Carrier · technician tips
Carrier service menus, test modes and resets
622 tips for air conditioner, air handler, furnace, heat pump, mini split: access codes, button combinations, test modes and the resets you need at the appliance.
Jump to: Access & passwords (8) · Button combinations (28) · Service & test modes (43) · Reset & cancel (24) · Settings shortcuts (44) · Commissioning (148) · Other (327)
Access & passwords
Installer and service menu codes, and how to get into them.
Document INQUIRY and SERVICE changes
Air handler · D5FUAA
Changes made in INQUIRY or SERVICE mode are not shown again the next time you enter. Example: CODE 22 (Heating Temperature Compensation) defaults to 0 and does not show a previous setting of -2. To reset an unknown value, press DOWN to -6, then press UP back to 0.
- Write down every change before exiting INQUIRY mode.
- If the previous value is unknown, press DOWN to the maximum change range of -6, then press UP until the value reads 0, then set the new value.
Applies to: D5FUAA wired and wireless remote control settings
Source: D5FUAA installation instructions, p. 47. Written in our own words; check the manual for your exact model.
Enter INQUIRY mode on the wireless remote
Air handler · D5FSAA, D5FLAA
INQUIRY mode is the first step before any service changes. It shows numbered codes 0 to 30 on the remote.
- Press ON/OFF and FAN SPEED together and hold for 8 seconds.
- The remote shows 0 by default when INQUIRY mode opens.
- Use UP and DOWN to step through the codes.
- Press OK to send the selected code value to the indoor unit display.
- If no button is pressed for 1 minute, the remote leaves INQUIRY mode on its own.
Applies to: Wireless remote controller, D5FSAA and D5FLAA air handler ductless systems
Source: Carrier D5FSAA/D5FLAA installation instructions, p. 35. Written in our own words; check the manual for your exact model.
Enter SERVICE mode from INQUIRY mode
Air handler · D5FUHA
Service changes can only be made in SERVICE mode, and SERVICE mode can only be reached from INQUIRY mode. Plan the changes before starting, because the remote does not show the new level after a change.
- Turn the indoor unit off with the remote.
- Turn off power to the outdoor unit for 2 minutes, then turn it back on.
- Remove the remote batteries and wait for the screen to clear.
- Within 30 seconds of putting the batteries back, use UP or DOWN to scroll to the required INQUIRY code.
- Press ON/OFF for 2 seconds to enter SERVICE mode for that code.
- Make the adjustment, then press ON/OFF for 2 seconds to exit SERVICE mode back to INQUIRY mode.
- Press ON/OFF and FAN SPEED for 2 seconds to exit INQUIRY mode. All remote buttons stay disabled for 60 seconds.
Applies to: D5FUHA remote controller
Source: D5FUHA installation instruction manual, p. 49. Written in our own words; check the manual for your exact model.
Record INQUIRY changes because the remote does not show them
Air handler · D5FSAA, D5FLAA
A changed value does not show again when INQUIRY is reopened. The display falls back to the default of 0, so the old setting can only be known from your own records.
- Write down every INQUIRY and SERVICE change, with the code number and new value.
- If the previous value is unknown, press DOWN to the maximum change range (-6 in the code 22 example).
- Press UP until the display is back at 0.
- Enter the new value and document it.
Applies to: Wireless remote controller, D5FSAA and D5FLAA air handler ductless systems
Source: Carrier D5FSAA/D5FLAA installation instructions, p. 35. Written in our own words; check the manual for your exact model.
Enter engineering data mode (information inquiry)
Mini-split · D5FSCAH / D5FLCAH
Read live unit data through the RG10 remote. Use only the Power, Up, Down and OK buttons inside this mode.
- Make sure the unit is in standby or running normally, not locked.
- Press Power and Fan together for 7 seconds until the remote shows 0 and the mode icons appear.
- Press Up or Down to choose channel 0 to 30.
- Read the value on the indoor display. It shows the code for 2 seconds, then the value.
- To exit, press Power and Fan together for 2 seconds.
Applies to: RG10 remote with D5FSCAH / D5FLCAH
Source: Carrier D5FSCAH / D5FLCAH service manual, p. 29. Written in our own words; check the manual for your exact model.
Lock or unlock the remote control
Mini-split · D5FSOAH
Locks or unlocks the wireless remote.
- Hold the BOOST and HUMIDITY buttons together for five seconds.
Applies to: D5FSOAH remote control RG10L5(2HS)
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Operate the unit without the remote
Mini-split · D5FCFAH
If the remote is lost, the system can be run from the AUTO setting on the indoor unit. The indoor unit's MANUAL button cycles through AUTO, FORCED COOL and OFF.
- Press the MANUAL button on the indoor unit to select AUTO, FORCED COOL or OFF.
Applies to: Indoor unit controls
Source: D5FCFAH Owner's Manual, p. 2, 7. Written in our own words; check the manual for your exact model.
Remote ON-OFF input (CN23 and jumper JR6)
Mini-split · D5FSOAH
Remove jumper JR6 to use the remote ON-OFF function. Open contact turns the system off and the display shows CP. Closed contact turns it on. The unit responds within 2 seconds.
- Remove jumper JR6 before wiring the remote switch to CN23.
- Leave the contact open to turn the system off (display shows CP).
- Close the contact to turn the system on.
Applies to: D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
Source: D5FSOAH service manual, p. 11. Written in our own words; check the manual for your exact model.
Button combinations
Key presses that open menus, show readouts or switch modes.
Black button forced modes (scenario 2 only)
Air handler · D5FUAA
On scenario 2 units, the black button on the indoor board steps through forced modes. Long press under forced cooling forces defrost.
- Press the black button once to enter forced automatic mode.
- Press again to enter forced cooling mode (display shows FC).
- Press again to shut down.
- In forced cooling, long press the black button for 5 s to enter forced defrost.
Applies to: D5FUAA indoor unit, scenario 2
Source: D5FUAA installation instructions, p. 26. Written in our own words; check the manual for your exact model.
Force defrost from outdoor unit SW4 button
Air handler · D5FUAA
Holding the SW4 button on the outdoor unit starts a forced defrost.
- Press and hold the SW4 button on the outdoor unit for 10 seconds.
Applies to: Outdoor unit paired with D5FUAA air handler
Source: Carrier D5FUAA product data, p. 17. Written in our own words; check the manual for your exact model.
Forced operation using the AUTO/COOL button
Air handler · D5FSAA
Pressing the AUTO/COOL button starts a forced sequence. Forced cooling runs the compressor and outdoor fan with the indoor fan on breeze speed, then after 30 minutes the unit changes to auto mode at a preset 76°F (24°C). Forced auto runs like normal auto mode at a preset 76°F (24°C). Forced operation ends when the unit is switched off or when a remote signal changes the running mode.
- Press the AUTO/COOL button once to start forced cooling.
- Wait 30 minutes; the unit moves to auto mode at 76°F (24°C).
- To use forced auto, select it with the button sequence and leave the preset at 76°F (24°C).
- To end forced operation, switch the unit off or send a remote command that changes the mode.
Applies to: D5FSAA
Source: Carrier D5FSAA product data, p. 4. Written in our own words; check the manual for your exact model.
Lock or unlock the wireless remote
Air handler · D5FUH
Holding TURBO and the C/F button together locks or unlocks the remote so buttons are not pressed by accident.
- Press and hold TURBO and the C/F button together for five seconds.
- Repeat to unlock. The LOCK display shows when the remote is locked.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FUHAQ owner's manual, p. 9 and p. 10. Written in our own words; check the manual for your exact model.
Switch remote display between °F and °C
Air handler · D5FUAAH
Changes the temperature units shown on the remote.
- Press the TEMP increase and TEMP decrease buttons together and hold for about 3 seconds.
- Repeat to switch back.
- The default display is °F.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: D5FUAAH Owner's Manual, p. 9. Written in our own words; check the manual for your exact model.
Switch the remote between °C and °F
Air handler · D5FUH
The default display is °F. Pressing the two temperature set point buttons together switches the display units.
- Press and hold the + and - temperature set point buttons together for about 3 seconds.
- Repeat to switch back between °F and °C.
Applies to: Wireless remote
Source: Carrier D5FUHAQ owner's manual, p. 9 and p. 11. Written in our own words; check the manual for your exact model.
Outdoor unit SW3 and SW4 buttons
Heat pump · D5CURA
Button functions on the outdoor unit control board.
- SW3 is not active. Do not rely on it.
- Use SW4 for point check inquiry.
- Use SW4 to start a forced defrost.
Applies to: D5CURA outdoor unit control board
Source: D5CURA installation manual, p. 20. Written in our own words; check the manual for your exact model.
Energy-efficient mode (Gear button)
Mini-split · D5FSFA
Pressing the Gear button on the remote cycles through the energy-efficient mode sequence. Turning the unit off or activating ECO, sleep, Super cool, 8°C heating, Silence or self clean ends this function. Not available on multi-zone systems.
- Press the Gear button on the remote to enter the energy-efficient mode sequence.
Applies to: Single-zone systems
Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Exit inquiry mode
Mini-split · D5FSOA
Leaves the service inquiry menu and returns to normal display.
- Press and hold On/Off and Fan together for 2 seconds.
Applies to: D5FSOAH indoor unit
Source: D5FSOAH service manual, p. 23. Written in our own words; check the manual for your exact model.
Fireplace operation from the BOOST button
Mini-split · D5FSFAH
In heating mode, holding BOOST for more than 5 seconds starts fireplace operation. Holding it for more than 3 seconds stops it.
- Set the unit to HEAT mode.
- Press and hold BOOST for more than 5 seconds to start fireplace operation.
- Press and hold BOOST for more than 3 seconds to stop it.
Applies to: Wireless remote controller, heating mode
Source: D5FSFAH Owner’s Manual, p. 9. Written in our own words; check the manual for your exact model.
Follow Me memory feature
Mini-split · D5FSOAH
Starts or stops the Follow Me memory. The display shows ON or OFF for 3 seconds to confirm.
- Press and hold BOOST for seven seconds.
Applies to: Units with Follow Me
Source: D5FSOAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Forced AUTO and Forced COOLING operation
Mini-split · D5FSFA
Used to run the unit without the remote. With the unit off, press TOUCH once to start Forced AUTO. Press TOUCH again within 5 seconds to start Forced COOLING. In any forced mode, press TOUCH to turn the unit off. Protections and the remote remain active in forced operation.
- With the unit off, press TOUCH once to engage Forced AUTO.
- Press TOUCH again within 5 seconds to engage Forced COOLING.
- Press TOUCH to turn the unit off from any forced mode.
Applies to: Indoor unit with TOUCH button
Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Forced operation (test) mode
Mini-split · D5FSOA
Forces the unit to run without the remote. Protections and remote control are still active in this mode.
- With the unit off, press TOUCH to start FORCED AUTO (75.2 F / 24 C setpoint).
- Press TOUCH again within 5 seconds to start FORCED COOLING.
- Press TOUCH once more to turn the unit off from any forced mode.
Applies to: D5FSOAH indoor unit
Source: D5FSOAH service manual, p. 19. Written in our own words; check the manual for your exact model.
Forced operation (TOUCH button)
Mini-split · D5FCFA
With the unit off, press TOUCH to start FORCED AUTO at 75.2°F (24°C). Press TOUCH again within 5 seconds for FORCED COOLING. Press TOUCH in any forced mode to turn the unit off. General protections and remote control stay active.
- Press TOUCH once with unit off to start FORCED AUTO.
- Press TOUCH again within 5 seconds to start FORCED COOLING.
- Press TOUCH to stop the unit.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 19. Written in our own words; check the manual for your exact model.
Forced operation using the TOUCH button
Mini-split · D5FSFA
Forced operation works without the remote and keeps the general protections and remote controller active.
- With the unit off, press TOUCH once to start Forced AUTO mode.
- Press TOUCH again within 5 seconds to switch to Forced COOLING mode.
- Forced COOLING runs at compressor frequency F2 with the indoor fan on BREEZE. After 30 minutes it switches to AUTO at 75.2 F (24 C).
- To stop the unit from any forced mode, press TOUCH.
Applies to: D5FSFAH 9K to 16K
Source: D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Lock or unlock the wireless remote
Mini-split · D5FSOAH
Locking or unlocking the remote is done by holding two buttons together.
- Hold the BOOST and HUMIDITY buttons together for 5 seconds to lock or unlock the remote.
Applies to: Wireless remote RG10L5(2HS)
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Silence feature shortcut
Mini-split · D5FCFAH
Press SILENCE, or hold FAN for more than 2 seconds, to enable the SILENCE function. The indoor unit runs at faint breeze and the compressor is held at a lower frequency. Not available on multi-zone systems.
- Press SILENCE, or hold FAN for more than 2 seconds, to enable it.
Applies to: Single-zone D5FCFAH systems
Source: Carrier D5FCFAH owner's manual, p. 12. Written in our own words; check the manual for your exact model.
SILENCE function (not on multi-zone systems)
Mini-split · D5FCFA
Press SILENCE or hold the FAN button for more than 2 seconds to enable. Compressor frequency is held lower than the set limit and the indoor unit runs at faint breeze. Disabled when matched to multiple outdoor units. The source gives both F2 and F3 as the frequency limit; confirm which applies.
- Press SILENCE on the remote control, or hold FAN for more than 2 seconds.
- Confirm the indoor unit is on faint breeze.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 20. Written in our own words; check the manual for your exact model.
SILENCE mode
Mini-split · D5FSFA
Keeps compressor frequency below F2 and runs the indoor unit at a faint breeze for the lowest noise level.
- Press SILENCE on the remote to start Silence mode.
- Turning the unit off, or activating ECO, sleep, Super cool, 8°C heating or self clean, ends Silence mode.
Applies to: Wireless remote controller
Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Start or stop the FOLLOW ME memory feature
Mini-split · D5FSFAH
Holding BOOST for 7 seconds toggles FOLLOW ME memory. The memory setting survives ON/OFF, MODE changes and indoor power failure.
- Press and hold BOOST for 7 seconds.
- Watch the display: ON shows for 3 seconds when memory starts, OFF shows for 3 seconds when it stops.
Applies to: Wireless remote controller, FOLLOW ME function
Source: D5FSFAH Owner’s Manual, p. 13. Written in our own words; check the manual for your exact model.
Start vertical louver auto swing
Mini-split · D5FSHAH
The SWING button starts and stops the horizontal louver. Holding it longer starts vertical auto swing.
- Hold the SWING button for 2 seconds.
Applies to: Wireless remote control
Source: Carrier D5FSHAH Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.
Switch display between F and C
Mini-split · D5FS(L)AAH
The remote can show temperature in Fahrenheit or Celsius. Default is Fahrenheit.
- Press the + and - temperature buttons together for about 3 seconds to switch between F and C.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FS(L)AAH owner's manual, p. 11, 13. Written in our own words; check the manual for your exact model.
Switch display between °C and °F
Mini-split · D5FSOAH
Both temperature buttons are pressed together to switch the temperature display units.
- Press the two temperature buttons together for 3 seconds to switch between °C and °F.
Applies to: Wireless remote RG10L5(2HS)
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Switch display between °F and °C
Mini-split · D5FCFAH
Press the two temperature buttons together for about 3 seconds to toggle the remote display between Fahrenheit and Celsius.
- Press both TEMP buttons together and hold for 3 seconds.
Applies to: Wireless remote control
Source: D5FCFAH Owner's Manual, p. 9. Written in our own words; check the manual for your exact model.
Switch the display between F and C
Mini-split · D5FCFAH
Press and hold the TEMP up and TEMP down buttons together for about 3 seconds to toggle the remote temperature display between Fahrenheit and Celsius.
- Press and hold both TEMP buttons together for about 3 seconds.
Applies to: D5FCFAH wireless remote controller
Source: Carrier D5FCFAH owner's manual, p. 8, 13. Written in our own words; check the manual for your exact model.
Switch the remote between Celsius and Fahrenheit
Mini-split · D5FSFAH
Hold the up and down TEMP buttons together for about 3 seconds to toggle the display between degrees C and degrees F.
- Press and hold TEMP up and TEMP down together for about 3 seconds.
- Check the display to confirm the new unit.
Applies to: Wireless remote controller
Source: D5FSFAH Owner’s Manual, p. 9. Written in our own words; check the manual for your exact model.
Switch the remote display between °F and °C
Mini-split · D5FSHAH
Press the two temperature buttons together to switch the display units.
- Press TEMP up and TEMP down together.
- Hold for 3 seconds.
Applies to: Wireless remote control
Source: Carrier D5FSHAH Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.
Vertical louver auto swing
Mini-split · D5FCFAH
Hold the SWING button for 2 seconds to start the vertical louver auto swing feature. A short press starts and stops horizontal louver movement.
- Hold SWING for 2 seconds to start vertical auto swing.
- Press SWING briefly to start or stop horizontal louver movement.
Applies to: D5FCFAH wireless remote controller
Source: Carrier D5FCFAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.
Service & test modes
Forced fan, low and high fire, test and diagnostic modes, error history and live data.
Recall the active status code on the outdoor board (25VNA8/24VNA9)
Air conditioner · Carrier Infinity 19VS 24VNA9
Replays the most recent, highest-priority active status code on the amber STATUS LED; codes are kept without power. The unit does not heat or cool while the forced defrost pins are shorted.
- Turn the unit power OFF
- Short the FORCED DEFROST connector (J2 on the board) with a clip wire
- Turn power ON; the amber LED flashes the stored code (short flashes = first digit, long flashes = second digit)
- Power down and remove the short
Applies to: Carrier Infinity 25VNA8/24VNA9
Source: Carrier 25VNA8/24VNA9 service manual, Status Codes - Status Code Recall Mode, p.14. Written in our own words; check the manual for your exact model.
Manual control button operation
Air conditioner · D5FSHAH
Used for testing or emergency only, when the remote is lost. The unit must be off before manual operation. Pressing the button once starts FORCED AUTO, twice starts FORCED COOLING, and a third press turns the unit off. Use the remote to return to normal operation.
- Open the front panel of the indoor unit.
- Find MANUAL CONTROL on the right-hand side.
- Press once for FORCED AUTO.
- Press again for FORCED COOLING.
- Press a third time to turn the unit off.
- Close the front panel.
Applies to: Indoor unit manual button
Source: D5FSHAH Owner's Manual, p. 13. Written in our own words; check the manual for your exact model.
Change fan airflow through CODE 23 and CODE 25
Air handler · D5FSAA, D5FLAA
Airflow is set in SERVICE mode by choosing a fan step. Code 23 sets the cooling fan speed and code 25 sets the heating fan speed.
- Enter SERVICE mode from INQUIRY mode as described for the remote service set-up.
- Scroll to CODE 23 for cooling fan speed, or CODE 25 for heating fan speed.
- Choose the step from the fan performance table for the unit size and mode (Default, -1 to -40, or +1 to +20).
- Check the CFM value in the table for the chosen fan speed (TURBO, HIGH, MIDDLE or LOW) at the external static pressure of the installation.
- Exit and power cycle the outdoor unit for 3 minutes to lock in the change.
Applies to: 18K, 24K, 30K and 36K air handler sizes, cooling and heating
Source: Carrier D5FSAA/D5FLAA installation instructions, p. 36. Written in our own words; check the manual for your exact model.
Enter engineering mode to set air volume
Air handler · D5FSAA
Engineering mode is used to set the fan airflow for cooling and heating separately. Cooling airflow is stored in channel 23 and heating airflow in channel 25.
- With the unit powered on or in standby, and the controls not locked, press and hold ON/OFF + Air Speed together for 7 seconds.
- Select channel 23 to set the cooling airflow, or channel 25 to set the heating airflow.
- Pick the CFM value from the matching airflow table for the unit size, speed and offset.
- Check the airflow after the change against the table for that size.
Applies to: D5FSAA all sizes (18K to 60K)
Source: D5FSAA product data, p. 24. Written in our own words; check the manual for your exact model.
Enter INQUIRY mode on the remote
Air handler · D5FUHA
Opens the remote's INQUIRY menu, which holds numbered codes 0 to 30 used for checking and setting the unit. Other buttons do nothing in this mode except UP, DOWN and OK, or the exit combination.
- Press ON/OFF and FAN SPEED together and hold for 8 seconds.
- The remote display shows 0 on entry. Use UP or DOWN to move through codes 0 to 30.
- Each code's information shows on the indoor unit display in about 1 second. Press OK to send the value.
- If no button is pressed, the remote leaves INQUIRY mode after 1 minute.
- To leave INQUIRY mode, press ON/OFF and FAN SPEED together for 2 seconds.
Applies to: D5FUHA remote controller
Source: D5FUHA installation instruction manual, p. 49. Written in our own words; check the manual for your exact model.
Enter SERVICE mode from INQUIRY
Air handler · D5FUAA
Service changes are only allowed in SERVICE mode, and you must be in INQUIRY mode first.
- Turn the indoor unit off with the remote.
- Turn off the outdoor unit power for 2 minutes, then turn it back on.
- Remove the remote batteries and wait for the screen to clear.
- Within 30 seconds of replacing the batteries, use UP or DOWN to scroll to the required INQUIRY mode.
- Press ON/OFF for 2 seconds to enter SERVICE mode for that code.
- After making changes, press ON/OFF for 2 seconds to leave SERVICE mode and return to INQUIRY.
Applies to: D5FUAA wireless remote controller
Source: D5FUAA installation instructions, p. 48. Written in our own words; check the manual for your exact model.
Force defrost on outdoor unit
Air handler · D5FUAA
Forces a defrost cycle from the outdoor unit board.
- Press and hold the SW4 button on the outdoor unit for 10 seconds.
Applies to: Outdoor unit
Source: D5FUAA installation instructions, p. 29. Written in our own words; check the manual for your exact model.
Forced cool operation from the indoor unit panel
Air handler · D5FUH
If the remote is lost or has no batteries, the unit can be run from the indoor display panel. In forced cool the operation light flashes, the unit runs high fan cooling for 30 minutes, then changes to AUTO. The remote is disabled during forced cool.
- Use the indoor unit display panel to start forced cool when the remote is unavailable.
- Wait for the 30-minute high-fan cooling period to finish.
- Expect the unit to change to AUTO after forced cool ends.
Applies to: Indoor unit front panel
Source: Carrier D5FUHAQ owner's manual, p. 15. Written in our own words; check the manual for your exact model.
Forced defrost test
Air handler · D5FUHA
SW4 on the outdoor unit board starts a forced defrost. It is for testing only. Termination conditions still control how long the defrost runs.
- Press and hold SW4 on the outdoor unit for 10 seconds.
- Let the forced defrost run and watch for normal defrost termination.
- Do not leave the unit in forced defrost as normal operation.
Applies to: D5FUHA outdoor unit
Source: D5FUHA Installation Instructions, p. 36. Written in our own words; check the manual for your exact model.
Forced operation modes from the wired controller
Air handler · D5FUHA
The wired controller's black button (KEY1) steps the unit through forced modes. Use this for commissioning or service checks, not for normal operation.
- Press KEY1 once to enter forced automatic mode.
- Press KEY1 again to enter forced cooling mode. The display shows FC.
- Press KEY1 again to shut the unit down.
- While in forced cooling (display FC), press and hold KEY1 for 5 seconds to enter forced defrost mode.
Applies to: Wired controller only
Source: Carrier D5FUHA installation instructions, p. 43. Written in our own words; check the manual for your exact model.
Test run and drainage check
Air handler · D5FUHA
Complete the pre-run checklist (piping, wiring, grounding, insulation, clear airflow, no leaks, correct voltage) before running. Failure to test run can cause unit or property damage or injury.
- Open both the liquid and gas service valves.
- Turn on main power and let the unit warm up.
- Set the air conditioner to COOL mode.
- Indoor unit: check room temperature reading, test the manual buttons, confirm drain flows freely, and listen for vibration or abnormal noise.
- Outdoor unit: check for refrigerant leaks, vibration and noise, and confirm wind, noise and water do not bother neighbours or create a hazard.
