EE4 Flame sensed with no call for heat
What the control is telling you
The control sees a flame signal when the gas valve should be closed. The inducer and circulator blower run continuously and the furnace will not operate.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Short to ground in the flame sensor or its wiring
- Lingering burner flame
- Gas valve closing slowly or leaking through
Test and repair steps
- Warning: if a flame is actually present with no call for heat, shut the manual gas valve immediately.
- Look into the burner compartment if there is no flame, the signal is false - check the flame sensor wire and insulator for a short to ground and repair it.
- If a flame lingers after the call ends, the gas valve is not closing properly - replace the gas valve.
- After repair, cycle power and confirm the inducer and blower stop at the end of the post-purge and fan-off delay.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.