Carrier · Furnace
SEC Twinning: secondary furnace
What the display is showing
Choice inside the tnn menu: this furnace is the secondary of a twinned pair; its display then shows bLr while the primary is active.
Applies to: 59SC6A and Payne PG96VTA furnaces
Settings for these units
Filter sizes by casing width and filter cabinet · 59SC6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | (1) 16 x 25 x 3/4 in. | (1) 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | (1) 16 x 25 x 3/4 in. | (1) 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
Side-return filters can differ in size - measure the existing filter.
Every return-air inlet needs a filter.
Minimum clearances to combustibles · 59SC6A
| Position | Minimum clearance |
|---|---|
| Rear | 0 |
| Front (combustion air openings in furnace and in structure) | 1 in. (25 mm) |
| Required for service | 24 in. (610 mm) (see note) |
| All sides of supply plenum | 1 in. (25 mm) (see note) |
| Sides | 0 |
| Vent | 0 |
| Top of furnace | 1 in. (25 mm) |
Service and supply-plenum values are marked 'consult local building codes'.
Keep 1 in. (25 mm) from combustibles to supply ductwork for 36 in. (914 mm) horizontally from the furnace.
- Filter sizes by casing width · Payne PG96VTA
Models that show this code
19 models in 59SC6A, Payne PG96VTA
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A installation instructions, Table 21, p.53; Payne PG96VTAB installation instructions, Main Menu Options, p.53. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.