Glow Brand · Boiler
Loc 5 Fan not running for more than 60 seconds
What the control is telling you
The measured fan speed never reached the target within 60 seconds.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Loose or poor line, neutral or ground connection to the boiler, or a bad internal ground
- Loose fan wiring at the fan or ICB
- Damaged harness
- Failed fan
Test and repair steps
- Check line, neutral and ground to the boiler and internal grounds.
- Check the fan connector at the fan and at the ICB.
- Replace the harness.
- Replace the fan.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
- Loc 3 Safety relay fault
- Loc 33 Low water cut-off circuit open
- Loc 38 Blocked flue switch tripped more than 3 times in 24 h
- Loc 4 Blocking error lasted over 20 hours
- Loc 6 Fan running too slow for more than 60 seconds
- Loc 7 Fan running too fast for more than 60 seconds
- Loc 8 Internal software fault
- Loc 9 EEPROM contents out of date
Sequence of operation
What the unit does around this code, step by step.
- Ignition and retry · Ignition
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.62. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.