.