Err 105 CH supply over 180 F (82 C)

Medium severity Glow B85/B120/B160

What the control is telling you

The supply sensor read above 180 F. The burner is blocked until the water cools.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Pump not running
  • Low flow through the boiler
  • Supply or return sensor fault
  • System pressure under 10 psi

Test and repair steps

  1. Check the CH, DHW and primary pumps.
  2. Confirm adequate flow through the boiler.
  3. Compare supply and return sensor readings while running.
  4. Make sure system pressure is above 10 psi.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Models that show this code

3 models in Glow B85/B120/B160

B120B160B85

Other codes on the same units

  • Err 101 Internal software error (blocking)
  • Err 102 Internal software error (blocking)
  • Err 103 Internal software error (blocking)
  • Err 104 Internal software error (blocking)
  • Err 106 Internal software error (blocking)
  • Err 107 Internal software error (blocking)
  • Err 108 Internal software error (blocking)
  • Err 109 Internal software error (blocking)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.2 p.64. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.