Goodman · Heat pump

01 Low side fault or low pressure switch trip

High severity Goodman/Amana ComfortNet ASZC/GSZC/DSZC

What the control is telling you

Code 01 covers two low-side events: (1) four compressor protector trips in a row with an average run time over 3 hours between trips (very long runs, compressor on high with fan on low); (2) the low pressure switch has opened - compressor and outdoor fan are off while the thermostat still calls.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Low refrigerant charge
  • Restricted liquid line (drier, kinked line)
  • Indoor blower motor failed or not running
  • Thermostat set very low
  • Faulty low pressure switch (switch-trip version)

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check charge with superheat/subcooling and correct it; leak check if low.
  3. Look for a temperature drop across the liquid line drier or any kinks - repair restrictions.
  4. Confirm the indoor blower runs at the right speed and filters/coil are clean.
  5. Check the thermostat set point.
  6. Test the low pressure switch it should open at about 21 psig and reset near 50 psig; replace if it does not.
  7. Low side fault version clears after 30 normal cycles in a row, or by power cycling the 24 VAC to the control.

Models that show this code

24 models in Goodman/Amana ComfortNet ASZC/GSZC/DSZC

ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601

Other codes on the same units

  • 02 High side fault or high pressure switch trip
  • 03 Short cycling
  • 04 Locked rotor
  • 05 Open circuit - compressor off over 4 hours
  • 06 Open start circuit
  • 07 Open run circuit
  • 08 No line voltage
  • 09 Low 24 V control voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84; pressure switch test p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.