Goodman · Heat pump
CoreSense 3 Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
What the control is telling you
Compressor ran 12 s to 15 min, then tripped for 35 s to 7 min - usually a pressure switch cycling. Red 3 flashes = lockout. The quick reference table says 4 in a row or 10 total; the detailed table says 10 short cycles in a row.
Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units
Likely causes
- Intermittent thermostat demand
- Faulty time delay relay or control board
- Low or high pressure switch cycling
Test and repair steps
- Check thermostat and wiring for intermittent contact.
- Check the time delay relay or defrost board.
- Find out why a pressure switch is cycling (see codes 1 and 2).
- Clear the lockout after repair and recheck.
Models that show this code
122 models in Goodman/Amana R-32 GLZS/ALZS, Goodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)
Other codes on the same units
- CoreSense 1 Yellow 1 flash - long run time (low side)
- CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
- CoreSense 4 Locked rotor - yellow 4 (red 4 = lockout)
- CoreSense 5 Moderate run trip - yellow 5 (red 5 = lockout)
- CoreSense 9 Red 9 flashes - PROT output overcurrent
- CoreSense solid red Solid red TRIP - call present but compressor not running
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.