- Drainage test: run in COOL mode and confirm water discharges (can take up to 1 minute). Check all piping for leaks.
- Stop the unit, turn off main power and reinstall the test cover.
- If the unit does not run correctly, refer to the Service Manual troubleshooting section.
Applies to: D5FUHA crossover air handler
Source: Carrier D5FUHA Installation Instructions, p. 62. Written in our own words; check the manual for your exact model.
Read the last 7 faults (3-digit display furnaces)
Furnace · 59SC6A, Payne PG96VTA, 59MN7C
The FLt menu stores the 7 most recent faults in major.minor form; non means none stored.
- Scroll the main menu to FLt with MENU/SELECT
- Press NEXT/OPTION to step through the stored faults
- Decode the codes with the furnace service label
Applies to: 59SC6A, Payne PG96VTA and 59MN7C furnaces (3-digit display control)
Source: Carrier 59SC6A installation instructions, Table 21 Main Menu Options, p.53; Payne PG96VTAB installation instructions, Main Menu Options table, p.53; Carrier 59MN7C installation instructions, Table 18 Main Menu Options, p.47. Written in our own words; check the manual for your exact model.
Recall stored status codes (amber LED furnaces)
Furnace · 59TP6A, 58SB0A/58SB1A
Replays the stored status codes on the amber LED; codes survive power loss. Two-digit codes are short flashes (first digit) then long flashes (second digit).
- 59TP6A: no thermostat signal, blower-off delays finished, 115 V on, blower door removed
- 59TP6A: turn SW1-1 ON and hold the blower door switch closed; up to 7 codes flash, the 8th is always 11 (nothing stored)
- 59TP6A: turn SW1-1 OFF, refit the door; steady amber LED = normal
- 58SB0A/58SB1A: with no call and delays finished, note the LED state through the sight glass
- 58SB0A/58SB1A: briefly pull the wire off the draft safeguard (DSS) switch until the LED goes out, then reconnect; the stored code flashes 4 times (11 = none)
- 58SB0A/58SB1A: do not leave the LS or DSS wire off longer than 4 seconds or the blower starts and the stored code is replaced by 33
Applies to: 59TP6A and 58SB0A/58SB1A furnaces (amber status LED control)
Source: Carrier 59TP6A installation instructions, Troubleshooting / Service and Maintenance, p.76-77; Carrier 58SB0A/58SB1A installation instructions (58SB0A-05SI), p.26 and p.31. Written in our own words; check the manual for your exact model.
Run the furnace component self-test (amber LED furnaces)
Furnace · 59TP6A, 58SB0A/58SB1A
Runs inducer, igniter and blower in sequence with no call for heat so each part can be checked. Only starts with no thermostat signal; the gas valve never opens.
- 59TP6A: remove blower door and the R wire; turn SW1-6 ON and hold the door switch closed
- 59TP6A sequence: inducer high-heat speed; after 10 s igniter on 15 s; blower mid-range 15 s; inducer low-heat speed 10 s, then stops
- 59TP6A: turn SW1-6 OFF, refit R wire and door; status code 11 or 25 flashes afterwards; to repeat turn SW1-6 OFF then ON
- 58SB0A/58SB1A: disconnect R lead, hold door switch closed, jumper COM-24V to the TEST/TWIN quick-connect until the LED goes out (about 2 s)
- 58SB0A/58SB1A sequence: LED repeats previous code 4 times; inducer runs to the end; igniter 15 s; blower HEAT speed 10 s then COOL speed 10 s; inducer stops
- 58SB0A/58SB1A: reconnect R lead, release the switch, refit the door
Applies to: 59TP6A and 58SB0A/58SB1A furnaces (amber status LED control)
Source: Carrier 59TP6A installation instructions, Component Self-Test, p.77 and setup switch SW1-6 table; Carrier 58SB0A/58SB1A installation instructions, Start-Up Procedures step 3-4, p.26. Written in our own words; check the manual for your exact model.
Connect inverter test tool or Dr. SMART tool
Heat pump · D5CURA
Use the test tool to read outdoor unit parameters. Units under 24K single zone have a test port connector. 24K HH and 30K to 60K single zone units have a diagnosis/check board with a digital display that shows the parameters directly.
- Shut off power and remove the electrical panel.
- Find the cable already connected to the test port on the outdoor unit.
- Connect the test tool to that cable using the connector supplied with the tool.
- For Dr. SMART, connect the tool to the white terminal.
- After service, push the female end back into the port.
Applies to: Outdoor unit (inverter R454B single zone)
Source: D5CURA service manual, p. 27. Written in our own words; check the manual for your exact model.
Force a defrost on the outdoor unit
Heat pump · D5FUAA
Press and hold the SW4 button on the outdoor unit for 10 seconds to force defrost.
- Press and hold SW4 on the outdoor unit for 10 seconds.
- Confirm the unit enters defrost.
Applies to: D5FUAA outdoor unit
Source: D5FUAA service manual, p. 10. Written in our own words; check the manual for your exact model.
Force defrost from outdoor unit button
Heat pump · D5FUHA
Holding the outdoor unit SW4 button starts a forced defrost.
- Press and hold the SW4 button for 10 seconds on the outdoor unit to force defrost.
Applies to: D5FUHA outdoor unit
Source: D5FUHA service manual, p. 10. Written in our own words; check the manual for your exact model.
Force defrost with the outdoor SW4 button
Heat pump · D5CURA
Forced defrost is only for testing defrost. Defrost termination conditions still set how long it runs.
- Press and hold the outdoor SW4 button for 10 seconds.
- Do not use SW3 for forced defrost; it is not active.
- Watch the defrost termination conditions, which still limit the run time.
Applies to: Outdoor unit
Source: D5CURA installation manual, p. 28. Written in our own words; check the manual for your exact model.
Inverter test tool connection
Heat pump · D5FUAA
The inverter test tool connects to the cable already plugged into the outdoor unit test port. The Dr. SMART tool connects to the white terminal.
- Shut off the power and remove the electrical panel.
- Find the cable already connected to the test port on the outdoor unit.
- Connect the test tool to that cable using the connector supplied with the tool.
- Connect the Dr. SMART tool to the white terminal as shown in the service steps.
- After maintenance, push the female end back into the port.
Applies to: D5FUAA outdoor unit
Source: D5FUAA service manual, p. 19. Written in our own words; check the manual for your exact model.
Inverter test tool hookup
Heat pump · D5FUHA
Electricity remains in the capacitors after power is off, so discharge them fully before work. Use anti-static gloves or a wrist strap when checking the indoor or outdoor PCB.
- Shut off the power and remove the electrical panel.
- Locate the cable already connected to the test port on the outdoor unit.
- Connect the test tool to that cable using the connector supplied with the tool.
- After maintenance, insert the female end back into the port.
Applies to: D5FUHA outdoor unit
Source: Carrier D5FUHA service manual, p. 19. Written in our own words; check the manual for your exact model.
Force a defrost cycle by shorting the defrost pins
Heat pump · Carrier single-stage communicating HP
Starts a defrost by hand. A full defrost only runs with coil at 32 F / 0 C or colder and outdoor air under 50 F / 10 C; otherwise only an abbreviated 30-second defrost. On HK32EA003/008 boards, with the defrost thermostat open you get about 30 s, closed a full cycle.
- Short the two-pin FORCED DEFROST header for 5 seconds, then release
- On HK32EA003/008 boards, short the speed-up pins (J1) with a screwdriver for 5 seconds and release
- On the Infinity single-stage communicating heat pump the same can be commanded from the user interface
Applies to: Carrier single-stage communicating heat pump; HK32EA003/008 defrost boards
Source: Carrier residential A/C and heat pump service manual 24-25, Forced Defrost, p.48; HK32EA003/008 Defrost Control, p.17-18. Written in our own words; check the manual for your exact model.
Recall the active status code on the outdoor board (25VNA8/24VNA9)
Heat pump · Carrier Infinity 18VS 25VNA8
Replays the most recent, highest-priority active status code on the amber STATUS LED; codes are kept without power. The unit does not heat or cool while the forced defrost pins are shorted.
- Turn the unit power OFF
- Short the FORCED DEFROST connector (J2 on the board) with a clip wire
- Turn power ON; the amber LED flashes the stored code (short flashes = first digit, long flashes = second digit)
- Power down and remove the short
Applies to: Carrier Infinity 25VNA8/24VNA9
Source: Carrier 25VNA8/24VNA9 service manual, Status Codes - Status Code Recall Mode, p.14. Written in our own words; check the manual for your exact model.
Read live data with the outdoor check button (SW1)
Mini split · Carrier DLCM(R/H)B multi-zone outdoor
Each press of SW1 steps through a value on the outdoor display.
- Press 1 = number of indoor units talking. 2 = mode (0 off, 1 fan, 2 cool, 3 heat, 4 forced cool, A forced defrost).
- Presses 17-21 = T2B per zone, 22-26 = room temp per zone, 27-31 = coil temp per zone, 32 = T3, 33 = T4, 34 = discharge temp.
- Press 45 (all sizes) = last fault or protection (00 = none). See the check switch table for the full list; the 18K board uses a slightly different order.
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Tables 25-26 p.29-31. Written in our own words; check the manual for your exact model.
Run the automatic wiring / piping correction
Mini split · Carrier DLCM(R/H)B multi-zone outdoor
The outdoor unit can find and fix crossed wiring vs piping ports by itself.
- Outdoor temperature must be above 41 F (5 C). Indoor units do not need to be running.
- Hold CHECK (SW1) on the outdoor board about 6 seconds until CE shows (FA may show first, keep holding).
- Indoor units go to 76 and the compressor runs for about 5-10 minutes.
- When CE changes to 00 it is done. Set each indoor unit back with its remote (they stay at 76).
Applies to: DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Source: DLCMRBH/DLCMHBH Multi-Zone Outdoor Service Manual (sold as Midea, Carrier and Viessmann Vitocal 200-S; Viessmann doc 6225551-03, 12/2024), Automatic Wiring/Piping Correction p.6. Written in our own words; check the manual for your exact model.
Activate 46°F (8°C) heating set-back
Mini-split · D5FSOAH
Activates freeze protection heating set-back. The indoor display shows FP.
- Set the unit to HEAT mode and point the remote at the indoor unit.
- Press the down arrow until the setpoint is 60°F (16°C).
- Press the down arrow two more times within two seconds to set 46°F (8°C).
Applies to: HEAT mode only
Source: D5FSOAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Connect inverter test tool to outdoor unit
Mini-split · D5FSCAH / D5FLCAH
Use the test port on the outdoor unit for inverter diagnostics. Power must be off during connection.
- Shut off power and remove the electrical panel.
- Find the cable already connected to the test port on the outdoor unit.
- Connect the test tool connector to that cable.
- After service, put the female end back into the port.
- For Dr. SMART, connect the tool to the white terminal as shown in the manual.
- On 24K HH and 30K to 60K single zone units, read parameters on the diagnosis/check board display instead.
Applies to: Single zone outdoor units
Source: Carrier D5FSCAH / D5FLCAH service manual, p. 27. Written in our own words; check the manual for your exact model.
Connect the Dr. SMART inverter test tool
Mini-split · D5FSOA
The test tool connects to the inverter test port on the outdoor unit through the cable that is already attached.
- Shut off power and remove the electrical panel.
- Unplug the cable from the test port on the outdoor unit.
- Connect the test tool to the cable with the connector provided.
- After maintenance, insert the female end back into the port.
Applies to: D5FSOAH outdoor unit
Source: D5FSOAH service manual, p. 25. Written in our own words; check the manual for your exact model.
Enter and exit Inquiry Mode (remote)
Mini-split · D5FSFA
Inquiry Mode lets you step through service codes 0 to 30 on the remote display. It times out after 1 minute with no button press. Codes are scrolled with the UP or DOWN arrow.
- Press and hold On/Off and Fan together for 8 seconds to enter Inquiry Mode.
- Press UP or DOWN to move through codes 0 to 30. The display starts at 0.
- Press and hold On/Off and Fan together for 2 seconds to exit.
Applies to: Wireless remote controller
Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Enter service mode to query or change function settings
Mini-split · D5FSCAH / D5FLCAH
Use channel numbers 0 to 30 to read or change the service mode function values. Changes must be finished within 1 minute.
- Disconnect power, wait 2 minutes, then reconnect. The unit must be in standby.
- Press Power and Fan together for 8 seconds until the remote shows 0 and the mode icons appear.
- Press Up or Down to select the channel.
- Press Power for 2 seconds until the remote shows Ch.
- To read: press OK. The value shows on the indoor display.
- To change: press Up or Down to set the value, then press OK. The indoor unit shows CS when the value is saved.
- Disconnect power, wait 10 minutes, then reconnect.
- To exit: press Power for 2 seconds until the remote shows 0, then press Power and Fan together for 2 seconds.
Applies to: D5FSCAH / D5FLCAH
Source: Carrier D5FSCAH / D5FLCAH service manual, p. 30. Written in our own words; check the manual for your exact model.
Enter wireless AP mode
Mini-split · D5FSOAH
Used to configure the wireless network.
- Press the LED button seven times continuously within 10 seconds.
Applies to: Units with wireless module
Source: D5FSOAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Error codes shown on indoor units
Mini-split · D5CMHA
When the microprocessor detects an abnormal condition, the unit stops and an error code is shown on the indoor unit front panel. Use the displayed code to start troubleshooting.
- Check the indoor unit front panel for an error code.
- Look up the code in the fault code tables in the full manual.
Applies to: D5CMHA indoor fan coil units
Source: Carrier D5CMHA product data, p. 2. Written in our own words; check the manual for your exact model.
Fireplace operation
Mini-split · D5FSOAH
Fireplace operation is started and stopped from the BOOST button while in heating mode.
- In heating mode, hold BOOST for more than 5 seconds to start fireplace operation.
- Hold BOOST for more than 3 seconds to stop fireplace operation.
Applies to: Heating mode
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Forced defrost mode
Mini-split · D5FSFA
Forces a defrost cycle from the unit.
- Press and hold AUTO/COOL for 5 seconds to enter Forced DEFROSTING. The indoor fan stops and the defrost lamp lights.
- Use the remote controller to exit and turn the unit off to end normal defrost.
- To exit Forced DEFROSTING directly, press and hold AUTO/COOL for 5 seconds again.
Applies to: D5FSFAH 9K to 16K
Source: D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Forced DEFROSTING mode
Mini-split · D5FSFA
Forces a defrost cycle. The indoor fan stops and the defrost lamp lights. Exit with the remote or by holding the button again.
- Press and hold AUTO/COOL for 5 seconds to enter Forced DEFROSTING.
- To exit, press and hold AUTO/COOL for 5 seconds again, or use the remote to turn the unit off.
Applies to: Indoor unit
Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Louver positions and heating capacity test
Mini-split · D5FSHAH
Do not set the louver at too vertical an angle for long periods in COOL or DRY, because condensation can drip. Too small an angle in COOL or HEAT reduces performance. For heating capacity testing, set the vertical louver to its maximum angle. Do not move the louver by hand. Power the unit off and back on to reset the louver.
- Use SWING or the remote to set airflow angle.
- For heating capacity tests, set the louver to maximum angle.
- If the louver is out of position, turn the unit off, unplug it for a few seconds, then restart it.
Applies to: Indoor unit louver
Source: D5FSHAH Owner's Manual, p. 13. Written in our own words; check the manual for your exact model.
MANUAL button fallback operation
Mini-split · D5FSFAH
For use when the remote is lost, damaged or out of batteries. Each press of MANUAL changes the mode in turn.
- Press MANUAL once for AUTO mode (heat or cool).
- Press MANUAL twice for TEST mode, which runs COOLING for 30 minutes and then goes to AUTO.
- Press MANUAL three times to turn the system off.
- Note the preset conditions: set point 76°F (24°C), fan speed AUTO, discharge direction preset for the current COOL or HEAT operation.
Applies to: Indoor unit manual operation
Source: D5FSFAH Owner’s Manual, p. 11. Written in our own words; check the manual for your exact model.
Reach the outdoor control LEDs for troubleshooting
Mini-split · D5CMHA
Remove the outdoor unit top panel to get to the control compartment and the diagnostic LEDs.
- Remove the top panel of the outdoor unit.
- Read the diagnostic LEDs on the control board to help find the fault.
Applies to: D5CMHA outdoor units
Source: Carrier D5CMHA product data, p. 2. Written in our own words; check the manual for your exact model.
Read-only inquiry codes
Mini-split · D5FSFA
These codes show values only and cannot be changed. 6 = compressor target frequency; 7 = compressor run frequency; 9 = unit voltage; 10 = capacity test (special use); 11 = not available; 14 = indoor fan speed (multiply display number by 8 for RPM); 15 = relative humidity (units with RH sensor only); 16 = setpoint compensation temperature; 17 = dust concentration (not used); 18 = Wi-Fi signal strength in dBm, shown as 0 to 4 (4 is strongest). Codes 19 and 27 to 30 show not available.
- Enter Inquiry Mode and scroll to the code.
- Read the value on the display and convert as noted above.
Applies to: Indoor unit / remote inquiry
Source: Carrier D5FSFAH service manual, p. 17-19. Written in our own words; check the manual for your exact model.
Remote controller inquiry mode
Mini-split · D5FSFA
Lets the remote show numbered inquiry codes from 0 to 30.
- Press and hold On/Off and Fan together for 8 seconds to enter Inquiry Mode.
- The remote stays in Inquiry Mode for 1 minute with no button press.
- The display starts at 0. Press UP or DOWN to step through codes 0 to 30.
Applies to: D5FSFAH remote controller
Source: D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Review error memory (inquiry code 0)
Mini-split · D5FSFA
Code 0 shows the error memory. The display reads Ch. Press OK to send the stored error code query.
- Enter Inquiry Mode and select code 0.
- Press OK to query the error code memory.
Applies to: Indoor unit / remote inquiry
Source: Carrier D5FSFAH service manual, p. 17. Written in our own words; check the manual for your exact model.
Self-clean cycle
Mini-split · D5FS(L)AAH
Clean cycle cleans and dries the evaporator. It runs 30 minutes and then shuts the unit off. It can only start in COOL or DRY mode. Pressing CLEAN during the cycle cancels it and turns the unit off.
- Press CLEAN in COOL or DRY mode to start the cycle.
- Press CLEAN during the cycle to cancel.
Applies to: Indoor unit with self-clean
Source: Carrier D5FS(L)AAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Set the lower air louver (size 12)
Mini-split · D5FSFAH
The lower air louver is set with a button on the electric control box behind the front filter service door. The display shows ON-OPEN or OF-CLOSED during setting.
- Turn the breaker OFF before opening the front panel.
- Open the front filter service door to reach the electric control box.
- Turn the unit on and, within 10 minutes of power-on, press the AIR LOUVER button for 5 seconds to enter the standby setting mode.
- Press the AIR LOUVER button to open or close the lower air louver.
- Confirm the status on the display: ON-OPEN or OF-CLOSED.
Applies to: Floor console indoor unit, lower air discharge
Source: D5FSFAH Owner’s Manual, p. 14-15. Written in our own words; check the manual for your exact model.
Reset & cancel
Clearing lockouts, service reminders and fault history; skipping purge or de-air programs.
Auto start after power failure
Air handler · D5FS(L)AAH
If power fails during operation, the unit stores its operating condition and restarts it automatically when power returns.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Cancel TURBO, SLEEP and CLEAN early
Air handler · D5FUH
TURBO can be ended early by pressing it again. SLEEP cancels when MODE, TEMP, FAN, TIMER or ON/OFF is pressed. CLEAN can be cancelled mid-cycle by pressing CLEAN again.
- Press TURBO again to end TURBO mode early.
- Press MODE, TEMP, FAN, TIMER or ON/OFF to cancel SLEEP.
- Press CLEAN during the cycle to cancel self-clean and turn the unit off.
Applies to: Wireless remote
Source: Carrier D5FUHAQ owner's manual, p. 14. Written in our own words; check the manual for your exact model.
Exit INQUIRY mode and lock buttons
Air handler · D5FUAA
Ends the service session. Remote buttons are disabled for a period after exiting.
- When finished, press ON/OFF and FAN SPEED together for 2 seconds to exit INQUIRY mode.
- Expect all remote buttons to be disabled for 60 seconds after exit.
Applies to: Wireless remote, D5FUAA air handler
Source: Carrier D5FUAA installation instructions, p. 48. Written in our own words; check the manual for your exact model.
Exit INQUIRY mode and lock changes
Air handler · D5FUAA
Exiting disables the remote buttons for a short time. Changes only lock in after the outdoor unit is powered down.
- When finished, press ON/OFF and FAN SPEED together for 2 seconds to exit INQUIRY mode.
- Wait 60 seconds. All remote buttons are disabled during this time.
- Power down the outdoor unit for 3 minutes after all service changes to lock them in.
Applies to: D5FUAA wireless remote controller
Source: D5FUAA installation instructions, p. 48. Written in our own words; check the manual for your exact model.
Leave SERVICE mode, exit INQUIRY and lock in changes
Air handler · D5FSAA, D5FLAA
Changes made in SERVICE mode are not locked in until the outdoor unit is power cycled.
- Press ON/OFF for 2 seconds to leave SERVICE mode and return to INQUIRY mode.
- Press ON/OFF and FAN SPEED together for 2 seconds to exit INQUIRY mode.
- Expect the remote buttons to be disabled for 60 seconds after exiting.
- Turn off the outdoor unit for 3 minutes after all service changes to lock them in.
Applies to: Wireless remote controller, D5FSAA and D5FLAA air handler ductless systems
Source: Carrier D5FSAA/D5FLAA installation instructions, p. 35. Written in our own words; check the manual for your exact model.
Remote control reset after battery removal
Air handler · D5FS(L)AAH
Removing the remote batteries cancels current settings and returns the control to initial settings in STANDBY.
- Press TURBO to activate the remote after new batteries are installed.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Remote reset after battery removal
Air handler · D5FUAAH
Removing the batteries erases all remote settings and returns the remote to its initial state.
- Remove the batteries to reset the remote to its initial settings.
- The remote enters STANDBY mode.
- Press TURBO to wake the remote.
- Reprogram the settings after fitting new batteries.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: D5FUAAH Owner's Manual, p. 11, p. 14. Written in our own words; check the manual for your exact model.
Remote settings are lost when batteries are removed
Air handler · D5FUH
Removing the remote batteries cancels the stored settings and returns the remote to its initial state in STANDBY. The remote must be set up again after new batteries are installed.
- Reinstall or replace the batteries.
- Press TURBO on the remote to activate it.
- Reprogram or re-enter the required settings.
Applies to: Wireless remote
Source: Carrier D5FUHAQ owner's manual, p. 11 and p. 14. Written in our own words; check the manual for your exact model.
Restart after power failure
Air handler · D5FS(L)AAH
The system stops at power loss. When power returns the Operation light flashes. Press ON/OFF on the remote to restart. If auto restart applies, the unit restarts with the same settings. If the unit reverts to factory defaults (AUTO mode, AUTO fan, 76°F/24°C), update the remote to match the unit.
- Press ON/OFF on the remote to restart.
- Use the remote to correct any mismatch between remote and unit panel.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Clear the stored fault history (3-digit display furnaces)
Furnace · 59SC6A, Payne PG96VTA, 59MN7C
Wipes the fault history from the FLt menu.
- Scroll the main menu to FLt with MENU/SELECT
- Scroll to Clr
- Press MENU/SELECT
Applies to: 59SC6A, Payne PG96VTA and 59MN7C furnaces (3-digit display control)
Source: Carrier 59SC6A installation instructions, Table 21 Main Menu Options, p.53; Payne PG96VTAB installation instructions, Main Menu Options table, p.53; Carrier 59MN7C installation instructions, Table 18 Main Menu Options, p.47. Written in our own words; check the manual for your exact model.
Reset all settings to factory defaults (3-digit display furnaces)
Furnace · 59SC6A, Payne PG96VTA, 59MN7C
The rSt menu item resets all installer settings to factory defaults when YEs is selected.
