Daikin furnace error codes

38 codes (25 faults, 13 normal display and menu codes), plus 1 settings tables.

CodeMeaningSeverity / type
1ACCooling, low stageNormal status
2ACCooling, high stageNormal status
A2uR-32 leak function testMenu / mode display
E10Grounding fault / poor neutral connectionHigh
E11Flame rollout switch openCritical
EE0Lockout - too many ignition retries (3)High
EE1Pressure switch closed at start of heating cycleMedium
EE2Pressure switch did not close (inducer runs, no ignition)Medium
EE3High (primary) limit openHigh
EE4Flame sensed with no call for heatCritical
EE5Open fuse (short in low voltage wiring)Medium
EE6Low flame signalLow
EE8High-stage pressure switch closed at start of heating cycleMedium
EE9High-stage pressure switch did not closeMedium
F10Last 10 faultsMenu / mode display
gH1Gas heat, low stageNormal status
gH2Gas heat, high stageNormal status
L6FStored faults (view and clear)Menu / mode display
CrCode release numberMenu / mode display
EAFR-32 sensor communication lost - mitigation modeHigh
EALR-32 refrigerant leak detected - mitigation modeCritical
EASR-32 sensor fault - mitigation modeHigh
EArA2L relay fault - mitigation modeHigh
EEAReversed line polarity or grounding errorHigh
EECInternal gas valve error - valve energized when it should not beCritical
EEEInternal control fault (IRQ loss)High
EEHTwinning errorLow
EEJInducer relay errorHigh
EELIgniter relay / igniter circuit faultHigh
EEbExternal gas valve error - valve not energized when it should beHigh
EEnIgniter openHigh
EOLOEM test modeMenu / mode display
EbLLow circulator current - hard lockoutHigh
EbUUnexpected circulator current - hard lockoutHigh
ErrActive alarm menuMenu / mode display
FAnContinuous fanNormal status
IdLIdle - no callNormal status
rFdReset to factory defaultsMenu / mode display

Settings and specs

Normal status displays (7-segment)

Installer menu · Daikin DR96TN/DD96TN

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat, low stagegH1
Gas heat, high stagegH2
Factory (OEM) test modeEOL
  • These are normal operating displays, not fault codes.

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Status Codes p.27

Models covered

DD96TN0403BNDD96TN0603BNDD96TN0803BNDD96TN1005CNDR96TN0303ANDR96TN0403ANDR96TN0603ANDR96TN0603BNDR96TN0803BNDR96TN0804CNDR96TN1004CNDR96TN1005CNDR96TN1205DN

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.