Carrier · Furnace · Other

Furnace used with a heat pump (dual fuel timing)

58SB0A58SB1A

What happens, in order

  1. Control detects R-W with Y (or Y and G) and changes its blower timing to avoid long blower-off periods during heat pump defrost
  2. Blower stays on at heat speed through the prepurge, drops out for 24 s, then comes back on at heat speed
  3. W drops normal inducer post-purge runs and the blower moves to cool speed after a 3 s delay
  4. If W, Y and G all drop together the blower runs for the selected blower-off delay
  5. If W and Y drop but G stays, blower runs the blower-off delay at heat speed and then holds

Timings and thresholds

ItemValue
Blower dropout in heat cycle24 s
Speed change delay after W drops3 s

Applies to: Carrier 58SB0A / 58SB1A 80% single-stage gas furnace

Models

58SB0A58SB1A

More Carrier furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier 58SB0A/58SB1A installation manual, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.