Carrier furnace error codes

96 codes (50 faults, 46 normal display and menu codes), plus 6 settings tables.

CodeMeaningSeverity / type
5,9Component test - gas valve communication check (59MN7C)Menu / mode display
10.1L1 polarity faultHigh
11No previous codeLow
12Blower on after power-up (normal)Low
12.1W (heat call) on at power upLow
13Limit circuit lockoutCritical
13.1Limit lockout - main limit open over 3 minutesHigh
14Ignition lockoutCritical
14.1Ignition lockout after 4 triesHigh
14.2Lockout - flame lost 3 times after 70 s of heatingHigh
14.3Lockout - 7 flame-loss events in one heat callHigh
15Blower motor lockoutHigh
21Gas heating lockoutCritical
21.124 VAC on gas valve when it should be offCritical
22Abnormal flame-proving signalCritical
22.1False flameCritical
23Pressure switch did not openMedium
23.1Main pressure switch stuck closedMedium
23.2Secondary pressure switch stuck closedMedium
24Secondary (24 V) fuse openMedium
24.1Fuse fault (24 V)High
25Invalid model selection or setup errorMedium
25.1No program in controlHigh
25.2Corrupted program fileHigh
25.3Twinned furnaces not identicalMedium
25.4Main program invalid, running on backupLow
25.5Installer settings corruptedLow
25.6Wrong program for this controlHigh
25.7Non-condensing program in condensing furnaceHigh
27.1Super plug program missing or corruptedMedium
27.2Super plug program missing or corruptedMedium
27.3Super plug program missing or corruptedMedium
31High-heat pressure switch or relay did not close or reopenedHigh
31.2Secondary pressure switch (HPS) openHigh
31.3Secondary pressure switch lockoutHigh
32Low-heat pressure switch did not close or reopenedHigh
32.1Main pressure switch (LPS) openHigh
33Limit circuit faultHigh
33.1Main limit circuit switch openHigh
34Ignition proving failureHigh
34.1Ignition fault during ignition trialsHigh
34.2Flame lost before blower on-delayMedium
34.3Flame lost after blower on-delayHigh
43Low-heat pressure switch open while high-heat switch closedHigh
45Control circuitry lockoutHigh
45.1Control failure - flame circuit / memory / sequenceHigh
45.2Control failure - gas valve relay will not closeHigh
45.3Control failure - EEPROM memoryHigh
46.1Momentary loss of powerLow
CF2Continuous fan (CF2 variant)Normal status
CF3Continuous fan (CF3 variant)Normal status
CL1Low cooling or heat pump (PG96VTA, 59MN7C)Normal status
CL2High cooling or heat pump (PG96VTA, 59MN7C)Normal status
Ht1Low-stage heating (PG96VTA)Normal status
Ht2High-stage heating (PG96VTA)Normal status
##.#Active status code shown as major.minor numberMenu / mode display
AirMenu: airflow (CFM) display on/offMenu / mode display
CLCooling or heat pump running (59SC6A)Normal status
CfnContinuous fanNormal status
ClrClear fault historyMenu / mode display
CodMenu: cool blower-off delayMenu / mode display
Component testComponent self-test modeMenu / mode display
CtMenu: component testMenu / mode display
CttMenu: cooling thermostat typeMenu / mode display
EndComponent test - endMenu / mode display
ErrComponent test could not startMenu / mode display
FLtMenu: last 7 faultsMenu / mode display
FnComponent test - blowerMenu / mode display
HSiComponent test - hot surface igniterMenu / mode display
HoDMenu: heat blower-off delayMenu / mode display
HpdHeat pump defrost - furnace heatingNormal status
HtHeating (59SC6A, 59MN7C menu: heating airflow setting)Normal status
Ht-%Heating at a percent firing rate (59MN7C)Normal status
HttMenu: heating thermostat typeMenu / mode display
LED OFFNo amber LED - no power to controlHigh
LED ONAmber LED steady onNormal status
PRGStartup display - model program numberNormal status
PUrComponent test - purge (inducer on)Menu / mode display
PriTwinning: primary furnaceMenu / mode display
Rapid FlashReversed 115-V polarity (or twinning phasing)High
SECTwinning: secondary furnaceMenu / mode display
Stored codesRecall stored status codesMenu / mode display
UPFDisplay set for upflowMenu / mode display
YEsReset confirmationMenu / mode display
bLrBlower running (secondary furnace / communicating system)Normal status
bStMenu: inducer boostMenu / mode display
dirMenu: display orientationMenu / mode display
dnFDisplay set for downflowMenu / mode display
iDlIdle - standby, no demandNormal status
inFMenu: program number and softwareMenu / mode display
nonNo faults storedMenu / mode display
rStMenu: reset to factory defaultsMenu / mode display
tStComponent test startedMenu / mode display
tnnMenu: twinningMenu / mode display
t°Menu: supply and return air temperature displayMenu / mode display
uErStartup display - software versionNormal status

Settings and specs

Filter sizes by casing width and filter cabinet

Filters · 59SC6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide(1) 16 x 25 x 3/4 in.(1) 20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide(1) 16 x 25 x 3/4 in.(1) 24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media
  • Side-return filters can differ in size - measure the existing filter.
  • Every return-air inlet needs a filter.
  • Airflow over 1800 CFM needs at least a 20 x 25 in. filter.

