Glow Brand · Boiler

ALEg Anti-legionella run

Normal status Glow B85/B120/B160

What the display is showing

In DHW mode 1 the control makes sure the tank reaches its maximum temperature at least once every 168 hours; if not, it fires and runs the pump to do so. The faucet icon blinks and the tank temperature shows.

Applies to: B85, B120, B160 (NG and LP)

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Other codes on the same units

  • AttE Warning prefix
  • AttE 202 Unknown appliance model selected
  • AttE 204 Outdoor sensor open or shorted
  • CodE Installer password prompt
  • Err Blocking error prefix
  • Err 100 Internal software error (blocking)
  • Err 101 Internal software error (blocking)
  • Err 102 Internal software error (blocking)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, 11.10 p.60. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.