Daikin · Furnace
EE1 Pressure switch closed at start of heating cycle
What the control is telling you
At the start of a heat call the (low-stage) pressure switch circuit is already closed before the inducer runs. The control will not start the ignition sequence. Flowcharts call this code E1.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Pressure switch contacts stuck closed
- Short in the pressure switch circuit wiring (to another wire or to ground)
Test and repair steps
- Turn off power, remove the wires from the pressure switch and check the contacts with an ohmmeter while the inducer is off - they must be open.
- If the contacts read closed with no vacuum applied, replace the pressure switch (on two-stage furnaces this is the low-stage switch).
- If the switch is open, trace the pressure switch circuit wiring for a short to another wire or to ground and repair it.
- Reconnect, cycle the thermostat and confirm the code clears.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- A2u R-32 leak function test
- E10 Grounding fault / poor neutral connection
- E11 Flame rollout switch open
- EE0 Lockout - too many ignition retries (3)
- EE2 Pressure switch did not close (inducer runs, no ignition)
- EE3 High (primary) limit open
- EE4 Flame sensed with no call for heat
- EE5 Open fuse (short in low voltage wiring)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29; Error Code E1, E2, E8, E9 flowchart p.36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.