EAF R-32 sensor communication lost - mitigation mode

High severity Daikin DR96TN/DD96TN

What the control is telling you

The furnace lost communication with the R-32 refrigerant sensor on the indoor coil and went into mitigation mode: gas heat stops and only the fan runs.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Furnace not paired with an R-32 cooling unit but A2L function still enabled
  • R-32 sensor wire loose or unplugged
  • Damaged sensor wire
  • Failed R-32 sensor

Test and repair steps

  1. No R-32 system with this furnace? Turn the A2L function off: use left/right to reach A2E, press the center button, pick no, then confirm.
  2. Check that the R-32 sensor wire is plugged into the furnace control board and the sensor.
  3. Inspect the sensor wire for damage - it should run with the thermostat wires and away from the flue pipe and hot surfaces.
  4. Replace the R-32 sensor if wiring is good.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; R-32 Information p.10. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.