Glow Brand · Boiler
AttE 202 Unknown appliance model selected
What the control is telling you
Parameter 2.138 (appliance setting) holds a value the control does not recognise. The burner may still run but with reduced function.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Appliance setting 2.138 set outside 50-55
Test and repair steps
- Enter the installer menu and set 2.138 to the value for the model and vent material (50-55, Table 11.7).
- Hold RESET to clear the warning.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.3 p.66. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.