EAF R-32 sensor communication lost - mitigation mode
What the control is telling you
The furnace lost communication with the R-32 refrigerant sensor on the indoor coil and went into mitigation mode: gas heat stops and only the fan runs.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Furnace not paired with an R-32 cooling unit but A2L function still enabled
- R-32 sensor wire loose or unplugged
- Damaged sensor wire
- Failed R-32 sensor
Test and repair steps
- No R-32 system with this furnace? Turn the A2L function off: use left/right to reach A2E, press the center button, pick no, then confirm.
- Check that the R-32 sensor wire is plugged into the furnace control board and the sensor.
- Inspect the sensor wire for damage - it should run with the thermostat wires and away from the flue pipe and hot surfaces.
- Replace the R-32 sensor if wiring is good.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; R-32 Information p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.