Loc 38 Blocked flue switch tripped more than 3 times in 24 h

High severity Glow B85/B120/B160

What the control is telling you

The blocked flue pressure switch opened more than three times in a day.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Vent blockage
  • Moisture or condensate in the silicone tubing to the flue switch
  • Failed blocked flue switch
  • Open wiring harness

Test and repair steps

  1. Check venting for blockages.
  2. Check the silicone tubing to the flue switch for moisture or condensate (Fig. 15.5).
  3. Check continuity across the blocked flue switch terminals. No continuity: replace the switch and press RESET.
  4. If the switch is good, check the harness for continuity; replace the harness if open and press RESET.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Models that show this code

3 models in Glow B85/B120/B160

B120B160B85

Other codes on the same units

  • Loc 22 Three flame failures in one demand
  • Loc 23 Error code memory corrupted
  • Loc 3 Safety relay fault
  • Loc 33 Low water cut-off circuit open
  • Loc 4 Blocking error lasted over 20 hours
  • Loc 5 Fan not running for more than 60 seconds
  • Loc 6 Fan running too slow for more than 60 seconds
  • Loc 7 Fan running too fast for more than 60 seconds

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.