Carrier · Furnace · Heating

Single-stage 80% furnace: heating cycle, blower delays and shutdown

58SB0A58SB1A

What happens, in order

  1. After flame is proven, blower starts on heat speed 25 s after the gas valve opens; the electronic air cleaner terminal comes on with the blower
  2. Burners run until the thermostat is satisfied
  3. R-W opens gas valve closes and the 24 V humidifier terminal drops out
  4. Inducer runs for a short post-purge, then stops
  5. Blower keeps running for the heat-off delay (90, 120, 150 or 180 s), then stops
  6. If power is lost during a call for heat, on return the control runs the blower alone for 90 s starting 2 s after power is back (display code 12), then answers the thermostat normally

Timings and thresholds

ItemValue
Blower-on delay25 s
Inducer post-purge5 s
Blower-off delay options90 / 120 / 150 / 180 s
Blower-off delay factory120 s
Blower-only run after power-up90 s

Codes you may see during this

12

Applies to: Carrier 58SB0A / 58SB1A 80% single-stage gas furnace

Models

58SB0A58SB1A

More Carrier furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier 58SB0A/58SB1A installation manual, Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.