Carrier · Furnace · Ignition
Single-stage 80% furnace: ignition sequence and retries
What happens, in order
- Thermostat closes R-W to call for heat
- Control runs a self-check and confirms the pressure switch is open, then starts the inducer
- Inducer reaches speed, pressure switch closes, and the prepurge timer starts (humidifier 24 V terminal powers up)
- Hot surface igniter warms up after prepurge
- Gas valve opens at the end of warm-up; flame proving window starts 5 s later and lasts 2 s
- Igniter stays on until flame is sensed or the 2 s proving window begins
- Flame proven at the sensor gas valve stays open and the blower-on delay starts
- No flame within 2 s gas valve closes and the control repeats the sequence up to 3 more times (4 trials total)
- After the last failed trial the control goes to ignition lockout; it clears by itself after 3 hours, or by cycling 115 V or 24 V power to the control (not at W, G or R)
- Flame seen when it should be off control locks out gas heat and keeps the inducer running until flame is gone
Timings and thresholds
| Item | Value |
|---|---|
| Prepurge | 15 s |
| Igniter warm-up | 17 s |
| Flame proving | 2 s (starts 5 s after gas valve opens) |
| Ignition trials | 4 total |
| Lockout auto-reset | 3 hours |
Codes you may see during this
Applies to: Carrier 58SB0A / 58SB1A 80% single-stage gas furnace
Models
58SB0A58SB1A
More Carrier furnace sequences
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Carrier 58SB0A/58SB1A installation manual, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.