Goodman · Heat pump

L2 Lockout - high pressure switch tripped 3 times

High severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

The high pressure switch opened 3 times in one thermostat call and the control locked out the outdoor unit. (The manual's symptom column says low pressure switch here - treat as a misprint; the fault name is high pressure lockout.)

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Dirty or blocked outdoor coil
  • Outdoor fan motor not running
  • Outdoor fan wiring or capacitor failure
  • Faulty high pressure switch

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Clean the outdoor coil and clear anything blocking air to or from the unit.
  3. Check the outdoor fan motor runs; check its wiring and run capacitor and replace failed parts.
  4. Test the high pressure switch (opens 610 +/- 10 psig, closes 420 +/- 25 psig).
  5. To reset a lockout, interrupt the 24 VAC supply to the outdoor control (power cycle the low voltage), then retest.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • d4 Shared data from the loader rejected
  • E5 Outdoor control low-voltage fuse open
  • H8 High line voltage
  • L1 Lockout - low pressure switch tripped 3 times
  • L6 Lockout - open start circuit detected 4 times
  • L7 Lockout - open run circuit detected 4 times
  • L8 Low line voltage
  • P0 Compressor protector open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.