Glow Brand · Boiler

Loc 2 Gas valve relay fault

High severity Glow B85/B120/B160

What the control is telling you

The control saw a problem in the gas valve electrical circuit and locked out.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Loose gas valve harness connection
  • Loose or poor line, neutral or ground connection to the boiler, or a bad internal ground
  • Electrical noise nearby (welders, large pump drives)
  • Failed ICB

Test and repair steps

  1. Check the gas valve wiring harness for a loose plug.
  2. Check line, neutral and ground at the boiler and the internal ground connections.
  3. Remove sources of electrical noise on the same circuit.
  4. If nothing is found, replace the ICB.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Models that show this code

3 models in Glow B85/B120/B160

B120B160B85

Other codes on the same units

  • Loc 16 Flue temperature too high
  • Loc 17 Internal software fault
  • Loc 18 Internal software fault
  • Loc 19 Internal software fault
  • Loc 20 Flame still present 10 s after gas valve closed
  • Loc 21 Flame detected before ignition
  • Loc 22 Three flame failures in one demand
  • Loc 23 Error code memory corrupted

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.62. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.