- Scroll the main menu to rSt with MENU/SELECT
- Press NEXT/OPTION and step to YEs
- Press MENU/SELECT to save; the display flashes three times
Applies to: 59SC6A, Payne PG96VTA and 59MN7C furnaces (3-digit display control)
Source: Carrier 59SC6A installation instructions, Table 21 Main Menu Options, p.53; Payne PG96VTAB installation instructions, Main Menu Options table, p.53; Carrier 59MN7C installation instructions, Table 18 Main Menu Options, p.47. Written in our own words; check the manual for your exact model.
Exit Inquiry Mode
Heat pump · D5FCFA
Inquiry Mode is left with a press-and-hold combination on the remote.
- Press and hold the On/Off and Fan buttons together for 2 seconds.
Applies to: D5FCFAH remote control
Source: Carrier D5FCFAH service manual, p. 26. Written in our own words; check the manual for your exact model.
Cancel a set function
Mini-split · D5FSOAH
Turns off a function selected with the SET button.
- Repeat the same steps used to select the function.
Applies to: D5FSOAH
Source: D5FSOAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Cancel TURBO and SLEEP
Mini-split · D5FSFAH
TURBO ends by itself after 20 minutes or when pressed again. SLEEP cancels when MODE, TEMP, FAN, TIMER or ON/OFF is pressed.
- To cancel TURBO early, press TURBO again.
- To cancel SLEEP, press MODE, TEMP, FAN, TIMER or ON/OFF on the remote.
Applies to: Wireless remote controller
Source: D5FSFAH Owner’s Manual, p. 14, 16. Written in our own words; check the manual for your exact model.
Power cycle and remote restart
Mini-split · D5FSHAH
A simple reset can clear an erratic operation problem.
- Disconnect the power, then reconnect it.
- Press ON/OFF on the remote control to restart operation.
Applies to: Indoor unit and remote control
Source: D5FSHAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Power-cycle the unit after a flashing indicator or error code
Mini-split · D5FCFAH
Wait first, then power cycle if the lamps or code remain.
- Wait about 10 minutes.
- Disconnect the power, then reconnect it.
- Turn the unit on.
Applies to: All models
Source: Carrier D5FCFAH owner's manual, p. 17. Written in our own words; check the manual for your exact model.
Power-cycle the unit after erratic operation
Mini-split · D5FSHA
A simple reset can clear interference-related faults.
- Disconnect the power.
- Reconnect the power.
- Press ON/OFF on the remote control to restart.
Applies to: Indoor unit and remote control
Source: Carrier D5FSHA installation manual, p. 25. Written in our own words; check the manual for your exact model.
Remote control reset after battery removal
Mini-split · D5FSFAH
Removing the remote batteries erases current settings and returns the control to initial settings in STANDBY.
- Replace the batteries.
- Push ON/OFF to activate the remote.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Remote control settings erased when batteries are removed
Mini-split · D5FCFAH
Removing the remote batteries erases all programmed settings. The remote must be reprogrammed after new batteries are inserted.
- Reprogram the remote control after inserting new batteries.
Applies to: D5FCFAH wireless remote controller
Source: Carrier D5FCFAH owner's manual, p. 13. Written in our own words; check the manual for your exact model.
Remote settings are lost when batteries are removed
Mini-split · D5FSFAH
Removing the remote batteries erases all programmed settings and returns the remote to its initial state in standby.
- Install two new AAA 1.5V alkaline batteries, following the polarity marks.
- Reprogram the settings on the remote.
- Press ON/OFF to wake the remote from standby.
Applies to: Wireless remote controller
Source: D5FSFAH Owner’s Manual, p. 11, 16. Written in our own words; check the manual for your exact model.
Reset after an error code appears
Mini-split · D5FUHAQ
Error codes starting with E, P or F, or EH, EL, EC, PH, PL, PC, may clear on their own. Use the steps in order.
- Wait about 10 minutes.
- If the code remains, disconnect the power, then reconnect it and turn the unit on.
- If the problem persists, disconnect the power and contact the nearest customer service center.
Applies to: Indoor and outdoor units
Source: Carrier D5FUHAQ Owner's Manual, p. 19. Written in our own words; check the manual for your exact model.
Reset horizontal louver
Mini-split · D5FSOAH
Resets the horizontal louver settings after the angle memory function has set the louver.
- Press the manual button on the indoor unit.
- Do not set the horizontal louver angle too small, as condensation may form and drip into the machine.
Applies to: Units with louver angle memory
Source: D5FSOAH Owner's Manual, p. 13. Written in our own words; check the manual for your exact model.
Reset remote after battery removal
Mini-split · D5FS(L)AAH
Removing the batteries cancels current settings and returns the remote to its initial settings in STANDBY mode.
- Install new batteries.
- Press TURBO on the remote to activate it.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FS(L)AAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Restart delay after shutdown
Mini-split · D5FSHAH
The unit has a 3-minute protection feature to prevent overloading, so it cannot restart within three minutes of being turned off.
- Wait three minutes after the unit is turned off before restarting.
Applies to: Indoor and outdoor units
Source: D5FSHAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Settings shortcuts
Where the useful parameters live and what they are set to from the factory.
Change operating mode with the Mode button
Air conditioner · DLFULA
Each press of the Mode button (M) on the interface cycles through the operating modes. The heat pump only mode and the furnace only AUX mode appear in the cycle. For dual fuel, keep pressing until HEAT+AUX shows.
- Press the Mode button (M) to change the operating mode.
- Continue pressing to step through: Auto, Cool, Dry, Heat (heat pump only), AUX (furnace only), Heat, AUX (dual fuel), Fan.
- For dual fuel operation, press the Mode button until HEAT+AUX is displayed.
Applies to: DLFULA interface mode selection (Fig. 17)
Source: DLFULA Installation Instructions, p. 17. Written in our own words; check the manual for your exact model.
Airflow adjustment in Engineer Mode
Air handler · D5FUHA
Computational Constant Airflow adjusts fan speed and output to match ductwork, blocked coils and dirty filters. Air volume can be changed to customer needs through Engineer Mode on the remote or wired controller.
- Enter Engineer Mode on the wireless remote or the wired controller.
- Adjust the air volume setting as required for the customer.
- Check that airflow is adequate for the ductwork and filter in use.
Applies to: D5FUHA
Source: D5FUHA product data, p. 2. Written in our own words; check the manual for your exact model.
CLEAN (self-cleaning) mode
Air handler · D5FS(L)AAH
Cleans and dries the evaporator in a 30-minute cycle, then shuts off. Works only in COOL or DRY mode. Pressing CLEAN mid-cycle cancels it and turns the unit off.
- Set the unit to COOL or DRY mode.
- Press CLEAN to start the cycle.
- Press CLEAN during the cycle to cancel and turn off.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
CODE 22 heating temperature compensation
Air handler · D5FUHA
INQUIRY CODE 22 sets heating temperature compensation. Its default is 0. The manual gives -6 as the maximum DOWN range. It does not give the full allowable range or the upper limit.
- Enter INQUIRY mode and scroll to CODE 22.
- Enter SERVICE mode for CODE 22 and set the required compensation value.
- Exit SERVICE mode, exit INQUIRY mode, and power-cycle the outdoor unit for 3 minutes.
- Record the value set, because CODE 22 will show 0 on the next visit.
Applies to: D5FUHA remote controller, INQUIRY CODE 22
Source: D5FUHA installation instruction manual, p. 49. Written in our own words; check the manual for your exact model.
LED display light
Air handler · D5FS(L)AAH
Turns the display light on and off from the remote.
- Press LED on the remote.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
SLEEP mode
Air handler · D5FUAAH
Saves energy at night. Available in COOL, HEAT or AUTO only, and not in FAN or DRY.
- Press SLEEP on the remote.
- In COOL, the set point rises 2°F (1°C) after 1 hour and another 2°F (1°C) after a second hour, with fan on low speed.
- In HEAT, the set point drops by the same steps.
- Any press of MODE, TEMP, FAN, TIMER or ON/OFF cancels SLEEP.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 14, p. 15. Written in our own words; check the manual for your exact model.
SLEEP mode (remote, COOL/HEAT/AUTO)
Air handler · D5FS(L)AAH
SLEEP saves energy and works only in COOL, HEAT or AUTO. In COOL the setpoint rises 2°F (1°C) after 1 hour and another 2°F after a second hour, with low fan speed. In HEAT the setpoint drops by the same steps. The manual gives conflicting shutdown times (see notes). SLEEP cancels when MODE, TEMP, FAN, TIMER or ON/OFF is pressed on the remote.
- Press SLEEP on the remote while in COOL, HEAT or AUTO.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Sleep operation (remote only, not in FAN or DRY)
Air handler · D5FS(L)AAH
Sleep is only available from the remote and not in FAN or DRY mode. In COOL the temperature rises 2°F (1°C) after 1 hour and another 2°F after a second hour. In HEAT it drops by the same steps. Per this section, sleep stops after 8 hours and the system keeps running in its final state. This conflicts with the 5-hour figure on p. 16.
- Press SLEEP on the remote before going to sleep.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Timer ON and TIMER OFF
Air handler · D5FUAAH
Starts or stops the unit at set times. Each can be used alone or together.
- Press TIMER ON (or TIMER OFF) to set the time. Each press adds 30 minutes up to 10 hours, then 60 minutes until 24 hours.
- When TIMER ON is set, the light on the unit comes on.
- To cancel, set the timer back to 0.0.
- To use both, set TIMER OFF and TIMER ON so the unit starts and stops at the chosen times.
- Keep the remote within 26 ft (8 m) of the unit when the timer is used.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 11, p. 13, p. 14. Written in our own words; check the manual for your exact model.
Timer ON/OFF setting
Air handler · D5FS(L)AAH
Timer is set with the remote. For a unit that is off, set TIMER ON first then TIMER OFF, so it starts at the ON time and stops at the OFF time. For a unit that is on, set TIMER OFF first then TIMER ON, so it stops at the OFF time and starts at the ON time.
- Unit off: set TIMER ON, then set TIMER OFF.
- Unit on: set TIMER OFF, then set TIMER ON.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
TURBO mode
Air handler · D5FUAAH
Heats or cools the room quickly by running the fan at super high speed.
- Press TURBO. An audible beep confirms if the indoor unit supports it.
- Press TURBO again to end it immediately.
- TURBO ends automatically after 20 minutes and the unit returns to its previous setting.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 14. Written in our own words; check the manual for your exact model.
Turn the indoor unit display LED on or off
Air handler · D5FUH
The LED button turns the indoor unit display light and the buzzer on or off for a quieter room.
- Press LED on the remote to toggle the indoor display and buzzer.
Applies to: Wireless remote
Source: Carrier D5FUHAQ owner's manual, p. 9 and p. 14. Written in our own words; check the manual for your exact model.
Show supply and return air temperature on the display (59MN7C)
Furnace · 59MN7C
The t° menu item turns on a rotating display of mode, supply air temperature (SAT), return air temperature (RAT) and the difference. Default is off; it only shows while heating, cooling or heat pump operation is running.
- Scroll to t° in the main menu
- Choose F or C (or off)
- If the displayed SAT does not agree with a thermometer, move the SAT sensor further from the furnace or past a bend in the duct
Applies to: 59MN7C modulating furnace
Source: Carrier 59MN7C installation instructions, Temperature Display, Table 18, p.47. Written in our own words; check the manual for your exact model.
46.4°F (8°C) heating setback
Mini-split · D5FCFA
In heating mode the set point can go as low as 46.4°F (8°C) to protect an unoccupied space from freezing.
- Set heating mode.
- Set the temperature to 46.4°F (8°C).
Applies to: D5FCFA heat pump units
Source: Carrier D5FCFA product data, p. 6. Written in our own words; check the manual for your exact model.
Activate SILENCE
Mini-split · D5FSOA
Silence runs the compressor at a lower frequency than F3 and the indoor fan at faint breeze (1%). Not available on Multi-Zone systems and disabled when matched with multi outdoor units.
- Press Silence on the remote, or hold FAN for more than 2 seconds.
Applies to: D5FSOA single-zone units
Source: D5FSOA Product Data, p. 6. Written in our own words; check the manual for your exact model.
Air direction louver control
Mini-split · D5FSFAH
Each SWING press moves the up-down louver 30 degrees. Holding SWING for 2 seconds starts vertical auto swing on some units. Do not move the louver by hand.
- Press SWING to step the louver to the next position.
- Hold SWING for 2 seconds to start vertical auto swing (some units only).
- If the louver has been moved by hand out of range, turn the unit off, then back on.
Applies to: Indoor unit louvers
Source: D5FSFAH Owner’s Manual, p. 9, 14. Written in our own words; check the manual for your exact model.
Airflow from upper or lower outlets
Mini-split · D5FSFAH
The floor console has a dual airflow switch. Single airflow sends air only from the upper outlet, which suits sleeping. The lower outlet is only on size 12.
- Open the front panel to reach the airflow selection switch (turn breaker OFF first).
- Set the switch to single airflow to send air only from the upper outlet.
- Leave it in dual airflow to let the unit choose the blowing pattern automatically.
Applies to: Floor console indoor unit, size 12 for lower outlet
Source: D5FSFAH Owner’s Manual, p. 15. Written in our own words; check the manual for your exact model.
Auto-restart after power loss
Mini-split · D5FSCAH / D5FLCAH
The indoor auto-restart module saves current settings and restores them after a power failure.
- Settings are restored automatically within 3 minutes after power returns.
- Channel 1 in service mode turns auto-restart on (1) or off (0).
Applies to: Indoor unit
Source: Carrier D5FSCAH / D5FLCAH service manual, p. 25 and 31. Written in our own words; check the manual for your exact model.
Breeze Away
Mini-split · D5FSOAH
Keeps direct airflow off the room occupants. Available in COOL, FAN and DRY modes only.
- Press SET, then select Breeze Away and press OK to confirm.
Applies to: COOL, FAN and DRY modes
Source: D5FSOAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Change indoor unit from 12K to 9K capacity
Mini-split · D5FSCAH, D5FLCAH
Downsizing a 45MBCAQ12XA3 indoor unit from 12K to 9K BTU/h using the ENC1 rotary switch. Other capacities stay at factory setting.
- Check that ENC1 is at 0 (the 12K default).
- Disconnect power first.
- Open the electronic control box and set ENC1 to 2. Close the box.
- Restore power. The unit now runs as a 9K.
Applies to: 45MBCAQ12XA3 indoor unit
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 14-15. Written in our own words; check the manual for your exact model.
Cycle through ECO and GEAR energy modes
Mini-split · D5FSHAH
The ECO/GEAR button steps through the energy saving options.
- Press ECO/GEAR to cycle ECO, GEAR 75%, GEAR 50%.
Applies to: Wireless remote control (not available with multi-zone condensers)
Source: Carrier D5FSHAH Owner's Manual, p. 6-7. Written in our own words; check the manual for your exact model.
Cycle through fan speeds
Mini-split · D5FSHAH
The FAN button steps through the fan speed options. Fan speed can also be fine-tuned with TEMP.
- Press FAN to cycle AUTO, 20%, 40%, 60%, 80%, 100%.
- Press TEMP up or down to change fan speed in 1% steps.
Applies to: Wireless remote control
Source: Carrier D5FSHAH Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.
Cycle through operating modes
Mini-split · D5FSHAH
The MODE button steps through the operating modes in a fixed order.
- Press MODE to step through AUTO, COOL, DRY, HEAT and FAN.
- HEAT is only available on heat pump models.
Applies to: Wireless remote control
Source: Carrier D5FSHAH Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.
Cycle through remote feature functions
Mini-split · D5FSHAH
The SET button scrolls through extra operating features, and OK confirms the selected one.
- Press SET to scroll through Breeze Away, Clean, Fresh, Sleep, Follow Me, AP mode and Breeze Active.
- Press OK to confirm the flashing symbol.
Applies to: Wireless remote control
Source: Carrier D5FSHAH Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.
Dry mode humidity adjustment
Mini-split · D5FCFAH
In DRY mode the room humidity can be set from 35% to 85% in 5% steps. The humidity sensor is not active on floor consoles matched with multi-zone outdoor units or when a wired controller is used.
- Select DRY mode.
- Press the HUMIDITY button to set the target in 5% steps between 35% and 85%.
Applies to: D5FCFAH wireless remote controller
Source: Carrier D5FCFAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.
ECO and GEAR energy-saving modes
Mini-split · D5FSFAH
ECO is only available in COOLING mode. It holds the temperature between 75°F and 86°F with AUTO fan and lasts 8 hours. GEAR steps down to 75% and 50% of electrical consumption.
- In COOLING mode, press ECO/GEAR to start ECO.
- Press ECO/GEAR again to cycle to GEAR 75% and then GEAR 50%.
- Keep cycling to return to the previous setting before ECO.
Applies to: Wireless remote controller, cooling mode
Source: D5FSFAH Owner’s Manual, p. 9, 14. Written in our own words; check the manual for your exact model.
ECO energy mode
Mini-split · D5FCFAH
Press ECO to enter energy efficient mode. In COOLING, the unit adjusts the set point to 75 F (24 C) and uses AUTO fan when the set point is below 75 F. ECO ends after 8 hours, or when ECO is pressed again, the mode is changed, or the set point is lowered below 75 F.
- Press ECO to enter the mode.
- Press ECO again, change mode, or set below 75 F (24 C) to exit early.
Applies to: Single-zone D5FCFAH systems
Source: Carrier D5FCFAH owner's manual, p. 8, 12. Written in our own words; check the manual for your exact model.
ECO energy saving mode
Mini-split · D5FCFA
In cooling, ECO sets the temperature to 75°F / 24°C and fan to auto, only if the set point is below 75°F. ECO runs for 8 hours.
- In cooling mode, press ECO on the remote.
- Press ECO again, change mode, or set the temperature below 75°F / 24°C to leave ECO.
Applies to: D5FCFA single-zone units
Source: Carrier D5FCFA product data, p. 6. Written in our own words; check the manual for your exact model.
ECO function (not on multi-zone systems)
Mini-split · D5FCFA
In cooling, ECO sets the remote to 75°F (24°C) with Auto fan if the setpoint is below 75°F. If the setpoint is between 75°F and 86°F, only the fan changes to Auto. ECO ends when ECO is pressed again, the mode changes, the setpoint is moved below 75°F, or after 8 hours.
- Press ECO in cooling to start.
- Press ECO again, change mode, or lower the setpoint below 75°F to exit early.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 19-20. Written in our own words; check the manual for your exact model.
Energy consumption control (Gear button)
Mini-split · D5FSOA
Gear button cycles the remote through the energy efficient mode sequence. Turning the unit off or activating ECO, SLEEP, Super Cool, 8°C heating, Silence or self clean cancels it.
- Press the Gear button on the remote to enter the energy efficient sequence.
Applies to: D5FSOA single-zone units
Source: D5FSOA Product Data, p. 7. Written in our own words; check the manual for your exact model.
Enter Silence mode from the remote
Mini-split · D5FCFA
Silence mode lowers the compressor frequency and runs the indoor fan at faint breeze. It is not available on multi-zone systems or with a multi outdoor unit.
- Press Silence on the remote control.
- Or hold FAN for more than 2 seconds on the remote control.
Applies to: D5FCFA single-zone units
Source: Carrier D5FCFA product data, p. 6. Written in our own words; check the manual for your exact model.
Fan speed limits by mode
Mini-split · D5FS(L)AAH
Fan speed can be set in COOL, HEAT and FAN modes. It cannot be adjusted in AUTO or DRY mode, where the unit sets it automatically.
- Press FAN to select the fan speed in COOL or HEAT.
- Set FAN mode speed with the FAN button.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FS(L)AAH owner's manual, p. 12, 14, 15. Written in our own words; check the manual for your exact model.
Fan speed selection order
Mini-split · D5FSFAH
The fan speed cycles AUTO, 20%, 40%, 60%, 80%, 100%. Fan speed cannot be set in AUTO or DRY mode. TEMP up or down changes fan speed in 1% steps.
- Press FAN to step through AUTO, 20%, 40%, 60%, 80% and 100%.
- To fine-tune, press TEMP up or down to change fan speed in 1% steps.
- In AUTO or DRY mode, expect the fan speed to be set automatically.
Applies to: Wireless remote controller, all modes
Source: D5FSFAH Owner’s Manual, p. 9, 11, 12. Written in our own words; check the manual for your exact model.
Follow Me function
Mini-split · D5FCFAH
When Follow Me is active, the remote sends its temperature signal every 3 minutes with no beeps. The function turns off if no signal is received for 7 minutes or if Follow Me is pressed again. The unit does not change mode from its own temperature setting.
- Press FOLLOW ME to activate or deactivate.
Applies to: D5FCFAH wireless remote controller
Source: Carrier D5FCFAH owner's manual, p. 12. Written in our own words; check the manual for your exact model.
Remote control feature availability
Mini-split · D5FS(L)AAH
Intelligence Sensor and Vertical Swing are not available on this unit. Several functions such as Humidity Control, ECO, Active Clean, Gear and Silent Mode are not available when matched with multi-zone condensers. Some indicators on the remote are marked not applicable for this unit.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FS(L)AAH owner's manual, p. 11-12. Written in our own words; check the manual for your exact model.
Remote control setpoint and fan ranges
Mini-split · D5FSOAH
Temperature and humidity limits and the fan speed sequence on the remote.
- Temperature setpoint range is 16°C (60°F) to 30°C (86°F), changed in 0.5°C (1°F) steps.
- Dehumidification humidity range is 35% to 85%, changed in 5% steps.
- Fan speed order: AUTO, then 20%, 40%, 60%, 80%, 100%. Fan speed can be adjusted in 1% steps with the TEMP buttons.
Applies to: Wireless remote RG10L5(2HS)
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
SILENCE mode and LED light
Mini-split · D5FSFAH
SILENCE lowers indoor fan to faint breeze (1% fan speed). LED toggles the display light.
- Press SILENCE on the remote to turn the function on.
- Press LED to turn the display light on or off.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
SLEEP mode
Mini-split · D5FSFAH
Energy-saving mode for COOL, HEAT or AUTO. Works with the remote control only.
- Press SLEEP.
- In COOLING, the set point rises 1.8 F (1 C) after 1 hour, rises another 1.8 F after a second hour, and the fan runs low; unit shuts off 5 hours after setting.
- In HEATING, set points are lowered by 1.8 F (1 C).
- SLEEP cancels if MODE, TEMP, FAN, TIMER or ON/OFF is pressed.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Switch remote between F and C
Mini-split · D5FSHAH
The remote defaults to Fahrenheit. To change the display to Celsius, press and hold the + and - temperature buttons together for about 3 seconds.
- Point the remote at the unit.
- Press and hold the + and - set point buttons together for about 3 seconds.
Applies to: Wireless remote controller
Source: D5FSHAH Owner's Manual, p. 10. Written in our own words; check the manual for your exact model.
Temperature set point limits on remote
Mini-split · D5FS(L)AAH
The set point range depends on model: 60-86 F (16-30 C) or 68-82 F (20-28 C). The unit accepts set points from 62 F (17 C) to 86 F (30 C) in 1 F or 1 C steps. Temperature can be raised or lowered in 1 F (0.5 C) steps.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FS(L)AAH owner's manual, p. 12, 14, 15. Written in our own words; check the manual for your exact model.
Timer function
Mini-split · D5FCFA
24-hour timing range. Timer modes: TIMER ON, TIMER OFF, TIMER ON/OFF and TIMER OFF/ON. The timer does not change the current operation mode. Setting TIMER OFF on an off unit will not start it. Times are relative and the timer exits if a malfunction occurs.
- Select the timer mode on the remote.
- Set the on and/or off times within the 24-hour range.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 19. Written in our own words; check the manual for your exact model.
Timer ON and TIMER OFF
Mini-split · D5FSFAH
Timer ON starts the unit at a set time; TIMER OFF stops it. Both can be used separately or together.