Source: Carrier 59SC6A Installation, Start-up, Operating and Service and Maintenance Instructions (59SC6A-01SI), Table 9 Air Filter Selection and Duct Sizing, p.24 (printed p.21)

Filter sizes by casing width and filter cabinet

Filters · 59TP6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide16 x 25 x 3/4 in.16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide16 x 25 x 3/4 in.20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide16 x 25 x 3/4 in.24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media
  • No internal filter rack in this furnace - an external filter is required.
  • Side-return filters can differ in size - measure the existing filter.
  • Not every family has the 14-3/16 in. casing.

Source: Carrier 59TP6A Installation, Start-up, Operating and Service and Maintenance Instructions, Table 7 Air Filter Selection and Duct Sizing, p.23 (PDF p.26 of 96-page file)

Minimum clearances to combustibles

Clearances · 59TP6A

PositionClearance
Rear0 in. (0 mm)
Front (combustion air openings)1 in. (25 mm)
Front, required for service24 in. (610 mm) - check local code
All sides of supply plenum1 in. (25 mm) - check local code
Sides0 in. (0 mm)
Vent0 in. (0 mm)
Top of furnace1 in. (25 mm)
  • Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.
  • Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.

Source: Carrier 59TP6A Installation, Start-up, Operating and Service and Maintenance Instructions, Table 2 Minimum Clearances to Combustible Materials, p.6 (PDF p.9 of 96-page file)

Minimum clearances to combustibles

Clearances · 59SC6A

PositionMinimum clearance
Rear0
Front (combustion air openings in furnace and in structure)1 in. (25 mm)
Required for service24 in. (610 mm) (see note)
All sides of supply plenum1 in. (25 mm) (see note)
Sides0
Vent0
Top of furnace1 in. (25 mm)
  • Service and supply-plenum values are marked 'consult local building codes'.
  • Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.
  • Downflow on a combustible or wood floor needs the special base unless installed on a factory cased coil or coil casing.
  • Same values for all sizes.

Source: Carrier 59SC6A Installation, Start-up, Operating and Service and Maintenance Instructions (59SC6A-01SI), Table 2 Minimum Clearances to Combustible Materials for All Units, p.8 (printed p.5)

Filter sizes by casing width

Filters · 58SB0A/58SB1A

Casing width in. (mm)Side returnBottom returnType
14-1/2 (368)16 x 25 x 3/414 x 25 x 3/4Washable
17-1/2 (445)16 x 25 x 3/416 x 25 x 3/4Washable
21 (533)16 x 25 x 3/420 x 25 x 3/4Washable
24 (610)16 x 25 x 3/424 x 25 x 3/4Washable
  • Filters are outside the casing; no internal rack.
  • Each return inlet needs a filter.
  • Wash a washable filter with cold water against the airflow; do not oil it.

Source: Carrier 58SB0A-05SI installation manual (text export), Table 14 Filter Size Information

Filter sizes by casing width

Filters · Payne PG96VTA

Casing width in. (mm)Side returnBottom returnType
14-3/16 (360)16 x 25 x 3/414 x 25 x 3/4Washable
17-1/2 (445)16 x 25 x 3/416 x 25 x 3/4Washable
21 (533)16 x 25 x 3/420 x 25 x 3/4Washable
24-1/2 (622)16 x 25 x 3/424 x 25 x 3/4Washable

Source: Payne IM-PG96VTAB-01 installation manual (text export), Table 9 Air Filter Selection

Models covered

58SB0A045E14--1258SB0A045E17--1258SB0A070E14--1258SB0A070E17--1258SB0A070E17--1658SB0A070E21--1658SB0A090E17--1458SB0A090E21--1658SB0A090E21--2058SB0A090E24--2058SB0A110E21--2058SB0A110E24--2058SB0A135E24--2058SB0A155E24--2059MN7C060C17--1459MN7C060C21--2059MN7C080C17--1459MN7C080C21--2059MN7C100C21--2259MN7C120C24--2259SC5B026E14--1059SC5B040E14--1059SC5B040E17--1259SC5B060E14--1259SC5B060E17--1459SC5B080E17--1659SC5B080E21--2059SC5B100E21--2059SC5B100E21--2259SC5B120E24--2259SC5B140E24--2259SC6A026M14--1059SC6A040M14--1059SC6A040M17--1259SC6A060M14--1259SC6A060M17--1659SC6A080M17--1659SC6A080M21--2059SC6A100M21--2059SC6A100M21--2259SC6A120M24--2259SC6A140M24--2259TP6A040-1059TP6A040-1259TP6A060-1259TP6A060-1459TP6A080-1659TP6A080-2059TP6A100-2059TP6A120-22926TB30040V14926TB36040V17926TB36060V14926TB42060V17926TB48080V17926TB60080V21926TB60100V21926TB66100V21926TB66120V24PG96VTA30040APG96VTA36040BPG96VTA36060APG96VTA48060BPG96VTA48080BPG96VTA60080CPG96VTA60100CPG96VTA66120D

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.