Daikin · Furnace
EEJ Inducer relay error
What the control is telling you
The control detected a fault in its inducer relay circuit. The furnace will not operate.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Failed inducer relay on the integrated control board
Test and repair steps
- Cycle power and retry to confirm the code returns.
- Check for 115 VAC from the control to the inducer during a heat call; with good wiring and no output, replace the integrated control board.
- If the inducer gets voltage but does not run, test the inducer motor windings (continuity between leads, none to ground) instead.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
- EEA Reversed line polarity or grounding error
- EEC Internal gas valve error - valve energized when it should not be
- EEE Internal control fault (IRQ loss)
- EEH Twinning error
- EEL Igniter relay / igniter circuit fault
- EEb External gas valve error - valve not energized when it should be
- EEn Igniter open
- EOL OEM test mode
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.