Goodman · Heat pump
EE Outdoor control fault - compressor relay contacts welded
What the control is telling you
The outdoor control has detected that its own compressor relay contacts are stuck closed (board misoperation).
Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18
Likely causes
- Welded compressor relay contacts on the outdoor control
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Confirm the code is steady after a power cycle.
- Replace the outdoor control with the correct replacement part and reload or verify shared data if needed.
- Check the contactor and compressor circuit for the cause of the high relay load before returning the system to service.
Models that show this code
24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC
Other codes on the same units
- Yellow 1 flash Low side fault / low pressure trip / low pressure lockout (older ComfortNet board)
- Yellow 2 flashes High side fault / high pressure trip / high pressure lockout (older ComfortNet board)
- Yellow 3 flashes Short cycling (older ComfortNet board)
- Yellow 4 flashes Locked rotor (older ComfortNet board)
- Yellow 5 flashes Open circuit (older ComfortNet board)
- Yellow 6 flashes Open start circuit / lockout (older ComfortNet board)
- Yellow 7 flashes Open run circuit / lockout (older ComfortNet board)
- Yellow 8 flashes Low or high line voltage (older ComfortNet board)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.