Glow Brand · Boiler

Loc 20 Flame still present 10 s after gas valve closed

High severity Glow B85/B120/B160

What the control is telling you

The flame sensor still saw flame ten seconds after the valve was told to close.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Ionization electrode shorted to ground
  • Ignition electrode shorted to ground
  • Blocked condensate drain or trap
  • Gas valve not closing fully

Test and repair steps

  1. Watch that the flame drops out right after a demand ends.
  2. Check the ionization electrode for a short to ground; replace if needed.
  3. Check the ignition electrode for a short to ground; replace if needed.
  4. Clear the condensate drain and trap.
  5. If the flame really stays on, the gas valve is leaking through: replace it.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Models that show this code

3 models in Glow B85/B120/B160

B120B160B85

Other codes on the same units

  • Loc 17 Internal software fault
  • Loc 18 Internal software fault
  • Loc 19 Internal software fault
  • Loc 2 Gas valve relay fault
  • Loc 21 Flame detected before ignition
  • Loc 22 Three flame failures in one demand
  • Loc 23 Error code memory corrupted
  • Loc 3 Safety relay fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.63. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.