Glow Brand · Boiler
AttE 204 Outdoor sensor open or shorted
What the control is telling you
The outdoor temperature sensor on terminals 3 and 4 reads open or shorted. The boiler keeps running without outdoor reset.
Applies to: B85, B120, B160 (NG and LP)
Likely causes
- Sensor wiring
- Failed outdoor sensor
- CH mode 1 or 2 selected with no sensor fitted
Test and repair steps
- Measure the sensor about 10,000 ohm at 77 F (25 C).
- If the resistance is right, check the wiring to terminals 3 and 4.
- Replace the sensor, or set CH mode 0 if no outdoor sensor is used.
Settings for these units
Maintenance intervals · Glow B85/B120/B160
| Item | When |
|---|---|
| Annual inspection by a technician | Every year (warranty) |
| Relief valve try-lever test | Annually |
| LWCO test | Annually |
| Condensate trap clean | Annually (14.3) |
| Heat exchanger combustion-side wash | Annually or when combustion drifts (14.4) |
| Burner door silicone gasket | Replace if damaged or after 2 years |
| Service reminder | 2.203 on, interval 2.204 (default 1000 days) |
Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.3 p.66. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.