- Press TIMER ON to set the start time; each press adds 30 minutes up to 10 h, then 60 minutes up to 24 h.
- Press TIMER OFF to set the stop time with the same increments.
- Set the timer to 0.0 to cancel it.
- To program both, set TIMER ON and TIMER OFF in the order described in the manual for the unit's current state.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
TURBO mode
Mini-split · D5FSFAH
Rapid cooling or heating; fan runs on super high speed.
- Press TURBO; a beep sounds if the indoor unit supports it.
- TURBO ends automatically after 20 minutes.
- To cancel early, press TURBO again; the unit returns to its previous setting.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Commissioning
Start-up and set-up steps that are easy to miss.
Refrigerant charging mode on Infinity control (25VNA8/24VNA9)
Air conditioner · Carrier Infinity 19VS 24VNA9
Opened from the Installation and Service screen to check or set charge. Offers weigh-in or heating check methods; the heating check runs at stage 5 with matched fans and counts down while stabilizing. Service-valve subcooling shows only when temperatures are in range.
- On the Infinity control open Installation and Service, then Refrigerant Charging
- Pick the charge method on the Charging Mode Selection screen
- Wait for the stabilization countdown before reading pressures
Applies to: Carrier Infinity 25VNA8/24VNA9 communicating systems
Source: Carrier 25VNA8/24VNA9 service manual, Check Charge and Heating Check Chart Procedure, p.9-12. Written in our own words; check the manual for your exact model.
Burial limit for refrigerant tubing
Air conditioner · DLFULA
Do not bury more than 36 in. of refrigerant tubing. A buried section needs a 6 in. vertical rise to the outdoor unit valve connections, or refrigerant can migrate to the buried section and cause slugging at start-up.
Applies to: Buried refrigerant lines
Source: DLFULA Installation Instructions, p. 14. Written in our own words; check the manual for your exact model.
Clearance from combustibles with auxiliary electric heater
Air conditioner · DLFULA
Units with an auxiliary electric heater must stay at least 3 ft (1 m) away from combustible materials. Do not install the unit where combustible gas can collect.
- Measure at least 3 ft (1 m) from any combustible material.
- Confirm the install site is not exposed to combustible gas leaks.
Applies to: DLFULA units with auxiliary electric heater
Source: DLFULA installation instructions, p. 3. Written in our own words; check the manual for your exact model.
Condensate drain connection
Air conditioner · DLFULA
Two 3/4 in. female threaded connections are on each coil condensate pan. Use PVC fittings and do not over-tighten.
- Tighten the fittings finger tight plus 1-1/2 turns.
- Install a plastic plug in the unused drain fitting.
- Pitch the condensate line 1 in. per 10 ft to an open drain or sump.
- A trap is not needed if the drain is on the supply air side of the furnace, unless local code requires one.
- If a trap is needed, install it as close to the coil as possible, at least 3 in. deep and no higher than the bottom of the drain opening.
- Make sure the trap outlet is below its connection to the pan, prime all traps, and leak test.
- Insulate traps and lines if they run above a living area.
Applies to: Condensate drain lines
Source: DLFULA Installation Instructions, p. 14. Written in our own words; check the manual for your exact model.
Condensate trap and secondary drain when unit is over living space
Air conditioner · DLFULA
If the unit sits in or above a living space where condensate overflow could cause damage, add a field-supplied external pan under the whole unit with a secondary condensate line and trap running into it. An alternative, where local code allows, is a separate 3/4 in (19 mm) condensate line with trap to a visible drain point. Tell the owner that flow from the secondary drain means the unit needs service. Fit a float switch to shut the unit off if the secondary pan water rises too high.
- Check whether the unit is in or above a living space where overflow could cause damage.
- Install a field-supplied external condensate pan under the entire unit if required.
- Run a secondary condensate line with an appropriate trap from the unit into the pan.
- Drain the external pan to a noticeable location.
- Where local code allows, use a separate 3/4 in (19 mm) condensate line with trap to a visible point instead of the pan.
- Install a float switch to shut the unit off if the secondary pan water gets too high.
- Tell the owner that secondary drain flow means the unit needs servicing.
Applies to: DLFULA air conditioner condensate drain (Fig. 15 Trap)
Source: DLFULA Installation Instructions, p. 16. Written in our own words; check the manual for your exact model.
Waste (sewer) line connection with air gap trap
Air conditioner · DLFULA
When the condensate line goes to a waste or sewer line, an open trap must be installed ahead of the waste line to keep sewer gases out. The drain line needs an air gap at the trap. Failure to do this can cause personal injury or death.
- Install an open trap ahead of the waste (sewer) line.
- Provide a 3 in (76 mm) air gap above the liquid level at the trap.
- Confirm the air gap is present in the drain line before connecting to the sewer line.
Applies to: DLFULA condensate drain to sewer (Fig. 16 Air Gap)
Source: DLFULA Installation Instructions, p. 16. Written in our own words; check the manual for your exact model.
1:1 single zone test run
Air handler · D5FUHA
For 1:1 single zone systems, set a call for the test operation and let it run.
- Adjust the set-point to create a call for the desired test operation.
- Run the system for at least 10 minutes.
- Record the set-point, mode, and temperatures T1 through LA/Lr.
- Record any indoor or outdoor error codes, plus wall controller and 24V interface notes.
Applies to: D5FUHA single zone systems
Source: D5FUHA Installation Instructions, p. 69. Written in our own words; check the manual for your exact model.
24V interface for third-party thermostat
Air handler · D5FUHA
The built-in 24V interface lets a third-party thermostat control the ductless system.
- Wire the third-party thermostat to the built-in 24V interface.
- Check control operation at the indoor unit after wiring.
Applies to: D5FUHA
Source: D5FUHA product data, p. 2, 4. Written in our own words; check the manual for your exact model.
24V thermostat interface
Air handler · D5FSAA
The 24V interface works with any single-stage third-party heat pump thermostat. A heat pump thermostat must be used.
- Set control scenario with SW1 and S1 + S2 per the control scenario table.
- Confirm the thermostat is a heat pump type before wiring.
Applies to: Units controlled by a third-party thermostat
Source: D5FSAA Product Data, p. 12. Written in our own words; check the manual for your exact model.
Additional refrigerant charge for longer line sets (R-454B)
Air handler · D5FUHA
Only charge extra refrigerant when the pipe run is longer than the 25 ft (7.5 m) standard. Never mix refrigerant types, as this damages the equipment. Charge through the service port on the outdoor unit's low pressure valve. The page's Table 28 header is partly cut off, but the formula for the 3/8 in. liquid line is legible.
- Measure the total installed liquid line length.
- Subtract the standard length of 25 ft (7.5 m).
- Multiply the difference by 65 g/m (0.7 oz/ft).
- Charge the result through the outdoor unit low pressure service port.
- Record the pipe length and additional charge (the test run checklist asks for both).
Applies to: D5FUHA with R-454B refrigerant, 3/8 in. (9.52 mm) liquid line
Source: Carrier D5FUHA Installation Instructions, p. 61. Written in our own words; check the manual for your exact model.
Air evacuation of the refrigerant circuit
Air handler · D5FUHA
Evacuate the circuit on first install and whenever the unit is relocated. Air and moisture raise pressure, lower efficiency and can damage the unit. Check that the refrigerant pipes between indoor and outdoor units and all wiring are connected correctly before starting.
- Connect the manifold gauge charge hose to the service port on the outdoor unit's low pressure valve.
- Connect a second charge hose from the manifold gauge to the vacuum pump.
- Open the low pressure side of the gauge and keep the high pressure side closed.
- Start the vacuum pump.
- Run the vacuum for at least 15 minutes, or until the micron gauge reads 500 microns (67 Pa).
- Close the low pressure side of the gauge and stop the pump.
- Wait 5 minutes and check that system pressure has not changed. If it changed, find and fix the leak before continuing.
- If pressure held, remove the cap from the high pressure (packed) valve.
- Insert the hex wrench into the high pressure valve and turn it 1/4 turn counterclockwise. Listen for gas to escape, then close the valve after 5 seconds.
- Watch the gauge for one minute. Pressure should stay steady and read slightly above atmospheric.
- Remove the charge hose from the service port.
- Open the outdoor unit stop valves fully with the hex wrench (high and low pressure valves) so refrigerant can flow.
- Tighten all three valve caps (service port, high pressure, low pressure) by hand, then with a torque wrench if needed.
- When opening valve stems, turn the hex wrench only until it hits the stopper. Do not force it further.
Applies to: D5FUHA crossover air handler, sizes 18K to 60K
Source: Carrier D5FUHA Installation Instructions, p. 61. Written in our own words; check the manual for your exact model.
Brazing and pressure test
Air handler · D5FUAA
Nitrogen purge and pressure test after brazing the line set.
- Set up nitrogen and connect it to the outdoor unit to flow nitrogen while brazing.
- Braze the tubing and fittings for a proper seal.
- Pressurize the system with nitrogen, pressure test to a maximum of 500 psig for at least 60 minutes.
- Insulate the suction line completely, including the outdoor unit valves.
Applies to: D5FUAA line set brazing
Source: D5FUAA installation instructions, p. 40. Written in our own words; check the manual for your exact model.
Built-in 24 V interface with heat pump thermostat
Air handler · D5FUAA
The indoor unit has a built-in 24 V interface (CN8 and CN9 shown in Figure 13) so a field-supplied 3rd party heat pump thermostat can control the unit. A heat pump thermostat is required. Electric heat needs a 2 heat/1 cool thermostat.
- Install a heat pump thermostat.
- For electric heat applications, use a 2 heat/1 cool thermostat.
- Connect to the 24 V interface terminals shown in Figure 13.
Applies to: D5FUAA indoor unit with 24 V thermostat
Source: D5FUAA Crossover Air Handler product data, p. 13. Written in our own words; check the manual for your exact model.
Built-in 24V interface
Air handler · D5FS(L)AAH
Standard 24V interface allows control of the air handler from a third-party thermostat supplied in the field.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Charging and recharge checks
Air handler · D5FULA
Use tools suitable for flammable refrigerants and keep hoses short. Keep cylinders upright and earth the system before charging. Do not overfill. Pressure test with oxygen-free nitrogen before recharging, and leak test after charging and again before leaving the site.
- Label the system when charging is done.
- Leak test after charging and before commissioning.
- Leak test again before leaving the site.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 7. Written in our own words; check the manual for your exact model.
Check coil airflow against limits
Air handler · D5FULA
Coil airflow must stay within the model's min and max CFM for the outdoor unit tonnage. The minimum airflow for the refrigerant charge (QHmin) must also be met. Furnace blower feedback must be able to shut the gas valve within one minute if the blower fails.
- Identify the model and the outdoor unit tonnage.
- Check the airflow is between the minimum and maximum CFM for that model and tonnage.
- Calculate Mc and look up QHmin in the charge vs minimum airflow table; confirm the airflow meets it.
- Confirm the furnace has blower failure detection and airflow verification that shuts the gas valve within one minute.
Applies to: D5FULA coil on furnace
Source: D5FULA installation instructions, p. 3, 11. Written in our own words; check the manual for your exact model.
Clearance from combustibles for auxiliary heater
Air handler · D5FUHA
Units with an auxiliary electric heater must not be installed within 3 ft (1 m) of combustible materials.
- Keep at least 3 ft (1 m) between the unit and any combustible material.
Applies to: Units with auxiliary electric heater
Source: Carrier D5FUHA service manual, p. 2. Written in our own words; check the manual for your exact model.
Clearance from combustibles for auxiliary heater units
Air handler · D5FUAA
For units with an auxiliary electric heater, do not install the unit within 3 ft (1 m) of any combustible materials.
- Check the unit is at least 3 ft (1 m) from combustible materials when an auxiliary electric heater is fitted.
Applies to: D5FUAA with auxiliary electric heater
Source: Carrier D5FUAA crossover air handler product data, p. 3. Written in our own words; check the manual for your exact model.
CN23 and CN33 terminal wiring
Air handler · D5FUAA
CN23 and CN33 are dry contact terminals that accept wire only on the outer terminals.
- Connect wires to the left and right terminals of CN23 and CN33.
- Do not connect a wire to the middle terminal.
Applies to: 24V board
Source: Carrier D5FUAA product data, p. 21. Written in our own words; check the manual for your exact model.
Coil interface and wired controller are required for AHRI ratings
Air handler · DLFULA
The coil interface and wired controller KSACN1101AAA must be installed for the unit to perform per AHRI ratings.
- Install the coil interface and KSACN1101AAA wired controller with the unit.
Applies to: DLFULA evaporator coil
Source: DLFULA product data, p. 1. Written in our own words; check the manual for your exact model.
Communication wire selection and retrofit rules
Air handler · D5FUAA
RS485 communication between indoor and outdoor units needs the correct wire.
- Use 16 AWG stranded shielded wire for RS485 between indoor and outdoor units, as recommended.
- Use 16 to 18 AWG wire, with a run no longer than the system maximum piping length.
- On retrofits, 18 AWG thermostat wire may be reused only if it is not coiled, has no splices on the used wires, all unused wires are grounded to the outdoor unit, it is in good condition, and there are no nearby EMI sources.
- If communication faults occur on reused 18 AWG wire, replace it with 16 AWG stranded shielded wire.
Applies to: D5FUAA indoor and outdoor unit communication
Source: D5FUAA Crossover Air Handler product data, p. 11. Written in our own words; check the manual for your exact model.
Condensate drain height and trap
Air handler · D5FULA
Condensate must drain freely. Where a water overflow could damage the space, a secondary drain or external pan is needed, and a float switch protects against high water.
- Set the condensate trap height per Fig. 16 (3 in / 76 mm).
- If the unit is in or above a living space, install a field-supplied external pan under the whole unit with a secondary condensate line and trap.
- Route the secondary drain to a visible location so overflow is noticed.
- If a waste line is used, install an open trap ahead of it to stop sewer gas entering.
- Fit a float switch to shut the unit off if the secondary pan fills.
- Tell the owner that water flowing from the secondary drain means the unit needs service.
Applies to: D5FULA
Source: D5FULA installation instructions, p. 24. Written in our own words; check the manual for your exact model.
Confirm before test run
Air handler · D5FULA
Check the installation is complete and recorded before powering up for the test run. Failure to run the test can cause unit damage, property damage or personal injury.
- Confirm indoor and outdoor units are installed correctly.
- Confirm piping and wiring are connected correctly.
- Clear any obstacles near the unit inlet and outlet.
- Confirm the refrigeration system does not leak.
- Confirm the drain system is clear and drains to a safe location.
- Confirm piping and duct insulation is installed.
- Confirm grounding wires are connected.
- Record the piping length and additional refrigerant charge.
- Confirm supply voltage matches the air conditioner rating.
Applies to: D5FULA before test run
Source: D5FULA Installation Instructions, p. 33. Written in our own words; check the manual for your exact model.
Confirm the unit has the correct electrical supply before wiring
Air handler · D5FUHA
Units can run on 115V or 208/230V. The board detects the input voltage automatically when power is applied.
- For 208V or 230V, connect L1 and L2.
- For 115V, connect L1 and L2, with L2 used as N.
- Check the outdoor unit MCA and MOCP before sizing the wire and disconnect.
Applies to: D5FUHA power wiring
Source: D5FUHA Product Data, p. 9, p. 10. Written in our own words; check the manual for your exact model.
Control options and wiring
Air handler · D5FUHAQ
Choose the control method the job uses. Only one control path should be active with a third party thermostat.
- Wired controller (optional, KSACN1401AAA) is non-polarity and has an infrared receiver. It can be used together with the wireless remote.
- Wireless remote is included and gives the same functions as the wired controller.
- Third party heat pump thermostat (not included) connects to the built-in 24V interface on the air handler.
- Do not use the wired controller or wireless remote when a third party thermostat is installed.
Applies to: D5FUHAQ air handler
Source: D5FUHAQ Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
DIP switch and connector notes for wiring
Air handler · D5FS(L)AAH
Remove the short connector on JR1 when using the ON-OFF function. Remove the short connector on J7 when using the water level switch function. Other DIP switches default to OFF. Refer to the Installation Manual for DIP switch functions. On CN23/CN33, connect wires to the left and right terminals, not the middle ones.
- Remove the short connector on JR1 only if the ON-OFF function is used.
- Remove the short connector on J7 only if the water level switch is used.
- Connect CN23/CN33 wires to the outer terminals only.
Applies to: D5FS(L)AAH wiring diagrams 18K to 60K
Source: D5FS(L)AAH Owner's Manual, p. 19. Written in our own words; check the manual for your exact model.
Drain connections
Air handler · DLFULA
Install drains to meet local sanitation codes. The built-in secondary drain allows mounting in upflow, downflow, left or right orientation.
- Install the drain to local sanitation codes.
- Select the orientation to suit the installation, using the built-in secondary drain.
Applies to: DLFULA evaporator coil
Source: DLFULA product data, p. 2, p. 7. Written in our own words; check the manual for your exact model.
Duct acoustical lining requirement
Air handler · D5FUHA
Metal duct systems without a 90 degree elbow and 10 ft (3 m) of main duct before the first branch may need internal acoustical lining.
- Check the duct layout for a 90 degree elbow and 10 ft of main duct before the first branch.
- Add internal acoustical lining if the layout does not meet this.
- Use fibrous ductwork only if built per the SMACNA glass duct standard and NFPA / UL 181 Class 1.
Applies to: Supply and return duct design
Source: Carrier D5FUHA installation instructions, p. 16. Written in our own words; check the manual for your exact model.
Electric heater needs its own power supply
Air handler · D5FUAA
The unit has no single-point connection for an electric heater, air purifier or other peripherals. Run a separate supply for each.
Applies to: D5FUAA with electric heater kit or other peripherals
Source: Carrier D5FUAA crossover air handler product data, p. 6. Written in our own words; check the manual for your exact model.
Electrical wiring and voltage checks
Air handler · D5FSAA, D5FLAA
Confirm the wiring between the outdoor and indoor units and check voltage at each point listed on the checklist.
- Record the wire size and type.
- Confirm there are no breaks, splices, wire nuts or butt connectors between the outdoor and indoor units.
- Confirm the wiring from the outdoor unit port goes to the correct indoor unit.
- Check voltage at the outdoor unit disconnect: 1(L1) to GND, 1(L1) to 2(L2), and 2(L2) to GND.
- Check voltage at the outdoor terminal block with the same pairs.
- Check voltage at the outdoor unit and at the indoor unit, including 2(L2) to 3(S), and record the results.
Applies to: D5FSAA / D5FLAA single zone ductless system
Source: Carrier D5FSAA and D5FLAA installation manual, p. 49. Written in our own words; check the manual for your exact model.
Enhanced versus standard defrost timing
Air handler · D5FUHA
With SW1-4 ON, defrost starts after 40 minutes of cumulative compressor run time in heat mode. With SW1-4 OFF (standard), it starts after 90 minutes.
- Set SW1-4 ON for enhanced defrost, or leave it OFF for standard defrost.
- Verify the setting before commissioning the system.
Applies to: D5FUHA outdoor unit
Source: D5FUHA Installation Instructions, p. 36. Written in our own words; check the manual for your exact model.
Evacuation acceptance limit
Air handler · D5FUHA
After reaching the specified vacuum, isolate the pump. The pressure must not rise above 1500 microns within 10 minutes. The target vacuum is the lesser of 500 microns or the value required by national and local codes.
- Pull the system to the specified vacuum, no higher than 500 microns or the code value if lower.
- Isolate the system from the vacuum pump.
- Watch the gauge for 10 minutes; the pressure must stay at or below 1500 microns.
Applies to: Field refrigerant piping evacuation
Source: Carrier D5FUHA service manual, p. 5. Written in our own words; check the manual for your exact model.
Evacuation of the refrigerant circuit
Air handler · D5FSAA, D5FLAA
Use one of the two evacuation methods in the manual and record which one was used.
- Use the Triple Evacuation Method as outlined in the installation manual, or the Deep Vacuum Method.
- For deep vacuum, hold 500 microns for 1 hour.
- Record YES or NO for each method on the checklist.
Applies to: D5FSAA / D5FLAA ductless air handler system
Source: Carrier D5FSAA and D5FLAA installation manual, p. 50. Written in our own words; check the manual for your exact model.
Evacuation requirements
Air handler · D5FUHA
Evacuate with the triple evacuation or the deep vacuum method as written in the installation manual.
- Use either the triple evacuation method or the deep vacuum method.
- Pull the system down to 500 microns.
- Hold 500 microns for 1 hour.
- Record the method used on the start-up checklist.
Applies to: D5FUHA piping
Source: D5FUHA Installation Instructions, p. 69. Written in our own words; check the manual for your exact model.
Field pipe pressure test
Air handler · D5FUHA
After field piping, pressure test with inert gas, then vacuum test before charging. The test pressure must hold for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure. Low side is tested to low side design pressure; high side to high side design pressure. If the sides cannot be isolated, test the whole system to the low side design pressure.
- Pressure test field piping with inert gas (never air or oxygen).
- Hold the test pressure for at least 1 hour.
- Confirm no pressure drop on a gauge with resolution of 5% of test pressure or better.
- Use low side design pressure for the low side and high side design pressure for the high side, or the low side pressure for the whole system if sides cannot be isolated.
Applies to: Split system field refrigerant piping
Source: Carrier D5FUHA service manual, p. 5. Written in our own words; check the manual for your exact model.
Field wiring rules
Air handler · D5FULA
Use only the specified wire. A damaged wire must be replaced by the manufacturer, its service agent or similarly qualified persons. Follow the Electrical Connection Diagram on the indoor and outdoor unit panels.
- Ground the product at installation.
- Connect cables tightly and clamp them so external forces cannot reach the terminals.
- Route all wiring so the control board cover closes properly.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 2. Written in our own words; check the manual for your exact model.
Furnace blower failure detection requirement
Air handler · D5FULA
When this coil is used with any furnace, the furnace must detect blower failure and verify airflow. Blower feedback must act within one minute to shut off the gas valve.
- Confirm the furnace has blower failure detection and airflow verification.
- Confirm blower feedback shuts off the gas valve within one minute of a blower failure.
Applies to: D5FULA crossover evaporator coil with any furnace
Source: D5FULA installation instructions, p. 3. Written in our own words; check the manual for your exact model.
Horizontal installation needs a secondary drain pan
Air handler · D5FUAA
Multi-poise unit can be set vertical up, horizontal left or right, or upflow/downflow. Horizontal installs need a secondary drain pan (not supplied) with at least 5 in (127 mm) between the bottom of the air handler and the pan for drainage. Vertical up and horizontal left do not require changing the evaporator direction.
- Confirm the install orientation from the multi-poise drawings.
- For horizontal installs, fit a secondary drain pan not supplied with the unit.
- Keep at least 5 in (127 mm) between the air handler bottom and the secondary pan.
Applies to: D5FUAA air handler
Source: Carrier D5FUAA crossover air handler product data, p. 4. Written in our own words; check the manual for your exact model.
Indoor refrigerant joint leak test
Air handler · D5FUHA
Field-made joints indoors must be leak tested with a method sensitive to 5 g/year of refrigerant or better, at a pressure of at least 0.25 times the maximum allowable pressure. No leak may be detected. Detachable joints are not allowed on the indoor side; brazed or welded joints are acceptable.
- Use a leak detector rated 5 g/year or better.
- Test at a pressure of at least 0.25 times maximum allowable pressure.
- Confirm no leak is detected.
- Do not use detachable joints on the indoor side.
Applies to: Indoor refrigerant joints
Source: Carrier D5FUHA service manual, p. 4 and p. 5. Written in our own words; check the manual for your exact model.
Indoor unit power and signal wiring steps
Air handler · D5FUAA
Basic wiring order for the base indoor unit. Auxiliary electric heat wiring is covered in the installation manual.
- Turn off the main disconnect and lock it out before opening the unit.
- Strip the signal cable to about 1/2 in (12 mm) and strip the wire ends; crimp fork terminals on each wire.
