Daikin · Furnace

EE5 Open fuse (short in low voltage wiring)

Medium severity Daikin DR96TN/DD96TN

What the control is telling you

The low-voltage fuse on the control board is open, usually because of a short in the 24 V wiring (thermostat, outdoor unit or accessory wiring).

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Short in thermostat, outdoor unit or accessory 24 V wiring
  • Fuse failed

Test and repair steps

  1. Measure R to C if the transformer secondary shows 24 VAC but R-C on the terminal board reads only about 13 VAC, the board fuse is blown.
  2. Before replacing the fuse, find the short: disconnect thermostat and outdoor unit wires and check each run for a short to ground or between conductors.
  3. Repair the shorted wire (often a nicked thermostat cable or a shorted contactor coil), then replace the fuse with one of the same rating.
  4. Restore power and run heat and cool calls to confirm.

Settings for these units

Normal status displays (7-segment) · Daikin DR96TN/DD96TN

ModeDisplay
IdleIdL
Continuous fanFAn
Cooling, low stage1AC
Cooling, high stage2AC
Gas heat, low stagegH1
Gas heat, high stagegH2
Factory (OEM) test modeEOL

These are normal operating displays, not fault codes.

Models that show this code

13 models in Daikin DR96TN/DD96TN

DD96TN0403BNDD96TN0603BNDD96TN0803BNDD96TN1005CNDR96TN0303ANDR96TN0403ANDR96TN0603ANDR96TN0603BNDR96TN0803BNDR96TN0804CNDR96TN1004CNDR96TN1005CNDR96TN1205DN

Other codes on the same units

  • EE1 Pressure switch closed at start of heating cycle
  • EE2 Pressure switch did not close (inducer runs, no ignition)
  • EE3 High (primary) limit open
  • EE4 Flame sensed with no call for heat
  • EE6 Low flame signal
  • EE8 High-stage pressure switch closed at start of heating cycle
  • EE9 High-stage pressure switch did not close
  • F10 Last 10 faults

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.