Daikin · Furnace
EAL R-32 refrigerant leak detected - mitigation mode
What the control is telling you
The R-32 sensor on the indoor coil detected refrigerant. The furnace shuts off gas heat, runs the blower at maximum airflow and energizes the optional ventilation and alarm outputs. It returns to normal 5 minutes after the leak is no longer detected.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Refrigerant leak at the indoor coil or nearby line set
- A2L verification test (A2u menu) running
Test and repair steps
- Warning: R-32 is a mildly flammable (A2L) refrigerant - ventilate the area and keep ignition sources away.
- Check whether someone started the A2L verification test (A2u menu = yes); it ends after 5 minutes or when turned off.
- Leak-check the indoor coil and line set and repair the leak.
- Let the furnace finish its 5-minute post-leak fan run; it then drops the ventilation/alarm outputs and goes back to normal operation.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- gH2 Gas heat, high stage
- L6F Stored faults (view and clear)
- Cr Code release number
- EAF R-32 sensor communication lost - mitigation mode
- EAS R-32 sensor fault - mitigation mode
- EAr A2L relay fault - mitigation mode
- EEA Reversed line polarity or grounding error
- EEC Internal gas valve error - valve energized when it should not be
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; R-32 Information p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.