- Open the front panel and remove the electric control box cover.
- Pass the power and signal cables through the wire outlet.
- Connect each fork terminal to the matching terminal, matching wire colors and labels.
- Tighten each screw and check against the wiring diagram on the control box cover.
- Clamp the cable so it is not loose and carries no strain on the terminals.
- Reattach the electric box cover and make sure it closes fully.
Applies to: D5FUAA indoor unit
Source: D5FUAA Crossover Air Handler product data, p. 10. Written in our own words; check the manual for your exact model.
Installation location and drainage
Air handler · D5FULA
Install on a firm surface that supports the unit weight. Install drain piping as the manual describes, because poor drainage can cause water damage. Do not install where combustible gas may leak.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 3, 8. Written in our own words; check the manual for your exact model.
Isolate interconnecting tubing from the structure
Air handler · DLFULA
Isolate the interconnecting tubing from the building structure so vibration and noise do not transmit into the building.
- Isolate the tubing from framing and structure when routing the line set.
Applies to: DLFULA evaporator coil with outdoor unit
Source: DLFULA product data, p. 7. Written in our own words; check the manual for your exact model.
Keep high voltage and communication wiring separate
Air handler · D5FSAA
High voltage and communication wire must not run through the same knockout. Keep them in separate holes, and do not route either against refrigerant tubing or moving parts.
- Use separate knockouts for line voltage and communication wiring.
- Route the connecting cable with conduit through the conduit panel hole.
- Ground the shield only at the outdoor unit when using shielded cable.
Applies to: Field wiring between indoor and outdoor units
Source: D5FSAA Product Data, p. 8, 11. Written in our own words; check the manual for your exact model.
Leak check and evacuation for start-up
Air handler · D5FUAA
Pressure test the piping with dry nitrogen. Never use air or oxygen-containing gases for leak testing. Evacuation can use the Triple Evacuation Method or the Deep Vacuum Method.
- Hold the system at 500 psig (max. 550 psi) for a minimum of 30 minutes using dry nitrogen.
- Evacuate by the Triple Evacuation Method or the Deep Vacuum Method as outlined in the manual.
- Confirm the system holds 500 microns for 1 hour.
- Confirm the line set diameter matches the evaporator connections.
- For conventional fan coils, confirm the line set matches the outdoor unit size.
- Measure the liquid line length, calculate the additional charge, and record the final charge amount.
Applies to: D5FUAA refrigerant piping start-up
Source: Carrier D5FUAA installation instructions, p. 63. Written in our own words; check the manual for your exact model.
Leak check with dry nitrogen
Air handler · D5FUHA
Pressure test the piping before evacuation. Use dry nitrogen only. Never use air or oxygen-containing gases for leak testing.
- Pressurize the system with dry nitrogen to 500 psig.
- Do not exceed 550 psi.
- Hold the pressure for at least 30 minutes.
- Record YES or NO on the start-up checklist.
Applies to: D5FUHA piping
Source: D5FUHA Installation Instructions, p. 69. Written in our own words; check the manual for your exact model.
Line set match and additional charge
Air handler · D5FUHA
Check the line set size against the evaporator connections and, for conventional fan coils, against the outdoor unit size. Calculate the extra charge from the liquid line length.
- Confirm the line set diameter matches the evaporator connections.
- For conventional fan coils, confirm the line set matches the outdoor unit size.
- Measure the liquid line length and calculate the additional charge.
- Record the final charge amount on the checklist.
Applies to: D5FUHA single zone piping
Source: D5FUHA Installation Instructions, p. 69. Written in our own words; check the manual for your exact model.
Line set sizing and charge
Air handler · D5FSAA, D5FLAA
The line set must match the evaporator connections, and the added charge must be calculated and recorded.
- Confirm the line set diameter matches the evaporator connections.
- For conventional fan coils, confirm the line set matches the outdoor unit size.
- Measure the liquid pipe length and calculate the additional charge.
- Record the liquid size, length and charge on the checklist.
- Record the final charge amount.
Applies to: D5FSAA / D5FLAA single zone ductless system
Source: Carrier D5FSAA and D5FLAA installation manual, p. 50. Written in our own words; check the manual for your exact model.
Line voltage terminal block connection
Air handler · D5FUAA
Terminal block wiring depends on the supply voltage.
- For 208V or 230V supply, connect L1 and L2.
- For 115V supply, connect L1 and L2, where L2 is used as neutral (N).
Applies to: Indoor unit power supply
Source: Carrier D5FUAA product data, p. 21. Written in our own words; check the manual for your exact model.
Lock in service mode changes
Air handler · D5FUHA
After all SERVICE mode changes are made, the outdoor unit must be powered down to lock the new settings in.
- After the last service change, turn off power to the outdoor unit.
- Keep the outdoor unit off for 3 minutes.
- Restore power to the outdoor unit.
Applies to: D5FUHA outdoor unit and remote controller
Source: D5FUHA installation instruction manual, p. 49. Written in our own words; check the manual for your exact model.
Nitrogen flow while brazing the line set
Air handler · DLFULA
Nitrogen must flow through the system while the line set is brazed.
- Flow nitrogen through the system during all line set brazing.
Applies to: DLFULA evaporator coil
Source: DLFULA product data, p. 7. Written in our own words; check the manual for your exact model.
No airflow setting needed
Air handler · D5FSAA
The indoor unit uses a constant air volume ECM motor that adjusts to static pressure up to 0.80 in.wc. ESP. The supplied remotes do not need to set airflow.
- Leave airflow on automatic and do not set CFM from the remote.
- Confirm the static pressure is within 0.80 in.wc. ESP.
Applies to: All sizes
Source: D5FSAA Product Data, p. 12. Written in our own words; check the manual for your exact model.
Paired outdoor unit liquid line
Air handler · DLFULA
When paired with the 38MURA outdoor units, the liquid line is a true liquid line and does not need both lines insulated.
- With 38MURA outdoor units, insulate only the line that needs it.
Applies to: DLFULA evaporator coil paired with 38MURA outdoor units
Source: DLFULA product data, p. 7. Written in our own words; check the manual for your exact model.
Power supply and disconnect requirements
Air handler · D5FUHA
Supply voltage must stay within 90 to 110 percent of rated voltage. Fixed wiring needs a disconnect with at least 3 mm contact separation on all poles. A surge suppressor at the outdoor disconnect is recommended.
- Check the supply voltage is within 90 to 110 percent of rated.
- Install a disconnect or breaker that opens all poles with at least 3 mm (1/8 in) contact separation.
- Install a surge suppressor at the outdoor disconnect if possible.
- Use an individual branch circuit. Do not share it with other equipment.
Applies to: D5FUHA outdoor and indoor units
Source: D5FUHA Installation Instructions, p. 33. Written in our own words; check the manual for your exact model.
Power supply and residual current protection
Air handler · D5FUHA
Use a dedicated circuit and a properly rated breaker. Fixed wiring needs an all-pole disconnect with at least 3 mm contact clearance in all poles. Where leakage current may exceed 10 mA, the RCD must have a rated residual operating current not above 30 mA. Do not share the outlet and do not modify or extend the power cable.
- Install a dedicated circuit and breaker that are not under-rated or defective.
- Fit an all-pole disconnect with at least 3 mm clearance in every pole.
- Where leakage may exceed 10 mA, fit an RCD rated at 30 mA or less.
- Confirm the unit is properly grounded and the power cable is secure and undamaged.
Applies to: Electrical connection of indoor unit
Source: Carrier D5FUHA service manual, p. 2 and p. 4. Written in our own words; check the manual for your exact model.
Preparation: air outlet, clearances and return air
Air handler · D5FSAA / D5FLAA
Set-up checks before the unit is connected and closed up.
- Remove all accessories and packing from the air outlet before installation.
- Keep a minimum 1 in (25.4 mm) clearance on all sides of the unit.
- For vertical installs, connect the lower end of the air outlet to the L-shaped metal duct and fasten with screws.
- If return air is ducted, run the duct flush with the floor and set the unit over the opening; all return air must pass through the coil.
- Seal around wires, refrigerant pipes and condensate pipes where they enter the cabinet, and seal any gaps around drain lines with duct tape or flexible sealant so warm air cannot enter.
- Keep the return air intake away from heat sources and warm or cool air that could skew the sensed return air temperature.
- Outlet side pipe length: 1.5 m (5.9 ft) as shown in the page 16 figure.
Applies to: Indoor air handler
Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 16. Written in our own words; check the manual for your exact model.
Pressure test and evacuation of field piping
Air handler · D5FSAA / D5FLAA
Field piping must be pressure tested with inert gas and then vacuum tested before charging. Evacuation limits apply as listed.
- Pressure test the low side at its design pressure and the high side at its design pressure. If the sides cannot be isolated, test the whole system at the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
- Evacuate the system to 500 microns or the lower level required by local code.
- Isolate the pump from the system. Pressure must not rise above 1500 microns within 10 minutes.
Applies to: Split system field refrigerant piping
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 7. Written in our own words; check the manual for your exact model.
Pressure, vacuum and leak test limits for field piping
Air handler · D5FUAAH
Limits for testing field refrigerant piping on split systems.
- Pressure test field piping with inert gas. Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of the test pressure.
- After evacuation, isolate the pump. Pressure must not rise above 1500 microns within 10 minutes. Vacuum must reach 500 microns or lower, or the level required by local code.
- Test field-made indoor joints at at least 125% of the maximum allowable pressure. Sensitivity must be 1/8 oz (5 g) per year or better. No leak is allowed.
Applies to: Field piping on D5FUAAH split systems
Source: D5FUAAH Owner's Manual, p. 4. Written in our own words; check the manual for your exact model.
Read the full manual before installation
Air handler · D5FULA
Read the whole instruction manual before starting the installation.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 1. Written in our own words; check the manual for your exact model.
Refrigerant joints and piping
Air handler · D5FULA
Keep refrigerant pipe runs to a minimum and protect them from physical damage. Use brazed or welded joints on the indoor side, not detachable joints. Mechanical connections must be reachable for service. Seal open pipe ends during storage.
- Seal pipe openings by pinching or taping them to keep out oil, water and dirt.
- Make sure all field joints can be inspected before they are covered.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 5. Written in our own words; check the manual for your exact model.
Refrigerant leak sensor orientation
Air handler · D5FUHA
The unit includes a refrigerant leak mitigation system (R-454B). The leak sensor does not need to be re-oriented for different install positions.
- Do not reorient the refrigerant leak sensor for the chosen install position.
Applies to: D5FUHA
Source: D5FUHA product data, p. 2, 8. Written in our own words; check the manual for your exact model.
Refrigerant leak sensor wiring and secondary input
Air handler · D5FULA
The leak sensor connects to the primary leak mitigation input at CN8 on the interface board. A secondary input at CN5 is available but must be enabled with DIP switch SW5.
- Connect the refrigerant sensor wire to CN8 (primary, active by default).
- To use the secondary input at CN5, turn on DIP switch SW5.
- Follow the wiring diagram and the leak mitigation kit label for operating details.
Applies to: D5FULA with R454B leak mitigation kit
Source: Carrier D5FULA installation instructions, p. 22. Written in our own words; check the manual for your exact model.
Refrigerant line routing and burial
Air handler · DLFULA
Outdoor units ship with a full R410A charge. Charge, line sizing and capacities assume runs of 25 ft (7.6 m). Lines must not be buried in the ground. If burial is unavoidable, do not bury more than 36 in (914 mm), and give the service valves at least 6 in (152 mm) of vertical rise to prevent refrigerant migration.
- Keep line runs near 25 ft (7.6 m) or adjust charge and line sizing to suit.
- Do not bury lines in the ground.
- If burial cannot be avoided, keep burial depth to 36 in (914 mm) maximum.
- Provide at least 6 in (152 mm) vertical rise to the service valves.
Applies to: DLFULA evaporator coil with outdoor unit
Source: DLFULA product data, p. 7. Written in our own words; check the manual for your exact model.
Refrigerant pipe burial limits
Air handler · D5FUAA
Do not bury more than 36 in (914 mm) of refrigerant pipe. If any pipe is buried, there must be a 6 in (152 mm) vertical rise to the outdoor unit valve connections. Too much buried pipe lets refrigerant migrate during shutdown and can slug the compressor at start-up.
- Keep buried refrigerant pipe to 36 in (914 mm) or less.
- If any pipe is buried, provide a 6 in (152 mm) vertical rise to the outdoor valve connections.
Applies to: D5FUAA system piping
Source: Carrier D5FUAA crossover air handler product data, p. 2. Written in our own words; check the manual for your exact model.
Refrigerant piping leak check
Air handler · D5FSAA, D5FLAA
The system is pressure-tested before evacuation. Use dry nitrogen only.
- Pressurise the system to 500 psig, with a maximum of 550 psi.
- Hold the pressure for at least 30 minutes using dry nitrogen.
- Never use air or oxygen-containing gases for this test.
- Record YES or NO on the start-up checklist.
Applies to: D5FSAA / D5FLAA ductless air handler system
Source: Carrier D5FSAA and D5FLAA installation manual, p. 50. Written in our own words; check the manual for your exact model.
Remote ON/OFF input (CN2, JR1)
Air handler · D5FUAA
Lets an external switch turn the unit on and off. The unit responds within 2 seconds of a change.
- Remove jumper JR1 to enable the ON/OFF function.
- Open the switch to turn the unit off. Close it to turn the unit on.
- With the switch open, the unit ignores the remote or wired controller and shows CP.
Applies to: D5FUAA indoor unit
Source: D5FUAA installation instructions, p. 25. Written in our own words; check the manual for your exact model.
Remove J1 short connector for water level switch
Air handler · D5FUAA
The J1 short connector must be removed before the water level switch can be used.
- Remove the short connector on J1 when using the water level switch function.
Applies to: Indoor main board
Source: Carrier D5FUAA product data, p. 21. Written in our own words; check the manual for your exact model.
Remove JR1 short connector for ON/OFF function
Air handler · D5FUAA
The JR1 short connector must be removed before the ON/OFF function can be used.
- Remove the short connector on JR1 when using the ON/OFF function.
Applies to: Indoor main board
Source: Carrier D5FUAA product data, p. 21. Written in our own words; check the manual for your exact model.
Remove packing and accessories from air outlet
Air handler · D5FUAA
Remove all accessories and packing material from the air outlet before installing.
- Remove all packing and accessories from the air outlet before mounting.
Applies to: All D5FUAA sizes
Source: D5FUAA installation instructions, p. 16. Written in our own words; check the manual for your exact model.
Room size and duct outlet height for R454B
Air handler · D5FUHA
R454B is a mildly flammable (A2L) refrigerant. The room area served and the total refrigerant charge are limited. The bottom of the duct air outlet in the room must be at the height stated on the page, 7.3 ft (2.2 m) above the floor. Table 2 (minimum room area) is not legible on these pages.
- Check the room area served against Table 2 and the charge limit.
- Set the duct outlet height to at least 7.3 ft (2.2 m) above the floor.
- Keep the room free of continuously operating open flames or other ignition sources if the room is below the minimum area.
Applies to: Units with R454B refrigerant
Source: D5FUHA Installation Instructions, p. 5. Written in our own words; check the manual for your exact model.
Room size and outlet height for flammable refrigerant systems
Air handler · D5FSAAH / D5FLAAH
The air duct outlet serving the room must sit more than 7.3 ft (2.2 m) above the floor. R454B is classed as mildly flammable, so the room area served and the total refrigerant charge are limited by the room size. Compare the actual charge against the allowable charge for the room.
- Confirm the air outlet height is above 7.3 ft (2.2 m) from the floor.
- Check the total refrigerant charge is at or below the maximum allowed for the room area served.
Applies to: R454B systems, 18K to 60K
Source: Carrier D5FS(L)AAH owner's manual, p. 4. Written in our own words; check the manual for your exact model.
Room ventilation and installation area
Air handler · D5FULA
Install in a well ventilated room that matches the room area stated for operation. Where mechanical ventilation is needed, keep the vents clear. In rooms smaller than the minimum area for the refrigerant charge, no open flames or hot surfaces may run.
- Keep ventilation openings free of obstruction.
- Check the room area against the minimum area table for the refrigerant charge.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 5, 8. Written in our own words; check the manual for your exact model.
Scenario 1: 24 V thermostat with RS485 to outdoor unit
Air handler · D5FUAA
Scenario 1 lets a 24 V thermostat work with RS485 communication between indoor and outdoor units. Figure 11 in the manual shows the wiring.
- Do not use the B and W terminals together.
- Use W only for a conventional thermostat heat demand.
- Treat DS as a reserve terminal.
- Do not use any outdoor 24 V terminals in scenario 1.
Applies to: D5FUAA with 24 V thermostat (scenario 1)
Source: D5FUAA Crossover Air Handler product data, p. 12. Written in our own words; check the manual for your exact model.
Scenario 2 (default): wired controller wiring
Air handler · D5FUAA
Scenario 2 is the default and lets the KSACN1401 or KSACN1701 wired controller work with RS485 between indoor and outdoor units.
- Do not use any 24 V terminals on the indoor or outdoor unit.
- Connect the Ha and Hb terminals on the wired controller to the Ha and Hb terminals on the indoor built-in 24 V interface (CN7) using 16 AWG shielded stranded wire.
- Follow the indoor and outdoor communication diagram (Figure 12).
Applies to: D5FUAA with wired controller (scenario 2)
Source: D5FUAA Crossover Air Handler product data, p. 12. Written in our own words; check the manual for your exact model.
Single zone performance check
Air handler · D5FSAA, D5FLAA
Run the system and record operating temperatures for the start-up record.
- On a 1:1 single zone system, adjust the setpoint to create a cooling or heating call for the test.
- Let the system run for at least 10 minutes.
- Use the wireless remote Point Check function to read the sensors.
- Record the set-point, mode, T1 ambient space, T2 indoor coil, T3 outdoor coil, T4 outdoor ambient, Tb suction line at PMV, Tp discharge, Th IPM board and LA/Lr PMV temperature.
Applies to: D5FSAA / D5FLAA single zone ductless system
Source: Carrier D5FSAA and D5FLAA installation manual, p. 50. Written in our own words; check the manual for your exact model.
Start-up error code check
Air handler · D5FSAA, D5FLAA
Check for any error codes during start-up and record them.
- Check whether any error codes were present at start-up.
- Record the indoor unit error code and the outdoor unit error code.
- Note the wall controller and 24V interface status in the comments.
Applies to: D5FSAA / D5FLAA single zone ductless system
Source: Carrier D5FSAA and D5FLAA installation manual, p. 50. Written in our own words; check the manual for your exact model.
Static pressure limit
Air handler · D5FUHA
Do not exceed 0.80 in.wc. (200 Pa) total external static pressure. Airflow falls sharply above this point.
- Measure total external static pressure during commissioning.
- Confirm it is 0.80 in.wc. (200 Pa) or less.
Applies to: All sizes
Source: Carrier D5FUHA installation instructions, p. 10. Written in our own words; check the manual for your exact model.
Use shielded cable in EMF areas
Air handler · D5FSAA
If installed in a high EMF area and communication problems occur, a 14/2 stranded shielded cable can replace the L(2) and S wires between the indoor and outdoor units.
- Use 14/2 stranded shielded cable to replace L(2) and S.
- Land the shield on ground at the outdoor unit only.
Applies to: Installations with communication interference
Source: D5FSAA Product Data, p. 11. Written in our own words; check the manual for your exact model.
Voltage check points
Air handler · D5FUHA
The checklist calls for voltage readings at the outdoor disconnect, the outdoor terminal block, and at both units. The pages give no acceptable values.
- Measure 1(L1) to GND, 2(L2) to GND, and 1(L1) to 2(L2) at the outdoor unit disconnect.
- Repeat at the outdoor unit terminal block.
- Measure 1(L1) to GND, 2(L2) to GND, 1(L1) to 2(L2), and 2(L2) to 3(S) at the outdoor unit and the indoor unit.
- Record the readings and any notes on the checklist.
Applies to: D5FUHA single zone wiring
Source: D5FUHA Installation Instructions, p. 68. Written in our own words; check the manual for your exact model.
Voltage selection
Air handler · D5FUHA
The unit can use 115V or 208/230V automatically. The K-suffix models are rated 208/230-1-60 and may be configured for 115 V AC.
- Confirm the supply voltage at the indoor unit before power-up.
- If the site is 115 V, check the configuration per the installation instructions for the K-suffix model.
Applies to: D5FUHA indoor units
Source: D5FUHA product data, p. 2-3. Written in our own words; check the manual for your exact model.
Wired controller and 24V thermostat cannot run together
Air handler · D5FUHA
The wired remote controller KSACN1401AAA (sold separately) and a 24V third-party heat pump thermostat cannot be connected at the same time. A 2 heat/1 cool thermostat is needed for electric heat applications.
- Connect either the wired controller or the 24V thermostat, not both.
- For electric heat, use a 2 heat/1 cool thermostat.
Applies to: D5FUHA control wiring
Source: D5FUHA Product Data, p. 11. Written in our own words; check the manual for your exact model.
24 V communication between units is not allowed
Heat pump · D5CURA
Compliance issues mean 24 V communication must not be used as a standard method. It is only for emergency operation, service procedures and troubleshooting.
Applies to: Indoor and outdoor unit communication
Source: D5CURA installation manual, p. 24. Written in our own words; check the manual for your exact model.
Adding charge on long line sets
Heat pump · D5CURA
The outdoor unit is shipped with a full R-454B charge that covers about 25 ft of line. Longer runs need extra refrigerant up to the allowed length.
- Check the total line length against the 24.6 ft (7.5 m) standard piping length.
- For runs over the standard length, add 0.7 oz/ft (65 g/m) of extra line.
- Do not exceed the maximum total piping length and drop height for the size (see the line-length table).
Applies to: D5CURA all sizes
Source: D5CURA service manual, p. 20. Written in our own words; check the manual for your exact model.
Air handler (AHU) limits and added charge
Heat pump · D5CMHA
A maximum of two AHUs can be added to an MZ system. When two AHUs are connected to any MZ outdoor unit, no other indoor units can be added. If a 30K or 36K AHU is connected to any outdoor unit, add 500 g (17.6 oz) of refrigerant. 30K and 36K indoor units are not compatible with phased-out models.
- Limit the system to two AHUs maximum.
- With two AHUs installed, do not add other indoor units.
- For any 30K or 36K AHU, add 500 g (17.6 oz) of refrigerant charge.
Applies to: D5CMHA multi-zone systems with AHUs
Source: D5CMHA Product Data, p. 124. Written in our own words; check the manual for your exact model.
Buried refrigerant lines
Heat pump · D5CMHA
Refrigerant lines should not be buried in the ground. If burial cannot be avoided, do not bury more than 36 in (914 mm), and provide at least a 6 in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
- Avoid burying the lines where possible.
- If buried, keep the burial depth to 36 in (914 mm) maximum.
- Provide at least 6 in (152 mm) of vertical rise to the service valves.
Applies to: D5CMHA refrigerant piping
Source: D5CMHA Product Data, p. 124. Written in our own words; check the manual for your exact model.
Clearance from combustibles for units with auxiliary electric heater
Heat pump · D5FSFA
Units with an auxiliary electric heater need clearance from combustible materials.
- Do not install the unit within 3 feet (1 meter) of any combustible material.
Applies to: D5FSFAH units with auxiliary electric heater
Source: D5FSFAH service manual, p. 2. Written in our own words; check the manual for your exact model.
Communication wire selection (RS485)
Heat pump · D5CURA
Communication wire runs up to the maximum system piping length. Stranded shielded wire is recommended. Thermostat wire can be reused only under set conditions.
- Use 16 AWG stranded shielded wire for RS485 between indoor and outdoor units; 16 to 18 AWG is allowed.
- Reuse 18 AWG thermostat wire only if it is not coiled, has no splices on the wires used, all unused wires are grounded to the ODU, it is in good condition, and no nearby EMI sources exist.
- Replace 18 AWG wire with 16 AWG stranded shielded wire if communication problems occur.
