Carrier · Furnace
Stored codes Recall stored status codes
What the display is showing
Both controls keep recent status codes in memory and do not lose them when 115 V or 24 V power is interrupted (amber LED boards). This mode replays them on the amber LED. The 59TP6A keeps the last 7; code 11 means no fault is stored. The two-digit codes are read as short flashes (first digit) then long flashes (second digit).
Applies to: 59TP6A and 58SB0A/58SB1A furnaces (amber status LED control)
What to do
- 59TP6A Make sure there is no thermostat signal and all blower-off delays have finished. Leave 115 V on and remove the blower door.
- 59TP6A Turn setup switch SW1-1 ON and manually hold the blower door switch closed. The control flashes up to 7 stored codes in order; the last one (the 8th) is always 11.
- 59TP6A Turn SW1-1 OFF. A steady amber LED then shows proper operation. Refit the blower door.
- 58SB0A/58SB1A With no thermostat signal and the blower-off delays finished, note the current LED state through the sight glass.
- 58SB0A/58SB1A Briefly pull the wire off the draft safeguard (DSS) switch until the LED goes out, then reconnect it. The LED then flashes the stored code 4 times; record it. If nothing is stored it flashes 11.
- 58SB0A/58SB1A Do not leave the LS or DSS wire off longer than 4 seconds, or the blower starts and the stored code is replaced by 33.
Settings for these units
Filter sizes by casing width and filter cabinet · 59TP6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | 16 x 25 x 3/4 in. | 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | 16 x 25 x 3/4 in. | 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | 16 x 25 x 3/4 in. | 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
No internal filter rack in this furnace - an external filter is required.
Side-return filters can differ in size - measure the existing filter.
Minimum clearances to combustibles · 59TP6A
| Position | Clearance |
|---|---|
| Rear | 0 in. (0 mm) |
| Front (combustion air openings) | 1 in. (25 mm) |
| Front, required for service | 24 in. (610 mm) - check local code |
| All sides of supply plenum | 1 in. (25 mm) - check local code |
| Sides | 0 in. (0 mm) |
| Vent | 0 in. (0 mm) |
| Top of furnace | 1 in. (25 mm) |
Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.
Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.
- Filter sizes by casing width · 58SB0A/58SB1A
Models that show this code
22 models in 59TP6A, 58SB0A/58SB1A
Other codes on the same units
- 33 Limit circuit fault
- 34 Ignition proving failure
- 43 Low-heat pressure switch open while high-heat switch closed
- 45 Control circuitry lockout
- Component test Component self-test mode
- LED OFF No amber LED - no power to control
- LED ON Amber LED steady on
- Rapid Flash Reversed 115-V polarity (or twinning phasing)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59TP6A installation instructions, Troubleshooting / Service and Maintenance, p.76-77; Carrier 58SB0A/58SB1A installation instructions (58SB0A-05SI), p.26 and p.31. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.