EE1 Pressure switch closed at start of heating cycle
What the control is telling you
At the start of a heat call the (low-stage) pressure switch circuit is already closed before the inducer runs. The control will not start the ignition sequence. Flowcharts call this code E1.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Pressure switch contacts stuck closed
- Short in the pressure switch circuit wiring (to another wire or to ground)
Test and repair steps
- Turn off power, remove the wires from the pressure switch and check the contacts with an ohmmeter while the inducer is off - they must be open.
- If the contacts read closed with no vacuum applied, replace the pressure switch (on two-stage furnaces this is the low-stage switch).
- If the switch is open, trace the pressure switch circuit wiring for a short to another wire or to ground and repair it.
- Reconnect, cycle the thermostat and confirm the code clears.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code E1, E2, E8, E9 flowchart p.36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.