Carrier · Furnace
34 Ignition proving failure
What the control is telling you
Flame was not sensed during trial for ignition; the control retries 3 more times before lockout 14. If flame is lost during blower on-delay, the blower runs its off-delay.
Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)
Likely causes
- Gas valve or manual shutoff off
- Green/yellow ground wire not connected to sheet metal
- Flame sensor grounded, dirty or mislocated
- Igniter or igniter harness failed
- Gas valve not getting 24 V or not opening
- Low inlet gas pressure, wrong firing rate, poor carryover or rough ignition
- Failed control
Test and repair steps
- Check the gas valve and manual shutoff are on, the green/yellow wire is bonded to the furnace sheet metal, and the flame sensor is not grounded.
- Run Component Self-Test (R wire off, reset power, SW1-6 ON). The igniter should glow orange/white by the end of the 15-second warm-up.
- If it does not glow unplug the igniter harness, rerun test (SW1-6 OFF then ON), and check for 115 V between pin 3 and NEUTRAL-L2 for 15 seconds. If 115 V is present, check harness and igniter continuity and replace the bad part; if not, replace the control.
- Reconnect R and call for heat. Check for 24 V at the gas valve; if none, check connections and then replace the control. If 24 V but no gas flow, check valves are on, then replace the gas valve.
- If burners do not light check for inadequate carryover, low inlet gas pressure and proper firing rate.
- If burners light but drop out check flame current during trial for ignition. Nominal is 4.0-6.0 microamps DC; if below 0.5 microamps, clean the sensor with fine steel wool and recheck, and replace the electrode if still low.
- If current is near normal but burners still drop: repeat in high heat; if still failing replace the control. If high heat works, check low-heat manifold pressure, then carryover and sensor location.
Settings for these units
Filter sizes by casing width and filter cabinet · 59TP6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | 16 x 25 x 3/4 in. | 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | 16 x 25 x 3/4 in. | 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | 16 x 25 x 3/4 in. | 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
No internal filter rack in this furnace - an external filter is required.
Side-return filters can differ in size - measure the existing filter.
Minimum clearances to combustibles · 59TP6A
| Position | Clearance |
|---|---|
| Rear | 0 in. (0 mm) |
| Front (combustion air openings) | 1 in. (25 mm) |
| Front, required for service | 24 in. (610 mm) - check local code |
| All sides of supply plenum | 1 in. (25 mm) - check local code |
| Sides | 0 in. (0 mm) |
| Vent | 0 in. (0 mm) |
| Top of furnace | 1 in. (25 mm) |
Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.
Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.
- Filter sizes by casing width · 58SB0A/58SB1A
Models that show this code
22 models in 59TP6A, 58SB0A/58SB1A
Other codes on the same units
- 24 Secondary (24 V) fuse open
- 25 Invalid model selection or setup error
- 31 High-heat pressure switch or relay did not close or reopened
- 32 Low-heat pressure switch did not close or reopened
- 33 Limit circuit fault
- 43 Low-heat pressure switch open while high-heat switch closed
- 45 Control circuitry lockout
- Component test Component self-test mode
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide (cont.), p.89; Component Self-Test p.77. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.