Goodman · Heat pump
CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
What the control is telling you
Compressor ran 12 s to 15 min, then tripped for longer than 7 min (discharge pressure too high or overload). Red 2 flashes with yellow off = locked out after 4 trips in a row or 10 total.
Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units
Likely causes
- Outdoor fan not running (capacitor, wiring, motor)
- High head pressure: high pressure switch, overcharge, non-condensables
- Dirty, blocked or damaged outdoor coil
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Check outdoor fan capacitor, wiring and motor.
- Clean the outdoor coil.
- Check charge for overcharge and for non-condensables; check the high pressure switch.
- After the repair, reset the module lockout (cycle power / reset button) and verify.
Models that show this code
122 models in Goodman/Amana R-32 GLZS/ALZS, Goodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)
Other codes on the same units
- CoreSense 1 Yellow 1 flash - long run time (low side)
- CoreSense 3 Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
- CoreSense 4 Locked rotor - yellow 4 (red 4 = lockout)
- CoreSense 5 Moderate run trip - yellow 5 (red 5 = lockout)
- CoreSense 9 Red 9 flashes - PROT output overcurrent
- CoreSense solid red Solid red TRIP - call present but compressor not running
- CoreSense solid yellow Solid yellow RUN - module powered, operating normally
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.