Daikin · Furnace

EE4 Flame sensed with no call for heat

Critical severity Daikin DR96TN/DD96TN

What the control is telling you

The control sees a flame signal when the gas valve should be closed. The inducer and circulator blower run continuously and the furnace will not operate.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Short to ground in the flame sensor or its wiring
  • Lingering burner flame
  • Gas valve closing slowly or leaking through

Test and repair steps

  1. Warning: if a flame is actually present with no call for heat, shut the manual gas valve immediately.
  2. Look into the burner compartment if there is no flame, the signal is false - check the flame sensor wire and insulator for a short to ground and repair it.
  3. If a flame lingers after the call ends, the gas valve is not closing properly - replace the gas valve.
  4. After repair, cycle power and confirm the inducer and blower stop at the end of the post-purge and fan-off delay.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.