Daikin · Furnace
EE9 High-stage pressure switch did not close
What the control is telling you
On a two-stage furnace the high-stage pressure switch does not close when the inducer goes to high speed. The furnace keeps running on low stage only. Flowcharts call this code E9.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Pressure switch hose blocked, pinched or connected wrong
- Blocked flue or intake, or vent too long / too many elbows
- Blocked condensate drain
- Weak inducer on high speed
- Bad switch or loose wiring
Test and repair steps
- Inspect the high-stage pressure switch hose and repair or replace it.
- Check the flue and intake piping for blockage and for correct length, elbows and termination.
- Check the drain system and front cover pressure switch.
- With a manometer, compare the negative pressure at high inducer speed with the switch rating; enough vacuum but open switch = replace the switch.
- Check inducer voltage and amps; replace the inducer if it cannot pull enough vacuum.
- Tighten or correct the pressure switch wiring and retest a high-fire call.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code E1, E2, E8, E9 flowchart p.36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.