Goodman · Heat pump

E5 Outdoor control low-voltage fuse open

High severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

The 24 V fuse on the outdoor control has blown, so the A/C or heat pump does not run.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Short to ground or between conductors in the low-voltage wiring

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Find the short first check thermostat/communication wires for nicks, pinches against sheet metal, and wiring at the contactor coil, reversing valve and pressure switches.
  3. Replace the fuse only with a 3 A automotive (blade) fuse.
  4. Restore power and confirm the code clears; if the fuse blows again, isolate circuits one at a time until the short is found.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • d1 Invalid shared data on the network
  • d2 System mismatch - indoor unit cannot supply required airflow
  • d3 Configuration mismatch - shared data does not match hardware
  • d4 Shared data from the loader rejected
  • H8 High line voltage
  • L1 Lockout - low pressure switch tripped 3 times
  • L2 Lockout - high pressure switch tripped 3 times
  • L6 Lockout - open start circuit detected 4 times

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.