Glow Brand · Boiler

Loc 15 High limit exceeded (203 F / 95 C)

High severity Glow B85/B120/B160

What the control is telling you

The supply water went past the high temperature limit.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • Primary, CH or DHW pump not running
  • Not enough flow through the heat exchanger
  • High limit switch contact or continuity problem
  • Supply or return sensor reading wrong
  • System pressure below 10 psi
  • Heat exchanger micro-fuse open (HX went above 336 F / 169 C)
  • Tank sensor or aquastat wiring problem
  • Secondary pump not running or turning the wrong way

Test and repair steps

  1. Confirm the primary, CH and DHW pumps run.
  2. Confirm there is enough flow through the boiler (minimum flow table).
  3. Check the high limit switch contact and continuity.
  4. Compare supply and return sensor readings while running.
  5. Make sure system pressure is above 10 psi.
  6. Check the heat exchanger micro-fuse for continuity. If it is open the HX overheated past 336 F and must be replaced.
  7. If an indirect tank is used, check its sensor/aquastat wiring and the secondary pump direction.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Other codes on the same units

  • Loc 1 Ignition failed three times in a row
  • Loc 10 Wrong safety parameters in EEPROM
  • Loc 11 Internal software fault
  • Loc 12 Internal software fault
  • Loc 16 Flue temperature too high
  • Loc 17 Internal software fault
  • Loc 18 Internal software fault
  • Loc 19 Internal software fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.1 p.62. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.