Daikin · Furnace
A2u R-32 leak function test
What the display is showing
Menu item that simulates an R-32 refrigerant leak so the installer can check the furnace response. It only works when no alarm or fault is active. After YES is chosen the control shows the leak code EAL, shuts off gas heat, energizes the optional ventilation and alarm outputs and runs the blower at maximum airflow. The test ends after 5 minutes, if a fault appears, or if the user turns it off.
Applies to: Daikin DR96TN/DD96TN two-stage furnaces
What to do
- Press the left or right switch until A2u shows
- Press the center switch, choose yes with the left or right switch
- Press the center switch to confirm and start the test
- Select no in the same menu to stop it early
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- 1AC Cooling, low stage
- 2AC Cooling, high stage
- E10 Grounding fault / poor neutral connection
- E11 Flame rollout switch open
- EE0 Lockout - too many ignition retries (3)
- EE1 Pressure switch closed at start of heating cycle
- EE2 Pressure switch did not close (inducer runs, no ignition)
- EE3 High (primary) limit open
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin DR96TN-DD96TN service RSD6612304 (05-2024), R-32 Information - A2L Verification p.10. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.