Goodman · Heat pump

d2 System mismatch - indoor unit cannot supply required airflow

Medium severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

In a communicating system the outdoor unit needs more airflow than the indoor unit can deliver, or the shared data is incompatible / missing values. The unit may not run, or runs at reduced capacity or on low stage only.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Indoor unit too small for the outdoor unit
  • Shared data not compatible with the system or missing parameters

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check model numbers of both units against the approved match-ups.
  3. Verify the shared data matches the exact model; reload it with the BTSDL01 if needed.
  4. Plug the BTSDL01 in BEFORE turning power on; after the data loads, turn power off before unplugging it.
  5. If the system cannot be run as communicating, wire it as a legacy 24 V system instead.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • b0 Indoor blower not running when it should be
  • b9 Indoor airflow lower than requested
  • d0 No shared data on the network
  • d1 Invalid shared data on the network
  • d3 Configuration mismatch - shared data does not match hardware
  • d4 Shared data from the loader rejected
  • E5 Outdoor control low-voltage fuse open
  • H8 High line voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.