Daikin · Furnace

EbL Low circulator current - hard lockout

High severity Daikin DR96TN/DD96TN

What the control is telling you

After the heat-on delay the main blower motor draws much less current than expected. The furnace stops and goes to hard lockout.

Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready

Likely causes

  • Loose blower motor wiring
  • Burnt or failed blower motor

Test and repair steps

  1. Power off and check all blower motor connections (line plug and speed tap harness) at the motor and control.
  2. Check that the motor gets 115 VAC and a speed tap signal during a call.
  3. If wiring and supply are good and the motor does not run or draws little current, replace the blower motor.
  4. Reset by cycling power and run a full heat cycle.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.