Applies to: D5CURA indoor to outdoor communication
Source: D5CURA product data, p. 116. Written in our own words; check the manual for your exact model.
Condensate drain
Heat pump · D5CMHA
Install drains that meet local plumbing codes.
- Install the drain to local plumbing code.
Applies to: D5CMHA indoor and outdoor units
Source: D5CMHA Product Data, p. 124. Written in our own words; check the manual for your exact model.
Crankcase and base pan heaters
Heat pump · D5CURA
Crankcase heater is fitted on all sizes and its clamps must sit around the compressor oil sump. A base pan heater is also standard on all sizes.
- Confirm the crankcase heater clamps are fitted around the compressor oil sump.
- Confirm the base pan heater is present on the unit.
Applies to: D5CURA outdoor units, all sizes
Source: D5CURA Product Data, p. 3. Written in our own words; check the manual for your exact model.
Dip switch defaults
Heat pump · D5FUAA
Dip switches not listed in the wiring diagram are factory set to OFF. Their specific use is covered in the installation manual.
- Check the installation manual before changing any dip switch that is not shown on the wiring diagram.
Applies to: D5FUAA indoor main board
Source: D5FUAA service manual, p. 16. Written in our own words; check the manual for your exact model.
Do not use 24 V indoor-outdoor wiring as the normal communication link
Heat pump · D5CURA
The 24 V wiring between indoor and outdoor units is not allowed as the standard communication method because of compliance issues. Use it only for emergency operation, service procedures and troubleshooting. Use the approved communication wiring methods for normal operation and to meet the published ratings.
Applies to: D5CURA outdoor unit with indoor unit wiring
Source: Carrier D5CURA product data, p. 121-125. Written in our own words; check the manual for your exact model.
Factory leak test of condenser coils
Heat pump · D5CURA
Air-cooled condenser coils are leak tested at the factory at 550 psig.
Applies to: D5CURA outdoor unit
Source: Carrier D5CURA product data, p. 126. Written in our own words; check the manual for your exact model.
Final tubing check and vacuum pump warning
Heat pump · D5CURA
Confirm factory tubing has not moved in shipping, and never run the compressor as a vacuum pump.
- Check that factory tubing on the indoor and outdoor units has not shifted during shipment.
- Make sure no tubes rub against each other or sheet metal.
- Check that wire ties on the feeder tubes are secure and tight.
- Do not use the system compressor as a vacuum pump.
Applies to: D5CURA indoor and outdoor units
Source: D5CURA service manual, p. 21. Written in our own words; check the manual for your exact model.
Jumper J7 for water level switch
Heat pump · D5FUAA
J7 has a short connector. It must be removed when the water level switch function is used.
- Remove the short connector from J7 when the water level switch is used.
Applies to: D5FUAA indoor main board
Source: D5FUAA service manual, p. 16. Written in our own words; check the manual for your exact model.
Jumper JR1 for ON-OFF function
Heat pump · D5FUAA
JR1 has a short connector. It must be removed when using the ON-OFF function.
- Remove the short connector from JR1 when the ON-OFF function is used.
Applies to: D5FUAA indoor main board
Source: D5FUAA service manual, p. 16. Written in our own words; check the manual for your exact model.
Keep power off until work is complete
Heat pump · D5CURA
Do not turn the power on until all installation work is finished. Consult experienced technicians before moving or relocating the unit.
- Leave power off until installation is complete.
Applies to: All units
Source: D5CURA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Leak check and flammable refrigerant safety
Heat pump · D5CURA
Safety points for refrigerant work on this system.
- Ventilate the area at once if refrigerant leaks during installation. Leaked gas is toxic and flammable.
- Check for leaks after the installation is finished.
- In a small room, take measures so that a leak cannot push the refrigerant concentration above the safety limit.
- Keep air, dust, moisture and foreign matter out of the refrigerant circuit.
Applies to: Refrigerant circuit installation
Source: Carrier D5CURA installation manual, p. 12. Written in our own words; check the manual for your exact model.
Limit buried refrigerant line length and rise
Heat pump · D5CURA
Buried refrigerant pipe can let refrigerant migrate to the cold buried section during shutdown, causing liquid slugging and possible compressor damage at start-up.
- Do not bury more than 36 in (914 mm) of refrigerant pipe.
- If any section is buried, make a vertical rise of at least 6 in (152 mm) to the outdoor unit valve connections.
Applies to: D5CURA refrigerant line installation
Source: D5CURA service manual, p. 1. Written in our own words; check the manual for your exact model.
Limit buried refrigerant pipe length
Heat pump · D5FUAA
Buried refrigerant line is limited so refrigerant does not migrate to the cold buried section and slug the compressor at start-up.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
Applies to: Refrigerant line installation
Source: D5FUAA Service Manual, p. 1. Written in our own words; check the manual for your exact model.
Limit on buried refrigerant pipe
Heat pump · D5FSFA
Buried refrigerant pipe must stay within limits. Refrigerant can migrate into a cold buried section and slug the compressor at start-up.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any section is buried, give it a vertical rise of at least 6 in. (152 mm) to the outdoor unit valve connections.
Applies to: D5FSFAH floor console ductless heat pump
Source: D5FSFAH service manual, p. 1. Written in our own words; check the manual for your exact model.
Outdoor unit power connection and wire matching
Heat pump · D5CURA
Connecting power to any terminal other than L1 or L2 damages the control board. Outdoor wire colors and terminal numbers must match the indoor unit.
- Connect line power only to L1 or L2, never to a signal terminal.
- Match each outdoor wire color and terminal number to the indoor unit.
- Tighten all connections firmly; loose wiring can overheat terminals.
- Keep wires clear of refrigerant tubing, the compressor and moving parts.
- Size the disconnect and wiring from the MCA and MOCP values on the electrical data table.
Applies to: D5CURA outdoor unit field wiring
Source: D5CURA service manual, p. 6. Written in our own words; check the manual for your exact model.
Outdoor unit power wiring
Heat pump · D5CURA
Connect power to the outdoor unit terminal block using fork terminals matched to the labels.
- Remove the electric cover of the outdoor unit.
- Connect each fork terminal to the terminal block.
- Match each wire label to the matching terminal label.
- Tighten each fork terminal firmly on its terminal.
- Insulate unused wires with electrical tape and keep them away from electrical and metal parts.
- Reinstall the electric control box cover.
Applies to: D5CURA outdoor unit
Source: D5CURA product data, p. 116. Written in our own words; check the manual for your exact model.
Power and communication wiring between outdoor and indoor unit
Heat pump · D5FCFA
Wire size and wire type depend on unit size. Use the correct method for the size being installed.
- For 09K through 24K: run a 14/3 power and communication cable with four wires (two AC power, one communication, one ground) from outdoor to indoor unit.
- If there is high EMF interference and communication faults, a 14/2 stranded shielded cable can replace L2 and S; land the shield to ground at the outdoor unit only.
- For 36K through 58K: run a 14/2 stranded power cable with ground (three wires) from outdoor to indoor unit to limit voltage drop.
- For 36K through 58K: use a separate shielded stranded copper communication cable rated 600 V, double insulated; the manual calls for a shielded 16 GA stranded control wire.
- Provide a disconnect within sight of and readily accessible from the air conditioner.
- Tighten every terminal connection; loose wiring can overheat the terminal.
- Keep all wires clear of refrigerant tubing, the compressor and moving parts.
- Route the conduit cable through the hole in the conduit panel and follow local codes for the indoor-to-outdoor run.
Applies to: 18K to 58K
Source: D5FCFAH service manual, p. 9. Written in our own words; check the manual for your exact model.
Power supply and disconnects
Heat pump · D5CURA
Outdoor and indoor units each need their own separate power. An auxiliary electric heater needs a separate supply too.
- Provide separate power for the outdoor unit and the indoor unit.
- Provide a separate supply for the auxiliary electric heater.
- Install service disconnects for the outdoor and indoor units per NEC and local codes.
- Size wires per NEC or CEC and local codes using the MCA and MOCP values from the electrical data table.
Applies to: D5CURA system
Source: D5CURA product data, p. 116-117. Written in our own words; check the manual for your exact model.
Pre-installation checks
Heat pump · D5CURA
Confirm the indoor unit is compatible with the outdoor unit using the product data, confirm the application, and do a heat load calculation for sizing.
- Check indoor and outdoor unit compatibility.
- Confirm the application.
- Perform a heat load calculation.
Applies to: All units
Source: D5CURA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Refrigerant charge and long runs
Heat pump · D5CMHA
Outdoor units ship with a full charge of R-454B refrigerant. Runs longer than the maximum piping length with no additional charge need a charge adjustment; the charge adjustment table is in the Refrigerant Piping section, which is not on these pages.
- Check the line run length against the maximum piping length with no additional charge.
- If the run is longer, look up the charge adjustment in the Refrigerant Piping section of the product data.
Applies to: D5CMHA systems with runs above the maximum piping length
Source: D5CMHA Product Data, p. 124. Written in our own words; check the manual for your exact model.
Refrigerant line installation
Heat pump · D5CURA
Units ship with a full R-454B charge based on 25 ft runs. Longer runs need a charge adjustment from the Long Line section.
- For runs over 25 ft (7.6 m), review the Long Line Applications section and adjust the charge.
- Do not bury refrigerant lines deeper than 36 in (914 mm).
- Provide at least 6 in (152 mm) of vertical rise to the service valves when lines are buried, to prevent refrigerant migration.
- Do not bury lines in the ground except as allowed above.
- Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation; the liquid line does not need insulation.
- Use closed-cell insulation on all long line runs.
- Isolate interconnecting tubing from the building structure so vibration and noise are not transmitted.
Applies to: D5CURA refrigerant piping
Source: D5CURA product data, p. 116. Written in our own words; check the manual for your exact model.
Refrigerant line length and insulation
Heat pump · D5CMHA
Minimum line length between indoor and outdoor units is 10 ft (3 m). Insulate each refrigerant line separately with at least 1/2 in (12.7 mm) thick insulation. Closed-cell insulation is recommended for long-line runs. Isolate the tubing from the building structure so vibration and noise do not transmit into it. Long-line applications need no change in line sizing.
- Keep the line run at least 10 ft (3 m).
- Insulate the liquid and suction lines separately, at least 1/2 in (12.7 mm) thick.
- Use closed-cell insulation on long-line runs.
- Isolate the tubing from the structure.
Applies to: D5CMHA line sets
Source: D5CMHA Product Data, p. 124. Written in our own words; check the manual for your exact model.
Refrigerant line routing and insulation rules
Heat pump · D5CURA
Keep buried line length and drop height within limits, insulate the suction line, and isolate the tubing from the building structure.
- Do not bury more than 36 in (914 mm) of refrigerant pipe.
- If any pipe is buried, provide at least a 6 in (152 mm) vertical rise to the outdoor unit service valves to prevent refrigerant migration and slugging at start-up.
- Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Closed-cell insulation is recommended on long-line runs.
- Isolate the interconnecting tubing from the building structure so vibration and noise do not transmit into it.
Applies to: D5CURA refrigerant piping
Source: D5CURA service manual, p. 20. Written in our own words; check the manual for your exact model.
Selecting indoor unit combinations and system size
Heat pump · D5CMHA
If the system will run at maximum load for most of the time, select the next larger system capacity. Use the application tables to confirm the indoor unit combination for the outdoor size.
- Estimate how often the load stays near maximum.
- If it runs near maximum most of the time, select the next larger outdoor size.
- Confirm the indoor combination in the application tables.
Applies to: D5CMHA system selection
Source: D5CMHA Product Data, p. 122. Written in our own words; check the manual for your exact model.
Separate power and control wiring
Heat pump · D5CURA
Control signal cable must be run apart from power wiring to avoid interference. Metal conduit or shielded cable is recommended.
- Run control signal cable separately from power wiring.
- Keep at least 12 in (300 mm) between control wiring and power wiring.
- Do not run power and control wiring in the same conduit.
- Size all wiring per NEC/CEC and local codes, and use different colors for different wires.
Applies to: D5CURA field wiring
Source: D5CURA service manual, p. 6. Written in our own words; check the manual for your exact model.
Triple evacuation method (when the pump cannot reach 500 micron)
Heat pump · D5CURA
Use only if the vacuum pump cannot pull 500 micron and the system holds no liquid water. Always break vacuum with dry nitrogen.
- Attach gauges and evacuate the system to 28 in Hg. Keep the pump running for 15 more minutes.
- Close the service valves and shut off the pump.
- Connect a nitrogen cylinder with regulator and flow nitrogen until system pressure reads 2 psig.
- Close the service valve and let the system stand for 1 hour so the dry nitrogen can absorb moisture.
- Repeat the evacuation and nitrogen steps as shown in Fig. 20 until the system is clean and dry.
Applies to: D5CURA evacuation when deep vacuum is not possible
Source: D5CURA service manual, p. 21. Written in our own words; check the manual for your exact model.
Refrigerant charging mode on Infinity control (25VNA8/24VNA9)
Heat pump · Carrier Infinity 18VS 25VNA8
Opened from the Installation and Service screen to check or set charge. Offers weigh-in or heating check methods; the heating check runs at stage 5 with matched fans and counts down while stabilizing. Service-valve subcooling shows only when temperatures are in range.
- On the Infinity control open Installation and Service, then Refrigerant Charging
- Pick the charge method on the Charging Mode Selection screen
- Wait for the stabilization countdown before reading pressures
Applies to: Carrier Infinity 25VNA8/24VNA9 communicating systems
Source: Carrier 25VNA8/24VNA9 service manual, Check Charge and Heating Check Chart Procedure, p.9-12. Written in our own words; check the manual for your exact model.
Charging and recharging requirements for flammable refrigerant
Mini-split · D5FSOA
Follow normal charging practice plus the flammable refrigerant rules. Avoid overfilling. The system must be leak tested after charging and again before leaving the site.
- Use only tools rated for flammable refrigerant, and keep hoses as short as possible.
- Keep refrigerant cylinders upright and make sure the system is earthed before charging.
- Before recharging, pressure test with oxygen-free nitrogen (OFN).
- Do not charge refrigerant into a system that is not clean and checked. Never use compressed air or oxygen for purging.
- Label the system once charging is complete.
- Carry out a leak test after charging and before commissioning, and repeat it before leaving the site.
Applies to: D5FSOAH systems using flammable refrigerant
Source: Carrier D5FSOAH service manual, p. 6-7. Written in our own words; check the manual for your exact model.
Condensate drain
Mini-split · D5FCFA
Drain must meet local sanitation codes.
- Install drains to meet local sanitation codes.
- If adequate gravity drainage cannot be provided, fit the accessory condensate pump.
- Check the drain size in the specifications table.
Applies to: Indoor unit condensate drain
Source: D5FCFA Product Data, p. 9. Written in our own words; check the manual for your exact model.
Condensate drain trap and slope
Mini-split · D5FSAA, D5FLAA
Negative pressure at the drain connection needs a trap.
- Install a drain trap as close to the unit as possible.
- Keep the top of the trap below the drain pan connection so the pan drains fully.
- Pitch the drain line 1/8 in per foot.
- Keep the drain outlet at least 1.9 in (5 cm) above the ground.
- On horizontal runs, install an anti-siphon air vent (standpipe) ahead of the run.
- Screw seal plugs in by hand only. Incorrect drain setup can flood the unit.
Applies to: Indoor unit condensate drain
Source: D5FSAA and D5FLAA installation instructions, p. 26. Written in our own words; check the manual for your exact model.
Confirm interunit wiring before power-up
Mini-split · D5CURA
Record whether there were any breaks, splices, wire nuts or butt connectors between the outdoor and indoor units. Also confirm that the outdoor port wiring goes to the correct indoor unit.
- Record the wire size and type used.
- Check the run between the outdoor unit and the indoor unit for breaks, splices, wire nuts or butt connectors.
- Verify that the wiring from the outdoor unit port goes to the correct indoor unit.
- Record the answers on the checklist.
Applies to: D5CURA single zone systems
Source: Carrier D5CURA installation manual, p. 32. Written in our own words; check the manual for your exact model.
Crankcase heater clamp placement
Mini-split · D5CMHA
The crankcase heater is standard on all sizes. Its clamps must be placed around the compressor oil sump.
- Confirm the crankcase heater is fitted on the unit.
- Place the heater clamps around the compressor oil sump.
Applies to: D5CMHA outdoor units, all sizes
Source: Carrier D5CMHA product data, p. 4. Written in our own words; check the manual for your exact model.
Drain hose routing
Mini-split · D5FSHA
Correct drain hose placement prevents water traps and overflow.
- Attach the drain hose on the same side the refrigerant piping exits the unit.
- Put the drain hose at the bottom of the pipe bundle.
- Keep the hose free of kinks and dents.
- Do not place the hose end in water or in containers that collect water.
- Wrap the indoor section of the hose with foam pipe insulation.
- Plug any unused drain hole with the rubber plug provided.
- Pour a small amount of water into the drain pan to confirm smooth flow.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 18-20. Written in our own words; check the manual for your exact model.
Electrical supply requirements
Mini-split · D5FCFA Ceiling/Floor Ductless
Limits on supply voltage, disconnects and grounding for the installation.
- Keep supply voltage within 90-110% of rated voltage.
- Use an all-pole disconnect with at least 1/8 in (3 mm) contact separation.
- Use an RCD rated at 30 mA or less where required.
- Give the unit its own branch circuit. Do not share it with other appliances.
- Ground the unit and check that every terminal wire is firmly connected.
- Turn off power and wait at least 10 minutes before touching electrical components.
- Connect outdoor wires before indoor wires.
Applies to: All field wiring
Source: Carrier D5FCFA installation manual, p. 2 and p. 19. Written in our own words; check the manual for your exact model.
Evacuation check after pulling vacuum
Mini-split · D5FCFA
The system must reach the required vacuum before it is checked for holding. The vacuum target is the lower of 500 microns or the level required by local code.
- Pull the system down to the specified vacuum level or lower.
- Isolate the system from the vacuum pump.
- Confirm the pressure does not rise above 1500 microns within 10 minutes.
Applies to: Split system field piping
Source: Carrier D5FCFAH service manual, p. 5. Written in our own words; check the manual for your exact model.
Evacuation method and vacuum hold
Mini-split · D5CURA
Evacuate the system with either the triple evacuation method or the deep vacuum method, as described in the installation manual. For deep vacuum, the system must hold 500 microns for 1 hour.
- Choose triple evacuation or deep vacuum, as described in the installation manual.
- If using deep vacuum, pull the system down to 500 microns.
- Close the valves and confirm the system holds 500 microns for 1 hour.
- Confirm the line set diameter matches the evaporator connections.
- Record each answer on the checklist.
Applies to: D5CURA refrigerant circuit
Source: Carrier D5CURA installation manual, p. 33. Written in our own words; check the manual for your exact model.
Field piping pressure test and evacuation limits
Mini-split · D5FSOA
Field refrigerant piping must be pressure tested with inert gas, then vacuum tested, before charging. Indoor field joints also need a tightness test.
- Pressure test field piping with inert gas. The low side is tested to its design pressure. The high side is tested to its design pressure, unless it cannot be isolated from the low side; then test the whole system to the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
- Evacuate to the vacuum level given in the manual or lower. The lower of 500 microns or the local code value applies.
- Isolate the pump and check that pressure does not rise above 1500 microns within 10 minutes.
- Test indoor field-made joints with a detector sensitive to 5 g/year of refrigerant or better, at at least 0.25 times the maximum allowable pressure. No leak is allowed.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
Applies to: Field refrigerant piping of D5FSOAH systems
Source: Carrier D5FSOAH service manual, p. 1, p. 5. Written in our own words; check the manual for your exact model.
Field refrigerant piping pressure and vacuum test
Mini-split · D5FCFA
Pressure test and evacuate field piping before charging. Use inert gas for the pressure test and oxygen-free nitrogen for flammable refrigerant systems. Never use air or oxygen-containing gas.
- Pressure test the low side at its design pressure and the high side at its design pressure. If the high side cannot be isolated, test the whole system at the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of the test pressure.
- Pull a vacuum to the level in the manual, which is 500 microns or less, or the level required by local code.
- Isolate the system from the vacuum pump. The pressure must not rise above 1500 microns within 10 minutes.
- Charge by the liquid method only, and keep hoses as short as possible.
Applies to: Split systems with field piping
Source: D5FCFA installation manual, p. 3 and p. 5. Written in our own words; check the manual for your exact model.
Final system checks before handover
Mini-split · D5FSOAH
Confirm the installation is finished and the customer is briefed before leaving site.
- Conceal tubing where possible and fasten it to the outside wall.
- Confirm the drain slopes downward along its full length.
- Confirm all tubing and connections are insulated.
- Seal the hole where cables and tubing pass through the wall.
- Check all remote buttons, the display panel lights, the air deflection louver and the drain.
- Explain operation, mode selection, timer, filter removal and cleaning, louver setting and care.
- Leave the owner's manual and installation instructions with the customer.
Applies to: Indoor unit commissioning
Source: D5FSOAH installation instructions, p. 23. Written in our own words; check the manual for your exact model.
Flammable refrigerant R-454B service precautions
Mini-split · D5FSOAH
The system uses R-454B, a flammable refrigerant. Only trained service personnel may repair it.
- Keep ignition sources out of the storage room.
- Do not puncture refrigerant tubing.
- Do not use methods to speed defrost or clean other than those the manufacturer recommends.
- Never use air or oxygen-containing gas for leak testing or running compressors.
Applies to: D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
Source: D5FSOAH service manual, p. 3. Written in our own words; check the manual for your exact model.
Indoor to outdoor communication wiring
Mini-split · D5FSCAH / D5FLCAH
The indoor and outdoor units communicate over a nonpolar RS-485 link. The connections are polarity sensitive, and wrong polarity causes a fault code.
- Do not use thermostat wire for the indoor to outdoor connection.
- Connect the indoor and outdoor units exactly as shown in the connection diagram for the model size.
- Check polarity on the RS-485 communication pair before power-up.
Applies to: 9K~48K
Source: D5FSCAH / D5FLCAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Indoor unit adjustment for embedded pipes
Mini-split · D5FSHA
The indoor unit can shift sideways to fit embedded pipes.
- If there is not enough room for embedded pipes, move the indoor unit left or right by about 1.18 to 1.95 in (30 to 50 mm), depending on model.
- Use the kickstand at the back of the unit to prop it up while connecting pipes and drain hose.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 17-18. Written in our own words; check the manual for your exact model.
Indoor unit mounting height for flammable refrigerant
Mini-split · D5FSCAH / D5FLCAH
The indoor unit must be mounted at least 5.9 ft (1.8 m) above the floor. The room area must meet the minimum in the room area table for the charge.
- Mount the indoor unit at least 5.9 ft (1.8 m) above the floor.
- Check the charge against the room area table for the measured centre height.
- Correct the minimum area for altitude if needed.
Applies to: Indoor unit installation
Source: D5FSCAH / D5FLCAH service manual, p. 4. Written in our own words; check the manual for your exact model.
Indoor unit placement and mounting
Mini-split · D5FCFA
Position the fan coil for airflow and support.
- Level the indoor unit in all planes for reliable operation.
- Keep adequate clearance for airflow (see Fig. 11).
- Mount the unit on the floor or against an outside wall for best air circulation, centred on the wall where possible.
- Keep furniture and curtains away from the return and discharge so the unit does not short cycle or recirculate air.
- Place the unit facing the normal location of room occupants.
- Support the fan coil weight adequately; use the mounting bracket locations on the dimension drawings.
Applies to: Indoor fan coil installation
Source: D5FCFA Product Data, p. 9. Written in our own words; check the manual for your exact model.
Installation height and room height limits
Mini-split · D5FSOAH
The indoor unit must be mounted at least 7.6 ft (2.3 m) above the floor. The room height must be at least 7.3 ft (2.2 m).
- Mount the indoor unit at least 7.6 ft (2.3 m) above the floor.
- Confirm the room height is at least 7.3 ft (2.2 m).
