Goodman heat pump error codes

42 codes (41 faults, 1 normal display and menu code).

CodeMeaningSeverity / type
01Low side fault or low pressure switch tripHigh
02High side fault or high pressure switch tripHigh
03Short cyclingMedium
04Locked rotorCritical
05Open circuit - compressor off over 4 hoursHigh
07Open run circuitCritical
09Low 24 V control voltageMedium
A2Outdoor air temperature sensor faultMedium
A3Outdoor coil temperature sensor faultHigh
b0Indoor blower not running when it should beHigh
b9Indoor airflow lower than requestedMedium
d0No shared data on the networkHigh
d1Invalid shared data on the networkHigh
d2System mismatch - indoor unit cannot supply required airflowMedium
d3Configuration mismatch - shared data does not match hardwareHigh
d4Shared data from the loader rejectedHigh
E5Outdoor control low-voltage fuse openHigh
H8High line voltageHigh
L1Lockout - low pressure switch tripped 3 timesHigh
L2Lockout - high pressure switch tripped 3 timesHigh
L6Lockout - open start circuit detected 4 timesCritical
L7Lockout - open run circuit detected 4 timesCritical
L8Low line voltageHigh
P0Compressor protector openHigh
CoreSense 1Yellow 1 flash - long run time (low side)Medium
CoreSense 2Pressure trip - yellow 2 flashes (red 2 = lockout)High
CoreSense 3Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)Medium
CoreSense 4Locked rotor - yellow 4 (red 4 = lockout)Critical
CoreSense 5Moderate run trip - yellow 5 (red 5 = lockout)High
CoreSense 9Red 9 flashes - PROT output overcurrentHigh
CoreSense solid redSolid red TRIP - call present but compressor not runningHigh
CoreSense solid yellowSolid yellow RUN - module powered, operating normallyNormal status
EEOutdoor control fault - compressor relay contacts weldedHigh
Yellow 1 flashLow side fault / low pressure trip / low pressure lockout (older ComfortNet board)High
Yellow 2 flashesHigh side fault / high pressure trip / high pressure lockout (older ComfortNet board)High
Yellow 3 flashesShort cycling (older ComfortNet board)Medium
Yellow 4 flashesLocked rotor (older ComfortNet board)Critical
Yellow 5 flashesOpen circuit (older ComfortNet board)High
Yellow 6 flashesOpen start circuit / lockout (older ComfortNet board)Critical
Yellow 7 flashesOpen run circuit / lockout (older ComfortNet board)Critical
Yellow 8 flashesLow or high line voltage (older ComfortNet board)High
Yellow ON + Red ONCompressor protector open (older ComfortNet board)High

Models covered

ALZS4BA**10AAALZS4NA**10AAALZS5BA**10AAANZ130181ANZ130241ANZ130301ANZ130361ANZ130421ANZ130481ANZ130601ANZ140181ANZ140241ANZ140301ANZ140361ANZ140421ANZ140481ANZ140491ANZ140601ASZ130181ASZ130241ASZ130301ASZ130361ASZ130421ASZ130481ASZ130601ASZ140181ASZ140241ASZ140301ASZ140361ASZ140381ASZ140421ASZ140481ASZ140491ASZ140601ASZ160181ASZ160241ASZ160301ASZ160361ASZ160421ASZ160481ASZ160601ASZ180361ASZ180481ASZ180601ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601ASZH5***10DSZ160241DSZ160361DSZ160481DSZ160601DSZ180361DSZ180481DSZ180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GLZS4BA**10AAGLZS4MA**10AAGLZS5BA**10AAGSZ110903GSZ110904GSZ111203GSZ111204GSZ130181GSZ130191GSZ130241GSZ130251GSZ130301GSZ130311GSZ130361GSZ130363GSZ130371GSZ130421GSZ130481GSZ130483GSZ130484GSZ130601GSZ140181GSZ140241GSZ140301GSZ140361GSZ140371GSZ140421GSZ140481GSZ140491GSZ140601GSZ160181GSZ160241GSZ160301GSZ160361GSZ160421GSZ160481GSZ160601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601GSZH5***10SSZ140181SSZ140191SSZ140241SSZ140251SSZ140301SSZ140311

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.