Daikin · Furnace
EAF R-32 sensor communication lost - mitigation mode
What the control is telling you
The furnace lost communication with the R-32 refrigerant sensor on the indoor coil and went into mitigation mode: gas heat stops and only the fan runs.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Furnace not paired with an R-32 cooling unit but A2L function still enabled
- R-32 sensor wire loose or unplugged
- Damaged sensor wire
- Failed R-32 sensor
Test and repair steps
- No R-32 system with this furnace? Turn the A2L function off: use left/right to reach A2E, press the center button, pick no, then confirm.
- Check that the R-32 sensor wire is plugged into the furnace control board and the sensor.
- Inspect the sensor wire for damage - it should run with the thermostat wires and away from the flue pipe and hot surfaces.
- Replace the R-32 sensor if wiring is good.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; R-32 Information p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.