Glow Brand · Boiler
init Display starting up
What the display is showing
Shown with a moving bar right after power-up while the display collects data from the ignition control board. Normal.
Applies to: B85, B120, B160 (NG and LP)
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
- Loc 4 Blocking error lasted over 20 hours
- Loc 5 Fan not running for more than 60 seconds
- Loc 6 Fan running too slow for more than 60 seconds
- Loc 7 Fan running too fast for more than 60 seconds
- Loc 8 Internal software fault
- Loc 9 EEPROM contents out of date
- dAir De-air sequence running
- tESt System test active
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, 11.2 p.51. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.