Goodman · Heat pump

02 High side fault or high pressure switch trip

High severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

Code 02 covers two high-side events: (1) four protector trips in a row with an average run between 1 and 15 minutes while both pressure switches are closed; (2) the high pressure switch has opened - compressor and fan off with a call present.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Dirty or blocked outdoor coil
  • Outdoor fan motor not running
  • Outdoor fan wiring or capacitor failure
  • Faulty high pressure switch (switch-trip version)

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Clean the outdoor coil and clear anything blocking air to or from the unit.
  3. Check the outdoor fan motor runs; check its wiring and run capacitor and replace failed parts.
  4. Check for overcharge or non-condensables if the coil and fan are fine.
  5. Test the high pressure switch it should open at 610 psig (plus or minus 10) and close at 420 psig (plus or minus 25).
  6. High side fault version clears after 4 normal cycles in a row, or by power cycling the 24 VAC.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • 01 Low side fault or low pressure switch trip
  • 03 Short cycling
  • 04 Locked rotor
  • 05 Open circuit - compressor off over 4 hours
  • 07 Open run circuit
  • 09 Low 24 V control voltage
  • A2 Outdoor air temperature sensor fault
  • A3 Outdoor coil temperature sensor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84; pressure switch test p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.