Glow Brand · Boiler

Err 162 Low water pressure under 10 psi (FILL)

Medium severity Glow B85/B120/B160

What the control is telling you

Pressure dropped below 10 psi (0.7 bar); the error shows immediately together with FILL.

Applies to: B85, B120, B160 (NG and LP)

Likely causes

  • System pressure too low
  • Dirty or failed pressure sensor
  • Pressure sensor cable

Test and repair steps

  1. Raise system pressure to at least 16 psi (1.1 bar) and cycle power.
  2. If the external gauge shows over 20 psi, inspect the pressure sensor and cable; clean a dirty sensor gently with a calcium/rust remover.
  3. Replace the pressure sensor if needed.

Settings for these units

Maintenance intervals · Glow B85/B120/B160

ItemWhen
Annual inspection by a technicianEvery year (warranty)
Relief valve try-lever testAnnually
LWCO testAnnually
Condensate trap cleanAnnually (14.3)
Heat exchanger combustion-side washAnnually or when combustion drifts (14.4)
Burner door silicone gasketReplace if damaged or after 2 years
Service reminder2.203 on, interval 2.204 (default 1000 days)

Operating pressure should sit 5 psi under the relief valve rating (max 25 psig on a 30 psi valve); water never above 180 F.

Other codes on the same units

  • Err 129 DHW tank temperature sensor shorted
  • Err 130 Flue temperature sensor shorted
  • Err 134 Too many resets in a short time
  • Err 156 Blocked flue switch open
  • FILL Low water pressure prompt
  • Loc Lockout prefix
  • Loc 0 Internal software fault
  • Loc 1 Ignition failed three times in a row

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Glow Brand B85/B120/B160 Installation & Operation Manual V20231025, Table 12.2 p.65. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.