Daikin · Furnace
EAS R-32 sensor fault - mitigation mode
What the control is telling you
The R-32 sensor reported an internal fault. The furnace goes into mitigation mode (no gas heat, fan only).
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Failed R-32 sensor
Test and repair steps
- Check the R-32 sensor and its wiring.
- Replace the R-32 sensor.
- Cycle power and confirm normal operation.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- L6F Stored faults (view and clear)
- Cr Code release number
- EAF R-32 sensor communication lost - mitigation mode
- EAL R-32 refrigerant leak detected - mitigation mode
- EAr A2L relay fault - mitigation mode
- EEA Reversed line polarity or grounding error
- EEC Internal gas valve error - valve energized when it should not be
- EEE Internal control fault (IRQ loss)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; R-32 Information p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.