Daikin · Furnace
EE6 Low flame signal
What the control is telling you
The furnace runs normally but the flame-sense current is weak. If it keeps dropping the furnace will start losing flame and locking out.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Flame sensor coated or oxidized
- Flame sensor not positioned correctly in the flame
- Lazy burner flame from wrong gas pressure or poor combustion air
- Poor ground
Test and repair steps
- Put a DC microamp meter in series with the flame sensor wire and run a heat cycle: normal is 1 to 4 microamps.
- Clean the flame sensor with steel wool (an invisible coating acts as an insulator) and check that it sits in the flame.
- Check the burner flame it should be stable, soft and blue, not lifting or yellow.
- Compare manifold and inlet gas pressure with the rating plate and adjust if needed.
- Inspect the combustion air intake pipe is it blocked, and are its length, elbow count and termination correct?
- Check high-resistance connections and grounding in the flame sense circuit.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- EE2 Pressure switch did not close (inducer runs, no ignition)
- EE3 High (primary) limit open
- EE4 Flame sensed with no call for heat
- EE5 Open fuse (short in low voltage wiring)
- EE8 High-stage pressure switch closed at start of heating cycle
- EE9 High-stage pressure switch did not close
- F10 Last 10 faults
- gH1 Gas heat, low stage
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Checking Flame Sensor p.25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.