Carrier furnace error codes
96 codes (50 faults, 46 normal display and menu codes), plus 6 settings tables.
| Code | Meaning | Severity / type |
|---|---|---|
| 5,9 | Component test - gas valve communication check (59MN7C) | Menu / mode display |
| 10.1 | L1 polarity fault | High |
| 11 | No previous code | Low |
| 12 | Blower on after power-up (normal) | Low |
| 12.1 | W (heat call) on at power up | Low |
| 13 | Limit circuit lockout | Critical |
| 13.1 | Limit lockout - main limit open over 3 minutes | High |
| 14 | Ignition lockout | Critical |
| 14.1 | Ignition lockout after 4 tries | High |
| 14.2 | Lockout - flame lost 3 times after 70 s of heating | High |
| 14.3 | Lockout - 7 flame-loss events in one heat call | High |
| 15 | Blower motor lockout | High |
| 21 | Gas heating lockout | Critical |
| 21.1 | 24 VAC on gas valve when it should be off | Critical |
| 22 | Abnormal flame-proving signal | Critical |
| 22.1 | False flame | Critical |
| 23 | Pressure switch did not open | Medium |
| 23.1 | Main pressure switch stuck closed | Medium |
| 23.2 | Secondary pressure switch stuck closed | Medium |
| 24 | Secondary (24 V) fuse open | Medium |
| 24.1 | Fuse fault (24 V) | High |
| 25 | Invalid model selection or setup error | Medium |
| 25.1 | No program in control | High |
| 25.2 | Corrupted program file | High |
| 25.3 | Twinned furnaces not identical | Medium |
| 25.4 | Main program invalid, running on backup | Low |
| 25.5 | Installer settings corrupted | Low |
| 25.6 | Wrong program for this control | High |
| 25.7 | Non-condensing program in condensing furnace | High |
| 27.1 | Super plug program missing or corrupted | Medium |
| 27.2 | Super plug program missing or corrupted | Medium |
| 27.3 | Super plug program missing or corrupted | Medium |
| 31 | High-heat pressure switch or relay did not close or reopened | High |
| 31.2 | Secondary pressure switch (HPS) open | High |
| 31.3 | Secondary pressure switch lockout | High |
| 32 | Low-heat pressure switch did not close or reopened | High |
| 32.1 | Main pressure switch (LPS) open | High |
| 33 | Limit circuit fault | High |
| 33.1 | Main limit circuit switch open | High |
| 34 | Ignition proving failure | High |
| 34.1 | Ignition fault during ignition trials | High |
| 34.2 | Flame lost before blower on-delay | Medium |
| 34.3 | Flame lost after blower on-delay | High |
| 43 | Low-heat pressure switch open while high-heat switch closed | High |
| 45 | Control circuitry lockout | High |
| 45.1 | Control failure - flame circuit / memory / sequence | High |
| 45.2 | Control failure - gas valve relay will not close | High |
| 45.3 | Control failure - EEPROM memory | High |
| 46.1 | Momentary loss of power | Low |
| CF2 | Continuous fan (CF2 variant) | Normal status |
| CF3 | Continuous fan (CF3 variant) | Normal status |
| CL1 | Low cooling or heat pump (PG96VTA, 59MN7C) | Normal status |
| CL2 | High cooling or heat pump (PG96VTA, 59MN7C) | Normal status |
| Ht1 | Low-stage heating (PG96VTA) | Normal status |
| Ht2 | High-stage heating (PG96VTA) | Normal status |
| ##.# | Active status code shown as major.minor number | Menu / mode display |
| Air | Menu: airflow (CFM) display on/off | Menu / mode display |
| CL | Cooling or heat pump running (59SC6A) | Normal status |
| Cfn | Continuous fan | Normal status |
| Clr | Clear fault history | Menu / mode display |
| Cod | Menu: cool blower-off delay | Menu / mode display |
| Component test | Component self-test mode | Menu / mode display |
| Ct | Menu: component test | Menu / mode display |
| Ctt | Menu: cooling thermostat type | Menu / mode display |
| End | Component test - end | Menu / mode display |
| Err | Component test could not start | Menu / mode display |
| FLt | Menu: last 7 faults | Menu / mode display |
| Fn | Component test - blower | Menu / mode display |
| HSi | Component test - hot surface igniter | Menu / mode display |
| HoD | Menu: heat blower-off delay | Menu / mode display |
| Hpd | Heat pump defrost - furnace heating | Normal status |
| Ht | Heating (59SC6A, 59MN7C menu: heating airflow setting) | Normal status |
| Ht-% | Heating at a percent firing rate (59MN7C) | Normal status |
| Htt | Menu: heating thermostat type | Menu / mode display |
| LED OFF | No amber LED - no power to control | High |
| LED ON | Amber LED steady on | Normal status |
| PRG | Startup display - model program number | Normal status |
| PUr | Component test - purge (inducer on) | Menu / mode display |
| Pri | Twinning: primary furnace | Menu / mode display |
| Rapid Flash | Reversed 115-V polarity (or twinning phasing) | High |
| SEC | Twinning: secondary furnace | Menu / mode display |
| Stored codes | Recall stored status codes | Menu / mode display |
| UPF | Display set for upflow | Menu / mode display |
| YEs | Reset confirmation | Menu / mode display |
| bLr | Blower running (secondary furnace / communicating system) | Normal status |
| bSt | Menu: inducer boost | Menu / mode display |
| dir | Menu: display orientation | Menu / mode display |
| dnF | Display set for downflow | Menu / mode display |
| iDl | Idle - standby, no demand | Normal status |
| inF | Menu: program number and software | Menu / mode display |
| non | No faults stored | Menu / mode display |
| rSt | Menu: reset to factory defaults | Menu / mode display |
| tSt | Component test started | Menu / mode display |
| tnn | Menu: twinning | Menu / mode display |
| t° | Menu: supply and return air temperature display | Menu / mode display |
| uEr | Startup display - software version | Normal status |
Settings and specs
Filter sizes by casing width and filter cabinet
Filters · 59SC6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | (1) 16 x 25 x 3/4 in. | (1) 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
- Side-return filters can differ in size - measure the existing filter.
