Daikin · Furnace
EE6 Low flame signal
What the control is telling you
The furnace runs normally but the flame-sense current is weak. If it keeps dropping the furnace will start losing flame and locking out.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Flame sensor coated or oxidized
- Flame sensor not positioned correctly in the flame
- Lazy burner flame from wrong gas pressure or poor combustion air
- Poor ground
Test and repair steps
- Put a DC microamp meter in series with the flame sensor wire and run a heat cycle: normal is 1 to 4 microamps.
- Clean the flame sensor with steel wool (an invisible coating acts as an insulator) and check that it sits in the flame.
- Check the burner flame it should be stable, soft and blue, not lifting or yellow.
- Compare manifold and inlet gas pressure with the rating plate and adjust if needed.
- Inspect the combustion air intake pipe is it blocked, and are its length, elbow count and termination correct?
- Check high-resistance connections and grounding in the flame sense circuit.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Checking Flame Sensor p.25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.