- Check the minimum room area for the system charge against the table for the installed height.
Applies to: Indoor unit installation
Source: D5FSOAH Owner's Manual, p. 7. Written in our own words; check the manual for your exact model.
Insulate refrigerant lines
Mini-split · D5FSOA
Both refrigerant lines must be insulated.
- Insulate the gas line.
- Insulate the liquid line.
Applies to: D5FSOA system
Source: Carrier D5FSOA product data, p. 19. Written in our own words; check the manual for your exact model.
Leak test indoor field joints
Mini-split · D5FCFA
Field-made joints inside the building must be tested for tightness with a sensitivity of 5 g/year of refrigerant or better.
- Test at a pressure of at least 0.25 times the maximum allowable pressure.
- Confirm no leak is detected.
- Do not use detachable joints on the indoor side. Brazed or welded joints are acceptable.
Applies to: Indoor field joints
Source: Carrier D5FCFAH service manual, p. 4-5. Written in our own words; check the manual for your exact model.
Leave pipe ends unwrapped for leak test
Mini-split · D5FSHA
The pipe ends must stay accessible for the final leak check.
- Wrap the pipe bundle, but leave the pipe ends unwrapped.
- Keep the connection point exposed for the leak test.
- After the leak test, wrap the connection point with insulation tape.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 18, 20. Written in our own words; check the manual for your exact model.
Minimum clearance above the indoor unit
Mini-split · D5FSHA
The 45MAHA-series note gives a minimum top clearance of 2 in, with 5.9 in recommended. Mounting height is set by the installation method.
- Use at least 2 in (5.08 cm) top clearance; 5.9 in is recommended.
Applies to: Indoor unit installation summary
Source: Carrier D5FSHA installation manual, p. 11. Written in our own words; check the manual for your exact model.
Nitrogen leak check
Mini-split · D5CURA
Hold the refrigerant piping at the specified pressure for the required time using dry nitrogen, then record the result.
- Pressurize the piping with dry nitrogen to 500 psig, not exceeding 550 psi.
- Hold the pressure for at least 30 minutes.
- Record YES or NO on the checklist.
Applies to: D5CURA refrigerant piping
Source: Carrier D5CURA installation manual, p. 33. Written in our own words; check the manual for your exact model.
Outdoor to indoor power and communication wiring
Mini-split · D5FSFA
Power and communication run between the outdoor and indoor units. Stranded copper with 600 V insulation is required. A shielded cable can replace the signal conductors in high EMF areas.
- Size wires per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use 14/3 stranded wire with ground, 600 V rated, for power and communication from outdoor to indoor unit.
- Connect L1 to terminal 1, N or L2 to terminal 2, and communication to terminal 3; land the green ground wire on the ground terminal.
- In high EMF areas with communication problems, use 14/2 stranded shielded wire for terminals 2 and 3 (polarity sensitive). Land the shield on ground at the outdoor unit only.
- Keep wires clear of refrigerant tubing, the compressor and moving parts, and tighten every connection.
Applies to: D5FSFAH 9K to 16K
Source: D5FSFAH service manual, p. 10. Written in our own words; check the manual for your exact model.
Pre-test run checklist
Mini-split · D5FSOAH
Confirm these points before switching the system on for the test run.
- Indoor and outdoor units are properly installed.
- Piping and wiring are connected correctly.
- No obstacles block the unit inlet or outlet.
- Refrigeration system has no leaks.
- Drainage runs freely to a safe location.
- Heating insulation is installed.
- Ground wires are connected.
- Piping length and any added refrigerant charge are recorded.
- Supply voltage is correct for the unit.
Applies to: System test run
Source: D5FSOAH installation instructions, p. 24. Written in our own words; check the manual for your exact model.
Pressure test and evacuation values
Mini-split · D5FSAA, D5FLAA
Values from the piping and start-up checklist. The pages disagree on the test time.
- Pressure test with dry nitrogen to a maximum of 500 psig.
- Hold the test for at least 60 minutes (p. 25). The start-up checklist lists a 30-minute hold with a 550 psig maximum (p. 50).
- Evacuate with the triple or deep vacuum method.
- Confirm the system holds 500 microns for 1 hour.
Applies to: Leak test and evacuation before charging
Source: D5FSAA and D5FLAA installation instructions, p. 25, p. 50. Written in our own words; check the manual for your exact model.
Pressure test field piping before charging
Mini-split · D5FCFA
Field piping must be pressure tested with inert gas before the vacuum and refrigerant charge. Never use air or oxygen-containing gases for leak testing.
- Pressure test the low side at the low side design pressure and the high side at the high side design pressure.
- If the high side cannot be isolated from the low side, test the whole system to the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge.
- Use a gauge with resolution no coarser than 5% of the test pressure.
- Use inert gas only. Do not use compressed air or oxygen.
Applies to: Split system field piping
Source: Carrier D5FCFAH service manual, p. 1, 5. Written in our own words; check the manual for your exact model.
Record error codes at start-up
Mini-split · D5CURA
Check for error codes at start-up. The checklist asks whether any were present, and the outdoor, indoor, wall controller and 24V interface entries are used to record them.
- Check the outdoor unit, indoor unit, wall controller and 24V interface for error codes.
- Record any codes in the matching field on the checklist.
- Write YES or NO to the start-up error code question.
Applies to: D5CURA system
Source: Carrier D5CURA installation manual, p. 33. Written in our own words; check the manual for your exact model.
Record single zone liquid line data
Mini-split · D5CURA
For single zone piping, measure the liquid line length and calculate the additional refrigerant charge. Record the size, length and charge for each port.
- Measure the liquid pipe length.
- Calculate the additional charge for that length.
- Record the liquid line size, length and charge on the checklist for each port.
Applies to: D5CURA single zone piping
Source: Carrier D5CURA installation manual, p. 33. Written in our own words; check the manual for your exact model.
Refrigerant line installation rules
Mini-split · D5FCFA
Limits for buried lines, rise to service valves and insulation thickness.
- Do not bury refrigerant lines directly in the ground.
- If lines must be buried, bury no more than 36 in (914 mm).
- Give the buried run a minimum 6 in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
- Insulate both lines with at least 1/2 in (12.7 mm) thick insulation; closed-cell is recommended for long lines.
- Isolate the interconnecting tubing from the building structure so vibration and noise are not carried into it.
- Outdoor units ship with a full charge of R-454B refrigerant.
Applies to: Interconnecting refrigerant tubing
Source: D5FCFA Product Data, p. 9-10. Written in our own words; check the manual for your exact model.
Refrigerant line length and burial limits
Mini-split · D5FSFA
Line sets are sized on runs up to 25 ft. Longer runs need extra charge within the allowable length from the product data.
- Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
- Do not bury more than 36 in (914 mm) of line. If any section is buried, give it a 6 in (152 mm) vertical rise to the service valves.
- Insulate both lines separately with at least 1/2 in (12.7 mm) insulation; closed-cell is recommended on long runs.
- Isolate the tubing from the building structure so vibration and noise do not transfer.
- For runs over 25 ft, add refrigerant up to the allowable length in the product data.
Applies to: D5FSFAH 9K to 16K, R-454B system
Source: D5FSFAH service manual, p. 12. Written in our own words; check the manual for your exact model.
Remote control range and timer distance
Mini-split · D5FS(L)AAH
The remote works up to 26 ft (8 m) with no obstructions. When the timer is used, keep the remote within 26 ft (8 m) of the indoor unit. The remote is shared across other indoor units.
- Point the remote at the right side of the unit when sending commands.
- Listen for the beep to confirm the unit received the command.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: Carrier D5FS(L)AAH owner's manual, p. 13. Written in our own words; check the manual for your exact model.
Single zone performance check record
Mini-split · D5FSHA
For 1:1 single zone systems, record operating data after the unit has run.
- Adjust the set-point to create an operational call for the test.
- Let the system run for at least 10 minutes.
- Record T1, T2, T3, T4, Tb, Tp, Th and LA/Lr with the remote controller Point Check function.
- Record any indoor or outdoor error codes and wall controller and 24V interface notes.
Applies to: Single zone systems
Source: Carrier D5FSHA installation manual, p. 28. Written in our own words; check the manual for your exact model.
Start-up checklist items to record
Mini-split · D5FCFA Ceiling/Floor Ductless
Items to write on the start-up checklist before leaving the job.
- Record wire size and type, and confirm no splices or wire nuts between outdoor and indoor units.
- Verify the wiring from the outdoor port to the correct indoor unit.
- Record liquid line size, length and additional charge. Record the final charge.
- Confirm the line set matches the evaporator connection diameter.
- Record whether any error codes were present at start-up.
- Record the indoor and outdoor error codes, if any, on the checklist.
Applies to: Ductless start-up checklist
Source: Carrier D5FCFA installation manual, p. 23-24. Written in our own words; check the manual for your exact model.
Timer function is relative, not clock time
Mini-split · D5FCFA
The 24-hour timer does not change the running mode. If the unit is off when a timer-off is set, it stays off until the timer on time is reached.
- Set Timer On, Timer Off, Timer On/Off or Timer Off/On on the remote.
- Confirm the unit's current mode is unchanged after the timer is set.
Applies to: D5FCFA
Source: Carrier D5FCFA product data, p. 6. Written in our own words; check the manual for your exact model.
Wall hole slope for drainage
Mini-split · D5FSHA
The wall hole must drain toward the outside so condensate does not run back into the room.
- Drill the wall hole with a 2.5 in (65 mm) or 3.54 in (90 mm) core drill.
- Drill at a slight downward angle so the outdoor end is about 0.2-0.275 in (5-7 mm) lower than the indoor end.
- Place the protective wall cuff in the hole.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 16. Written in our own words; check the manual for your exact model.
Other
Everything else worth knowing at the appliance.
Aluminum tubing and dissimilar metals
Air conditioner · DLFULA
Keep aluminum tubing from contacting dissimilar metals and keep condensate from running onto them. Dissimilar metals cause galvanic corrosion and early failure.
- Separate aluminum tubes from dissimilar metal parts.
- Route condensate away from dissimilar metals.
Applies to: DLFULA indoor coil installation
Source: DLFULA installation instructions, p. 3. Written in our own words; check the manual for your exact model.
Auto-restart, louver memory and Breeze Away
Air conditioner · D5FSHAH
After a power loss the unit restarts automatically with its prior settings. When powered on, the louver returns to its former angle. Breeze Away avoids direct airflow on occupants.
Applies to: All models
Source: D5FSHAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Condensate drainage
Air conditioner · DLFULA
Condensate must drain freely from the unit. Install drainage piping per the manual so water does not back up into the home.
- Check that condensate drains freely from the unit.
- Install drain piping as specified in the manual.
- Check for water backup after install.
Applies to: DLFULA indoor coil installation
Source: DLFULA installation instructions, p. 3. Written in our own words; check the manual for your exact model.
Dual fuel operation setup
Air conditioner · DLFULA
For dual fuel, the compressor drop-out temperature is set on the S3 dial of the interface. The S3 table is in the KSACN1101AAA Installation Manual, page 11, which is not part of this document. On a wired controller, set the heat mode to HEAT + AUX to run the heat for dual fuel.
- Set the S3 dial on the interface for compressor drop-out temperature using the KSACN1101AAA Installation Manual S3 table, page 11.
- On a wired controller, set the heat mode to HEAT + AUX.
- Use the Mode button to select HEAT+AUX if setting from the interface.
Applies to: DLFULA dual fuel systems
Source: DLFULA Installation Instructions, p. 17. Written in our own words; check the manual for your exact model.
ECO Intelligent Eye behaviour
Air conditioner · D5FSHAH
Intelligent Eye detects people in the room. In COOL or HEAT, if no activity is sensed for 30 minutes the unit lowers compressor frequency to save energy. It restarts operation when activity is sensed again.
Applies to: Units with Intelligent Eye only
Source: D5FSHAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
Recycle components before disposal
Air conditioner · DLFULA
Environmental caution: remove and recycle all components and materials, including oil and refrigerant, before the unit is finally disposed of.
- Remove and recycle all components and materials, including oil and refrigerant, before final disposal.
Applies to: DLFULA air conditioner disposal
Source: DLFULA Installation Instructions, p. 17. Written in our own words; check the manual for your exact model.
Routine maintenance and filter care
Air conditioner · DLFULA
The unit needs periodic maintenance at least once a year, and the frequency should be confirmed with the local dealer. Maintenance needs mechanical skill and tools; otherwise use the dealer. The only owner service is filter cleaning or replacement monthly.
- Schedule maintenance at least once a year, or as the local dealer advises.
- Clean or replace the filter monthly.
- Turn off the unit and disconnect power before any cleaning.
- Do not clean with excessive water or combustible cleaning agents.
Applies to: DLFULA air conditioner
Source: DLFULA Installation Instructions, p. 17. Written in our own words; check the manual for your exact model.
Wiring holes and sensor extension wires
Air conditioner · DLFULA
The 1/2-inch wiring holes on the control box need standard conduit fittings and conduit (flexible or rigid). Extension wires for sensors T1 and T2 are included in the accessory kit.
- Install standard conduit fittings in the 1/2-inch wiring holes.
- Use flexible or rigid conduit.
- Use the accessory-kit extension wires for T1 and T2 if needed.
Applies to: DLFULA indoor coil installation
Source: DLFULA installation instructions, p. 4. Written in our own words; check the manual for your exact model.
115V conversion
Air handler · D5FUAA
The unit can be converted to 115V applications.
Applies to: D5FUAA air handler
Source: Carrier D5FUAA crossover air handler product data, p. 4. Written in our own words; check the manual for your exact model.
24 V communication prohibited
Air handler · D5FUAA
24 V communication between indoor and outdoor units is not allowed for compliance reasons. Do not connect 24 V AC to S1-S2; this will damage the system.
- Check the wiring nameplate before wiring.
- Never connect 24 V AC to S1 or S2.
Applies to: D5FUAA
Source: D5FUAA Crossover Air Handler product data, p. 12. Written in our own words; check the manual for your exact model.
Active clean (self-clean) cycle
Air handler · D5FUAAH
Cleans and dries the evaporator automatically.
- Press CLEAN to start. The function works only in COOL or DRY mode.
- The cycle runs about 30 minutes, then the unit turns off automatically.
- Press CLEAN during the cycle to cancel and turn the unit off.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 14. Written in our own words; check the manual for your exact model.
Adding refrigerant on long pipe runs
Air handler · D5FUAA
Standard pipe length in North America is 25 ft (7.5 m). Charge any extra refrigerant from the service port on the outdoor unit low pressure valve. Refer to the outdoor unit manual for the amount.
Applies to: D5FUAA with extra pipe length
Source: D5FUAA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Air filter replacement interval
Air handler · D5FUH
The filter should be replaced every 30 to 90 days depending on its thickness and MERV rating. The user must buy a standard filter that meets UL900.
- Replace the filter every 30 to 90 days, based on filter thickness and MERV rating.
- Inspect and clean or replace the filter monthly or as needed.
- Use only a standard filter that meets UL900.
Applies to: Indoor unit air filter
Source: Carrier D5FUHAQ owner's manual, p. 8 and p. 16. Written in our own words; check the manual for your exact model.
Air filter requirement
Air handler · D5FSAA, D5FLAA
The filter is not supplied. The installer must provide a standard filter that meets UL900. Ask the manufacturer if you need help choosing one.
- Fit a UL900 standard filter.
Applies to: D5FSAA / D5FLAA air handler
Source: Carrier D5FSAA/D5FLAA installation manual, p. 16. Written in our own words; check the manual for your exact model.
Air outlet height in room
Air handler · D5FSAA / D5FLAA
Where the unit connects to one or more rooms by air duct, the bottom of the duct air outlet in the room must be at a height of 7.3 ft (2.2 m) from the floor.
- Set the bottom of the room air outlet at 7.3 ft (2.2 m) above the floor.
Applies to: Ducted room outlets
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 4. Written in our own words; check the manual for your exact model.
Alarm output (CN33)
Air handler · D5FUAA
Passive relay output. Relay is normally open in normal operation and closes when a fault is active. An external voltage signal must be supplied.
- Wire the alarm device to CN33 and supply the voltage signal needed for the device.
Applies to: D5FUAA indoor unit
Source: D5FUAA installation instructions, p. 25. Written in our own words; check the manual for your exact model.
Auto defrost in HEAT mode
Air handler · D5FS(L)AAH
When the outdoor coil frosts in HEAT mode, the indoor and outdoor fans turn off while the frost is removed. Normal operation resumes automatically.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Auto-restart after power failure
Air handler · D5FSAA
The indoor unit stores its current settings. After a sudden power loss, it restores those settings automatically within 3 minutes of power returning.
- After a power failure, allow up to 3 minutes for the unit to restore its previous settings.
- If settings do not return, check the power supply and the indoor unit's auto-restart module.
Applies to: D5FSAA indoor units
Source: Carrier D5FSAA product data, p. 4. Written in our own words; check the manual for your exact model.
Automatic restart after power failure
Air handler · D5FUAA
After a power failure the unit returns to the same operating conditions it had when power was lost.
Applies to: D5FUAA crossover air handler
Source: D5FUAA product data, p. 25. Written in our own words; check the manual for your exact model.
Built-in 24V interface and controls
Air handler · D5FUAA
A built-in 24V interface allows a third-party thermostat to control the system. The unit has microprocessor controls, cleanable filters, and built-in diagnostics. Freeze protection and high temperature protection on the heat pump are standard.
Applies to: D5FUAA air handler
Source: Carrier D5FUAA crossover air handler product data, p. 4. Written in our own words; check the manual for your exact model.
Built-in control functions
Air handler · D5FUHA
The indoor control includes several protection and operating functions.
- After a power failure, the unit returns to the operating condition it had when power was lost.
- Heat pump mode switches automatically between heating and cooling, with a deadband to prevent rapid cycling.
- Indoor coil freeze protection and high coil temperature protection are active in heat pump mode.
- Self diagnostics display error messages on the unit.
Applies to: D5FUHA indoor air handler
Source: D5FUHA Product Data, p. 28. Written in our own words; check the manual for your exact model.
Buried refrigerant pipe limits
Air handler · D5FSAA / D5FLAA
No more than 36 in. (914 mm) of refrigerant pipe may be buried. If any section is buried, there must be a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
- Limit buried refrigerant pipe to 36 in. (914 mm).
- Provide a 6 in. (152 mm) vertical rise to the outdoor valve connections where any pipe is buried.
Applies to: Refrigerant line routing
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 2. Written in our own words; check the manual for your exact model.
Charging and leak test rules
Air handler · D5FUAA
Requirements for charging flammable refrigerant systems.
- Use tools suitable for flammable refrigerants and keep hoses as short as possible.
- Keep cylinders upright.
- Earth (ground) the refrigeration system before charging.
- Label the system when charging is complete.
- Do not overfill the system.
- Pressure test with oxygen-free nitrogen before recharging.
- Leak test after charging and before commissioning, and again before leaving the site.
Applies to: Flammable refrigerant systems
Source: D5FUAA Installation Instructions, p. 7. Written in our own words; check the manual for your exact model.
Charging and recharging requirements
Air handler · D5FUHA
Use only tools suited to flammable refrigerant. Keep hoses short and avoid cross-contamination. Keep cylinders upright. Earth the system before charging. Do not overfill. Pressure test with OFN before recharging. Leak test after charging and again before leaving the site. Label the system when charging is done.
- Use tools and hoses suited to flammable refrigerant, kept as short as possible.
- Keep cylinders upright and earth the system before charging.
- Do not overfill the system.
- Pressure test with OFN before recharging.
- Leak test after charging and before commissioning, and again before leaving the site.
- Label the system when charging is complete.
Applies to: Refrigerant charging
Source: Carrier D5FUHA service manual, p. 7. Written in our own words; check the manual for your exact model.
Check outdoor unit match and sizing before installing
Air handler · D5FUHA
Confirm the indoor unit is compatible with the outdoor unit using the product data. Confirm the application and run a heat load calculation for proper sizing.
- Check indoor and outdoor unit compatibility in the product data.
- Confirm the application and complete a heat load calculation.
Applies to: D5FUHA indoor unit
Source: D5FUHA installation manual, p. 16. Written in our own words; check the manual for your exact model.
Circuit board fuse replacement
Air handler · D5FULA
The circuit board has an overcurrent fuse. The rating is printed on the board. Only a blast-proof ceramic fuse may be used.
- Read the fuse rating printed on the circuit board.
- Replace only with a blast-proof ceramic fuse of the same rating.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 3, 8. Written in our own words; check the manual for your exact model.
Clean the indoor unit with approved methods only
Air handler · D5FUH
Turn off the unit and disconnect power before cleaning. Use a soft dry cloth or a damp lint-free cloth with neutral detergent. Do not use solvents, benzene, chemical cloths, running water or water above 104°F (40°C) on the front panel. Replacement fuses must match the removed fuse exactly.
- Turn off the unit and disconnect the power supply.
- Wipe with a soft dry cloth, or a damp lint-free cloth with neutral detergent.
- Do not use solvents, chemicals, combustible cleaners or running water.
- Keep water on the front panel below 104°F (40°C).
- Replace a blown fuse only with an identical fuse rating.
Applies to: Indoor unit cleaning and maintenance
Source: Carrier D5FUHAQ owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Cleaning precautions
Air handler · D5FULA
Only untrained personnel should do basic cleaning such as coil cleaning. Cut power before cleaning. Do not use excessive water or combustible cleaning agents.
- Turn off the device and disconnect power.
- Do not flood the unit with water.
- Do not use combustible cleaning agents.
Applies to: D5FULA indoor coil
Source: D5FULA installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Cleaning the air filter
Air handler · D5FS(L)AAH
Inspect and clean or replace the filter monthly or as needed. Clean by vacuuming or washing in warm water with mild detergent. Do not dry in direct sunlight, as the filter can shrink.
- Turn off the unit and disconnect power.
- Remove the filter cover.
- Remove the air filter.
- Vacuum the filter or wash it in warm water with mild detergent.
- Let it dry out of direct sunlight and reinstall.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 21-22. Written in our own words; check the manual for your exact model.
Clear the air outlet before installing
Air handler · D5FSAA, D5FLAA
Remove all accessories and packing material from the air outlet before mounting the indoor unit.
- Remove all accessories and packing from the air outlet.
- Do this before the unit is put in place.
Applies to: D5FSAA / D5FLAA air handler, 18-60K
Source: Carrier D5FSAA/D5FLAA installation manual, p. 16. Written in our own words; check the manual for your exact model.
Clearance and location limits
Air handler · D5FUAA
Location rules for the air handler.
- For units with an auxiliary electric heater, keep the unit at least 1 m (3 ft) from combustible materials.
- Do not install the unit where combustible gas leaks may collect.
- Install on a firm surface that can carry the unit weight.
- Install drain piping per the manual to avoid water damage.
- Do not turn on power until all work is complete.
Applies to: Indoor unit installation
Source: D5FUAA Installation Instructions, p. 3. Written in our own words; check the manual for your exact model.
Clearance from combustible materials
Air handler · D5FUHA
For units with an auxiliary electric heater, do not install the unit within 3 ft (1 m) of combustible materials.
- Keep at least 3 ft (1 m) between the unit and any combustible materials when an auxiliary electric heater is fitted.
Applies to: Units with auxiliary electric heater
Source: D5FUHA Installation Instructions, p. 3. Written in our own words; check the manual for your exact model.
Clearance from combustibles for units with auxiliary heater
Air handler · D5FSAA / D5FLAA
Units with an auxiliary electric heater must be kept at least 3 ft (1 m) from combustible materials.
- Keep units with auxiliary electric heater at least 3 ft (1 m) from combustible materials.
Applies to: Units with auxiliary electric heater
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 3. Written in our own words; check the manual for your exact model.