- Every return-air inlet needs a filter.
- Airflow over 1800 CFM needs at least a 20 x 25 in. filter.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service and Maintenance Instructions (59SC6A-01SI), Table 9 Air Filter Selection and Duct Sizing, p.24 (printed p.21)
Filter sizes by casing width and filter cabinet
Filters · 59TP6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | 16 x 25 x 3/4 in. | 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | 16 x 25 x 3/4 in. | 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | 16 x 25 x 3/4 in. | 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
- No internal filter rack in this furnace - an external filter is required.
- Side-return filters can differ in size - measure the existing filter.
- Not every family has the 14-3/16 in. casing.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service and Maintenance Instructions, Table 7 Air Filter Selection and Duct Sizing, p.23 (PDF p.26 of 96-page file)
Minimum clearances to combustibles
Clearances · 59TP6A
| Position | Clearance |
|---|---|
| Rear | 0 in. (0 mm) |
| Front (combustion air openings) | 1 in. (25 mm) |
| Front, required for service | 24 in. (610 mm) - check local code |
| All sides of supply plenum | 1 in. (25 mm) - check local code |
| Sides | 0 in. (0 mm) |
| Vent | 0 in. (0 mm) |
| Top of furnace | 1 in. (25 mm) |
- Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.
- Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service and Maintenance Instructions, Table 2 Minimum Clearances to Combustible Materials, p.6 (PDF p.9 of 96-page file)
Minimum clearances to combustibles
Clearances · 59SC6A
| Position | Minimum clearance |
|---|---|
| Rear | 0 |
| Front (combustion air openings in furnace and in structure) | 1 in. (25 mm) |
| Required for service | 24 in. (610 mm) (see note) |
| All sides of supply plenum | 1 in. (25 mm) (see note) |
| Sides | 0 |
| Vent | 0 |
| Top of furnace | 1 in. (25 mm) |
- Service and supply-plenum values are marked 'consult local building codes'.
- Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.
- Downflow on a combustible or wood floor needs the special base unless installed on a factory cased coil or coil casing.
- Same values for all sizes.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service and Maintenance Instructions (59SC6A-01SI), Table 2 Minimum Clearances to Combustible Materials for All Units, p.8 (printed p.5)
Filter sizes by casing width
Filters · 58SB0A/58SB1A
| Casing width in. (mm) | Side return | Bottom return | Type |
|---|---|---|---|
| 14-1/2 (368) | 16 x 25 x 3/4 | 14 x 25 x 3/4 | Washable |
| 17-1/2 (445) | 16 x 25 x 3/4 | 16 x 25 x 3/4 | Washable |
| 21 (533) | 16 x 25 x 3/4 | 20 x 25 x 3/4 | Washable |
| 24 (610) | 16 x 25 x 3/4 | 24 x 25 x 3/4 | Washable |
- Filters are outside the casing; no internal rack.
- Each return inlet needs a filter.
- Wash a washable filter with cold water against the airflow; do not oil it.
Source: Carrier 58SB0A-05SI installation manual (text export), Table 14 Filter Size Information
Filter sizes by casing width
Filters · Payne PG96VTA
| Casing width in. (mm) | Side return | Bottom return | Type |
|---|---|---|---|
| 14-3/16 (360) | 16 x 25 x 3/4 | 14 x 25 x 3/4 | Washable |
| 17-1/2 (445) | 16 x 25 x 3/4 | 16 x 25 x 3/4 | Washable |
| 21 (533) | 16 x 25 x 3/4 | 20 x 25 x 3/4 | Washable |
| 24-1/2 (622) | 16 x 25 x 3/4 | 24 x 25 x 3/4 | Washable |
Source: Payne IM-PG96VTAB-01 installation manual (text export), Table 9 Air Filter Selection
Models covered
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.