Goodman · Heat pump

CoreSense 1 Yellow 1 flash - long run time (low side)

Medium severity Goodman/Amana R-32 GLZS/ALZSGoodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)

What the control is telling you

Compressor has run more than 18 hours straight, showing low capacity from a low-side problem. This code is disabled in heat pump heating mode.

Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units

Likely causes

  • Low charge
  • Indoor blower not running (relay, capacitor, motor, wiring, indoor board, open thermostat wire)
  • Frozen evaporator (low suction, low set point, blocked coil/filter/ducts)
  • Metering device stuck or TXV bulb badly mounted
  • Restricted liquid line drier
  • Thermostat short or poor location

Test and repair steps

  1. Check charge and look for leaks.
  2. Verify the indoor blower and its control; clean filter and coil, open registers.
  3. Check TXV bulb size, location and contact; check for a stuck TXV or piston.
  4. Check the drier for a temperature drop.
  5. Check thermostat sub-base, wiring and location.

Models that show this code

122 models in Goodman/Amana R-32 GLZS/ALZS, Goodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)

ALZS4BA**10AAALZS4NA**10AAALZS5BA**10AAANZ130181ANZ130241ANZ130301ANZ130361ANZ130421ANZ130481ANZ130601ANZ140181ANZ140241ANZ140301ANZ140361ANZ140421ANZ140481ANZ140491ANZ140601ASZ130181ASZ130241ASZ130301ASZ130361ASZ130421ASZ130481ASZ130601ASZ140181ASZ140241ASZ140301ASZ140361ASZ140381ASZ140421ASZ140481ASZ140491ASZ140601ASZ160181ASZ160241ASZ160301ASZ160361ASZ160421ASZ160481ASZ160601ASZ180361ASZ180481ASZ180601ASZH5***10DSZ160241DSZ160361DSZ160481DSZ160601DSZ180361DSZ180481DSZ180601GLZS4BA**10AAGLZS4MA**10AAGLZS5BA**10AAGSZ110903GSZ110904GSZ111203GSZ111204GSZ130181

Other codes on the same units

  • CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
  • CoreSense 3 Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
  • CoreSense 4 Locked rotor - yellow 4 (red 4 = lockout)
  • CoreSense 5 Moderate run trip - yellow 5 (red 5 = lockout)
  • CoreSense 9 Red 9 flashes - PROT output overcurrent
  • CoreSense solid red Solid red TRIP - call present but compressor not running

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.