Carrier · Furnace

45 Control circuitry lockout

High severity 59TP6A58SB0A/58SB1A

What the control is telling you

Control locks out (auto-reset after 1 hour) due to a flame circuit failure, stuck-open gas valve relay or software check error.

Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)

Likely causes

  • Flame circuit failure on control
  • Gas valve relay stuck open
  • Software check error

Test and repair steps

  1. Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
  2. Reset power to clear the lockout.
  3. Run a heat cycle and watch for the code to return.
  4. If code 45 repeats, replace the furnace control (install model plug PL4 on the new board).

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide (cont.), p.89. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.