Daikin · Furnace
L6F Stored faults (view and clear)
What the display is showing
Label used in the troubleshooting chart for viewing and clearing stored fault codes. The wiring diagram note says the last 6 faults can also be recalled by pressing the switch for more than 2 seconds in standby with no thermostat call.
Applies to: Daikin DR96TN/DD96TN two-stage furnaces
What to do
- Press the left or right switch until L6F shows
- Press the center switch and read the stored faults
- To erase them, keep the center switch pressed for 5 to 30 seconds; the display blinks three dashes three times, then shows L6F again
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin DR96TN-DD96TN service RSD6612304 (05-2024), LED Display Menu p.26 and troubleshooting chart p.28. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.