Daikin · Furnace
EbL Low circulator current - hard lockout
What the control is telling you
After the heat-on delay the main blower motor draws much less current than expected. The furnace stops and goes to hard lockout.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Loose blower motor wiring
- Burnt or failed blower motor
Test and repair steps
- Power off and check all blower motor connections (line plug and speed tap harness) at the motor and control.
- Check that the motor gets 115 VAC and a speed tap signal during a call.
- If wiring and supply are good and the motor does not run or draws little current, replace the blower motor.
- Reset by cycling power and run a full heat cycle.
Settings for these units
Normal status displays (7-segment) · Daikin DR96TN/DD96TN
| Mode | Display |
|---|---|
| Idle | IdL |
| Continuous fan | FAn |
| Cooling, low stage | 1AC |
| Cooling, high stage | 2AC |
| Gas heat, low stage | gH1 |
| Gas heat, high stage | gH2 |
| Factory (OEM) test mode | EOL |
These are normal operating displays, not fault codes.
Models that show this code
13 models in Daikin DR96TN/DD96TN
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.