EEL Igniter relay / igniter circuit fault
What the control is telling you
The control detected a problem in the igniter circuit: wiring, a shorted or improperly connected igniter, poor ground, or a failed igniter relay on the board.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Wiring problem between control and igniter
- Shorted or improperly connected igniter
- Poor unit ground
- Igniter relay fault on the integrated control
Test and repair steps
- Check and correct the wiring and plug between the integrated control and the igniter.
- Ohm the igniter at room temperature (37-68 ohms silicon nitride; 30-300 ohms carbide mini igniter on 80% models); replace a shorted igniter.
- Verify the unit ground wire runs back to the panel and the ground connection is tight.
- During igniter warm-up, check for 115 VAC output at the control's igniter terminals; no output with a good igniter and wiring = replace the control board.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.