Goodman · Heat pump

Yellow 2 flashes High side fault / high pressure trip / high pressure lockout (older ComfortNet board)

High severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

Yellow LED 2 flashes. Green OFF = high side fault (4 protector trips, average run 1-15 min). Green ON + red OFF = high pressure switch opened. Green ON + red ON = high pressure lockout. Same meaning as 02 / L2 on newer boards.

Applies to: Earlier ComfortNet condensers/heat pumps with the PCBHR101-103 or PBBGR101-102 outdoor control (green, yellow and red status LEDs) - ASXC/DSXC/ASZC/DSZC revisions before the PCBHR104 change

Likely causes

  • Dirty or blocked outdoor coil
  • Outdoor fan motor not running
  • Outdoor fan wiring or capacitor failure

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Clean the outdoor coil and clear anything blocking air to or from the unit.
  3. Check the outdoor fan motor runs; check its wiring and run capacitor and replace failed parts.
  4. Test the high pressure switch (opens 610 +/- 10 psig, closes 420 +/- 25 psig).
  5. High side fault clears after 4 normal cycles; lockout needs a 24 VAC power cycle.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, diagnostic/status LED table (PCBHR101-103, PBBGR101-102) p.65-69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.