Compressor time delay after stop
Air handler · D5FS(L)AAH
If ON/OFF is pressed soon after a stop, the compressor will not start for 3 to 4 minutes to protect against frequent cycling. The unit beeps only when the signal is received correctly.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Condensate drain requirements
Air handler · D5FSAA, D5FLAA
Route the drain so water cannot leak onto the building or create icy walkways. A water leak can cause a water-level switch fault.
- Insulate all piping to prevent condensation.
- Slope and route the drain pipe so water drains away from the unit without bends or wrong installation.
- Place the drain outlet away from walkways because the outdoor unit discharges water in heat mode.
- Do not pull the drain pipe hard, because it can come loose.
- Seal around the drain pipe, liquid line and suction line to keep humid air out.
Applies to: D5FSAA / D5FLAA air handler
Source: Carrier D5FSAA/D5FLAA installation manual, p. 23. Written in our own words; check the manual for your exact model.
Control board fuse
Air handler · D5FUHA
The control board has a fuse for overcurrent protection. The rating is printed on the board, for example T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC or T30A/250VAC. Only a blast-proof ceramic fuse may be used.
- Read the rating printed on the board.
- Replace only with a blast-proof ceramic fuse of the same rating.
- Power off and disconnect before replacing.
Applies to: Indoor and outdoor control boards
Source: D5FUHA Installation Instructions, p. 3. Written in our own words; check the manual for your exact model.
Control board fuse replacement
Air handler · D5FUHA
The board is protected by a fuse. The rating is printed on the circuit board (examples given: T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC). Only a blast-proof ceramic fuse may be used.
- Read the fuse rating printed on the circuit board.
- Replace with the same rating in a blast-proof ceramic fuse only.
Applies to: Indoor unit control PCB
Source: Carrier D5FUHA service manual, p. 2. Written in our own words; check the manual for your exact model.
Control options and compatibility
Air handler · D5FUAAH
The unit can be run from the included wireless remote, the optional wired controller, or a third-party 24V heat pump thermostat. The wired controller and wireless remote cannot be used together with a third-party thermostat. If the remote is lost, the unit can be run from the Auto setting on the unit.
Applies to: D5FUAAH
Source: D5FUAAH Owner's Manual, p. 2, 8. Written in our own words; check the manual for your exact model.
Control options: wired controller, wireless remote, third-party thermostat
Air handler · D5FUH
The unit can be run from the included wireless remote, an optional wired controller (KSACN1401AAA), or a third-party heat pump thermostat on the built-in 24V interface. The wired controller and wireless remote cannot be used when a third-party thermostat is installed.
- Choose one control method only.
- Do not use the wired controller or wireless remote with a third-party thermostat.
Applies to: Indoor unit controls
Source: Carrier D5FUHAQ owner's manual, p. 8. Written in our own words; check the manual for your exact model.
Control system sensors
Air handler · D5FUAA
The indoor unit control board is a microprocessor that protects the system and controls operating modes. Thermistors sit in the indoor air inlet and on the indoor coil. Heat pump units also have a thermistor on the outdoor coil. These monitor operation and keep the unit within limits.
Applies to: D5FUAA indoor unit
Source: D5FUAA Crossover Air Handler product data, p. 11. Written in our own words; check the manual for your exact model.
Controls options
Air handler · D5FUAAH
Three ways the air handler can be controlled. The wired controller and the wireless remote cannot be used together with a third party thermostat.
- Wired controller (optional, KSACN1401AAA): non-polarity controller for all functions. It has an infrared receiver and can be used with the wireless remote.
- Wireless remote (included): same functions as the wired controller, usable alone or with the wired controller.
- Third party heat pump thermostat (not included): connects through the built-in 24V interface.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Decommissioning labels
Air handler · D5FULA
Equipment that has been decommissioned and emptied of refrigerant must be labeled, dated and signed. Units with flammable refrigerant must carry a flammable refrigerant label.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 7. Written in our own words; check the manual for your exact model.
Default dip switch positions
Air handler · D5FUAA
Unless noted, all dip switches on the indoor board default to OFF. Check the installation manual for the specific use of each switch.
Applies to: Indoor unit main board
Source: Carrier D5FUAA product data, p. 21. Written in our own words; check the manual for your exact model.
Default settings after power failure
Air handler · D5FUAAH
After power is restored the unit may return to factory defaults.
- Factory defaults are AUTO mode, AUTO fan and 76°F (24°C).
- Use the remote to update the unit status, since the remote and panel may not match.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 15. Written in our own words; check the manual for your exact model.
Dehumidification mode
Air handler · D5FUAA
Dehumidification increases moisture removal by changing system operation and setpoint. It only works with third-party thermostats that have a dehumidification option.
Applies to: D5FUAA crossover air handler
Source: D5FUAA product data, p. 25. Written in our own words; check the manual for your exact model.
Disconnect power and lock out before servicing
Air handler · D5FULA
Before installing, modifying or servicing the system, the main electrical disconnect must be OFF. There may be more than one disconnect. Lock out and tag each one.
- Switch off the main disconnect.
- Check for more than one disconnect.
- Lock out and tag each switch with a warning label.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 2-3. Written in our own words; check the manual for your exact model.
Do not mix refrigerant types
Air handler · D5FUAA
Never mix refrigerant types in the system.
Applies to: D5FUAA refrigerant circuit
Source: D5FUAA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Do not use air or oxygen for leak testing
Air handler · D5FULA
Never use air or gas containing oxygen for leak testing or for running refrigerant compressors. Oxygen mixtures can explode.
- Use only inert gas, such as oxygen-free nitrogen, for pressure testing.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 2. Written in our own words; check the manual for your exact model.
Drain hose and wiring checks after service
Air handler · D5FUH
Improper drain set-up can cause leakage and property damage. Improper wiring can cause shock or fire.
- Confirm the drain hose is installed per the instructions.
- Confirm all wires are connected per the instructions before power is restored.
Applies to: Indoor unit after service
Source: Carrier D5FUHAQ owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Duct connections, supports and insulation
Air handler · D5FUHA
Use flexible duct collars to reduce vibration and noise. Use sound absorbing lining in short return ducts. Insulate ducts that run through unconditioned space in cooling season and use a vapor barrier. Suspend ducts on flexible hangers, never fastened directly to the structure. The unit is not designed for free-blow (non-ducted) applications.
- Install flexible duct collars at the unit connections.
- Insulate ducts through unconditioned space and add a vapor barrier.
- Suspend ducts with flexible hangers.
Applies to: Supply and return ductwork
Source: D5FUHA installation manual, p. 16 and p. 18. Written in our own words; check the manual for your exact model.
Ducted air outlet, no free blow
Air handler · D5FUHA
The unit is not designed for non-ducted (free blow) use. Size the supply duct with a transition that matches the unit opening.
- Install a transition that matches the unit air outlet.
- Do not use the unit in free-blow applications.
Applies to: Supply air outlet
Source: Carrier D5FUHA installation instructions, p. 16. Written in our own words; check the manual for your exact model.
Ductwork acoustic treatment and fabrication
Air handler · D5FUHA
Metal ducts without a 90 degree elbow and 10 ft of main duct before the first branch may need internal acoustic lining. Fibrous duct must follow the SMACNA fibrous glass duct standard. Both must meet NFPA and UL 181 Class 1 requirements. Duct work must follow local and national codes.
- Check the metal duct layout for a 90 degree elbow and 10 ft of main duct before the first branch.
- Add internal acoustic lining where the layout does not meet this, or use fibrous duct built to SMACNA.
- Size the supply duct with a transition that matches the unit opening.
Applies to: Supply and return ductwork
Source: D5FUHA installation manual, p. 16. Written in our own words; check the manual for your exact model.
Ductwork and auxiliary devices with flammable refrigerant
Air handler · D5FULA
Do not install auxiliary devices that could be ignition sources in the ductwork. Only auxiliary devices approved by the manufacturer, listed by model, may be used in connecting ducts.
- Check the approved device list by model before adding any duct accessory.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant and air duct system
Source: D5FULA installation instructions, p. 6, 8. Written in our own words; check the manual for your exact model.
Ductwork auxiliary devices with A2L refrigerant
Air handler · D5FUHA
Only auxiliary devices approved by the manufacturer, or declared suitable for the refrigerant, may be installed in the connecting ductwork. Devices that could be an ignition source must not be placed in the duct. Examples include hot surfaces and electric switching devices.
- Use only manufacturer-approved auxiliary devices in the ductwork.
- Do not install electric switching devices or hot surfaces in the duct.
Applies to: Ducted A2L installations
Source: D5FUHA Installation Instructions, p. 8. Written in our own words; check the manual for your exact model.
Electrical disconnect and RCD requirements
Air handler · D5FSAA / D5FLAA
Fixed wiring needs an all-pole disconnect with at least 3 mm contact clearance in all poles. Where leakage may exceed 10 mA, an RCD rated 30 mA or less must be fitted.
- Install an all-pole disconnect with at least 3 mm clearance in all poles.
- Install an RCD rated at 30 mA or less where leakage may exceed 10 mA.
- Do not share the outlet with other appliances.
- Wire according to the connection diagram on the indoor and outdoor unit panels.
Applies to: Fixed wiring installations
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 2. Written in our own words; check the manual for your exact model.
Electrical safety before service
Air handler · D5FUHA
Turn off the main power before any electrical or wiring work. After power is off, wait at least 10 minutes before touching electrical components.
- Turn off and lock out the main power.
- Wait 10 minutes or more after power-off before touching electrical components.
- Verify the wiring against the diagram on the unit panels.
Applies to: D5FUHA indoor and outdoor units
Source: D5FUHA Installation Instructions, pp. 33-34. Written in our own words; check the manual for your exact model.
Electrical supply and disconnect requirements
Air handler · D5FUHA
Turn off power and lock out the main disconnect before installing, modifying or servicing. Fixed wiring must include an all-pole disconnect with at least 3 mm clearance per pole. An RCD with a rated residual operating current of 30 mA or less is required where leakage may exceed 10 mA. Use only the specified wire. Connect according to the electrical diagram on the unit panels. The control board cover must close properly.
- Switch off the main disconnect and tag it out.
- Wire the unit according to the diagram on the panels.
- Install an all-pole disconnect with at least 3 mm clearance per pole.
- Install a 30 mA or lower RCD where leakage may exceed 10 mA.
- Clamp all cables securely and confirm the control board cover closes.
Applies to: All electrical work
Source: D5FUHA Installation Instructions, p. 2-3. Written in our own words; check the manual for your exact model.
Energy saving checks for the homeowner
Air handler · D5FUHAQ
Simple checks to reduce run time when a call comes in about high energy use.
- Keep doors and windows closed.
- Use TIMER ON and TIMER OFF functions to limit run time.
- Avoid excessive setpoint temperatures.
- Close curtains during cooling to block direct sunlight.
- Close curtains during heating to keep heat in.
Applies to: D5FUHAQ installations
Source: D5FUHAQ Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Energy saving habits
Air handler · D5FUAAH
Simple user habits that keep the unit running efficiently.
- Keep doors and windows closed.
- Use the TIMER ON and TIMER OFF functions to limit run time.
- Do not block the air inlets or outlets.
- Inspect and clean the air filters regularly.
- Replace the air filter every 30 to 90 days, depending on thickness and MERV rating.
- Do not set the unit to excessive temperatures.
- Close curtains while cooling to block direct sunlight, and close them while heating to keep heat in.
- Keep objects away from the air inlet and outlet.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Factory default dip switch positions
Air handler · D5FUHA
Dip switches have factory defaults; the manual asks you to use the installation manual for specific dip switch functions.
- Leave all dip switches not listed in the manual set to OFF, which is the factory default.
- Check the installation manual before changing any dip switch function.
Applies to: D5FUHA indoor unit boards SW1 to SW5
Source: D5FUHA Product Data, p. 26. Written in our own words; check the manual for your exact model.
Factory nitrogen charge and TXV
Air handler · D5FULA
The coil ships with a 30-40 psi nitrogen charge. Nitrogen can leak past rubber plugs during storage, which does not mean the coil is leaking. The TXV has a factory-set superheat and cannot be field adjusted. The TXV is designed only for R454B, so use it only with outdoor units built for R454B.
- Check the coil pressure before removing plugs.
- Do not adjust the TXV superheat in the field.
Applies to: D5FULA coils
Source: Carrier D5FULA installation instructions, p. 22-23. Written in our own words; check the manual for your exact model.
Fan speed selection
Air handler · D5FUAA
The indoor fan speed can be set by the user to high, medium, low, or automatic control by the microprocessor in all operating modes. The fan motor has four speeds.
Applies to: D5FUAA crossover air handler
Source: D5FUAA product data, p. 25. Written in our own words; check the manual for your exact model.
Filter and energy saving care
Air handler · D5FUAAH
Keep the system running efficiently by following these basic rules.
- Replace the air filter every 30 to 90 days, depending on thickness and MERV rating.
- Keep doors and windows closed.
- Do not block air inlets or outlets or place objects near them.
- Do not set the unit to excessive temperatures.
- Close curtains during cooling to block direct sun, and during heating to keep heat in.
Applies to: D5FUAAH
Source: D5FUAAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Filter replacement and airflow
Air handler · D5FUHAQ
Keep the filter clean so airflow and efficiency stay up.
- Replace the air filter every 30 to 90 days, depending on thickness and MERV rating.
- Do not block the air inlets or outlets.
- Do not place objects near the air inlet or outlet.
Applies to: D5FUHAQ air handler
Source: D5FUHAQ Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Filter requirement
Air handler · D5FUAA
The user must provide a standard filter that meets UL 900. Consult the manufacturer for filter selection questions.
Applies to: D5FUAA 18K to 60K
Source: D5FUAA Crossover Air Handler product data, p. 8. Written in our own words; check the manual for your exact model.
Filter requirements
Air handler · D5FUAA
Use a standard filter that meets UL900. Filter size is shown on the filter dimension figure on page 8. Consult the manufacturer for filter selection questions.
- Select a filter meeting UL900.
- Check the filter size against the filter dimension drawing.
Applies to: D5FUAA air handler
Source: Carrier D5FUAA crossover air handler product data, p. 8. Written in our own words; check the manual for your exact model.
Flammable (R454B / A2L) refrigerant precautions
Air handler · D5FUAA
This unit uses a mildly flammable refrigerant (R454B, classed A2L). Refrigerant may have no odor. Do not use open flames or gas appliances in the same space as a leak. Joints must be tested with detection equipment rated for leaks of 5 g/year or better. Keep pipe work short and protected from damage, and keep mechanical joints accessible. Do not use means other than the manufacturer's to speed defrost or to clean. Store the unit in a ventilated room with no continuous ignition sources.
- Keep pipe work to a minimum and protect it from physical damage.
- Make mechanical joints accessible for service.
- Test joints with leak detection rated 5 g/year or better after installation.
- Do not use open flames or other ignition sources where the unit is stored or serviced.
- Do not pierce or burn refrigerant lines or components.
Applies to: R454B refrigerant systems (37MURAQ / 37MUHAQ outdoor pairings)
Source: D5FUAA installation instructions, p. 3, p. 8, p. 9. Written in our own words; check the manual for your exact model.
Flammable refrigerant handling
Air handler · D5FUAA
The unit uses a flammable refrigerant. Only trained service personnel should repair it. Do not puncture refrigerant tubing. Do not use means to speed defrost or clean other than those the manufacturer recommends. Store the unit in a room without continuously operating ignition sources. Refrigerant may have no odor.
- Do not puncture refrigerant tubing.
- Use only manufacturer-recommended methods to defrost or clean.
- Store the unit away from open flames, operating gas appliances and operating electric heaters.
- Treat any leak as a fire risk if it meets an ignition source.
Applies to: D5FUAA refrigerant circuit
Source: Carrier D5FUAA crossover air handler product data, p. 3. Written in our own words; check the manual for your exact model.
Flammable refrigerant R454B service requirements
Air handler · D5FSAA / D5FLAA
This system uses R454B, a mildly flammable refrigerant. Room area and maximum charge limits apply. Technicians must hold current refrigerant handling certification.
- Check the room area against the minimum area table before charging.
- Use only the detection and work practices allowed for flammable refrigerants.
- Do not use naked flames to find leaks.
- Keep ignition sources away while refrigerant is handled or the piping is opened.
Applies to: Units using R454B refrigerant
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 4. Written in our own words; check the manual for your exact model.
Flammable refrigerant service rules
Air handler · D5FULA
Only technicians with a current valid refrigerant handling certificate may work on or open the refrigerant circuit. Joints must be leak tested with detection equipment rated at 5 g/year or better. Detachable joints are not allowed on the indoor side; brazed or welded joints are used there. Do not accelerate defrost or clean by means other than the manufacturer's, and do not pierce or burn the refrigerant circuit.
- Confirm the technician holds a current refrigerant handling certificate.
- Leak test all joints with detection equipment rated 5 g/year or better.
- Use only brazed or welded joints on the indoor side.
- Do not pierce or burn any part of the refrigerant circuit.
- Store the unit in a room with no open flames or running gas or electric heaters.
Applies to: R454B / A2L indoor coil
Source: D5FULA installation instructions, p. 8-9. Written in our own words; check the manual for your exact model.
Flammable refrigerant warning symbols
Air handler · D5FSAAH / D5FLAAH
The unit labels use three symbols: a warning for flammable refrigerant, a read-the-manual caution, and a service-personnel-only caution. Table 3 in the manual lists these labels.
- Check the unit labels for the flammable refrigerant warning before opening the refrigerant circuit.
- Refer to the installation manual for any work done by service personnel.
Applies to: Indoor and outdoor units
Source: Carrier D5FS(L)AAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.
Flammable refrigerant: ignition sources and leak detection
Air handler · D5FUHA
The unit uses a flammable refrigerant. Keep ignition sources away during work. Never use a halide torch or any naked flame to find leaks. Use leak detection suitable for flammable refrigerants, calibrated in a refrigerant-free area, and set at 25% of LFL maximum. Leak detection fluids must not contain chlorine detergents.
- Check the area with a suitable refrigerant detector before and during work.
- Remove or extinguish all naked flames if a leak is suspected.
- Do not use a halide torch or naked flame to detect leaks.
- Use bubble or fluorescent leak fluid without chlorine detergents, or an electronic detector calibrated for the refrigerant.
Applies to: Refrigerant circuit work on flammable refrigerant units
Source: Carrier D5FUHA service manual, p. 6. Written in our own words; check the manual for your exact model.
Flammable refrigerant: unventilated areas and duct-connected installs
Air handler · D5FSAA / D5FLAA
Limits for rooms with A2L refrigerant and duct-connected units.
- If the room is smaller than the required minimum area, keep open flames and other potential ignition sources out of it.
- Do not install auxiliary devices that could be ignition sources inside the ductwork. Only use heater kits approved by the manufacturer.
- Ceilings may be used as a return air plenum only if a refrigerant detection system is installed and a sensor sits just below the plenum duct joint.
- Replace refrigerant sensors only with sensors specified by the manufacturer.
- Keep the leak detection system installed and the unit powered except during service.
Applies to: Duct-connected units using A2L refrigerant
Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 10. Written in our own words; check the manual for your exact model.
FORCED COOL mode
Air handler · D5FS(L)AAH
Operation light flashes. The unit cools at high fan for 30 minutes, then switches to AUTO. The remote is disabled during this time.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Fuse replacement on indoor board
Air handler · D5FUHA
Only the blast-proof ceramic fuse is permitted for the control board.
- Check the fuse rating printed on the circuit board before replacing.
- Use only a blast-proof ceramic fuse of the printed rating.
Applies to: D5FUHA indoor control board
Source: D5FUHA service manual, p. 2. Written in our own words; check the manual for your exact model.
Guide specification requirements for installation
Air handler · D5FSAA
Key requirements from the guide specification that affect install and commissioning.
- Connect the indoor unit to the outdoor unit with refrigerant lines and wiring only; both refrigerant lines must be insulated.
- Confirm the indoor fan supply is 208-230 V single phase, per the electrical requirements.
- Check the unit has its refrigerant leak detection sensor in place and working.
- Set the fan speed to high, medium, low or automatic as needed; the motor is 4-speed.
- Confirm the auto restart after power failure and the 24-hour timer are set to the job requirements if the thermostat or controller uses them.
- Use the wired remote controller or a third-party thermostat with dehumidification only where that option is available.
Applies to: D5FSAA vertical air handler, sizes 1.5 to 5 ton
Source: D5FSAA product data, p. 30. Written in our own words; check the manual for your exact model.
Heat exchanger dust removal
Air handler · D5FS(L)AAH
After the unit turns off, there is a 10-second delay, then the outdoor fan runs in reverse for 70 seconds to blow loose dust off the outdoor coil.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Heat exchanger temperature limit with R454B sensor
Air handler · D5FULA
When a gas furnace is used for heating, the heat exchanger must stay under the temperature limit or the refrigerant leak sensor may fail. The exact temperature value is garbled in the source text and must be checked in the manual.
- Confirm the furnace heat exchanger temperature stays below the limit printed in the manual before commissioning.
Applies to: D5FULA with gas furnace and R454B leak sensor
Source: Carrier D5FULA installation instructions, p. 22. Written in our own words; check the manual for your exact model.
Heat pump changeover and high temperature protection
Air handler · D5FUAA
In heat pump mode the unit changes automatically between heating and cooling, with a deadband to stop rapid cycling. Indoor coil high temperature protection detects excessive discharge temperature while in heat pump mode.
Applies to: D5FUAA crossover air handler
Source: D5FUAA product data, p. 25. Written in our own words; check the manual for your exact model.
Heating fan start delay
Air handler · D5FS(L)AAH
In HEAT mode the indoor fan starts only after the coil has warmed up, to prevent cold blow.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Humidifier connection through the WORK output (CN23)
Air handler · D5FUHA
The WORK output is tied to the fan. Its relay closes whenever the fan runs, which lets power reach the humidifier when the humidistat calls for humidity. The humidistat and humidifier are wired as shown in the diagram with the R and C wires.
- Wire the humidistat and humidifier per the wiring diagram, using CN23 and the R and C terminals.
- If the thermostat has a HUM terminal, connect the humidifier directly to HUM and C instead.
Applies to: D5FUHA with humidifier
Source: Carrier D5FUHA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Humidifier control (CN23)
Air handler · D5FUAA
Dry contact WORK output on CN23 with R and C wires drives the humidistat and humidifier. The CN23 relay closes when the fan runs.
- Wire the humidistat and humidifier per the wiring diagram.
- Use the R and C wires on the controller with CN23.
Applies to: D5FUAA indoor unit
Source: D5FUAA installation instructions, p. 25. Written in our own words; check the manual for your exact model.
Ignition source controls on site
Air handler · D5FULA
Before breaking into the system, survey the area for flammable hazards. Keep all ignition sources away, including smoking. Use no halide torch or open flame for leak checks. Leak detection fluids must not contain chlorine detergents.
- Post no smoking signs.
- Use only a leak detector that is not an ignition source.
- Use leak detection fluid without chlorine-based detergents.
- Have a dry powder or CO2 extinguisher at the charging area for any hot work.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 6. Written in our own words; check the manual for your exact model.
Indoor display panel and IR receiver
Air handler · D5FS(L)AAH
The display panel sits inside the control box and works as an infrared receiver for the remote, used by the installer to set airflow. If the remote is lost or out of batteries, the unit can be run from the display panel buttons, as described in the general section.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Indoor unit cleaning and filter care
Air handler · D5FUAAH
Routine care of the indoor unit. Turn the unit off and disconnect power before cleaning.
- Inspect and clean or replace the air filter each month or as required.
- The user must buy a standard filter that meets UL900 requirements.
- Wipe the unit with a soft, dry cloth. Use a damp cloth with warm water for heavy dirt.
- Do not use chemicals, benzene, paint thinner, polishing powder or other solvents.
- Do not use water hotter than 104°F (40°C) on the front panel.
- Do not wash the unit under running water or use excessive water.
- Check that the drain hose is set up according to the instructions.
- If a fuse blows, replace it with an identical fuse only.
Applies to: D5FUAAH air handler
Source: D5FUAAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Indoor unit diagnostics and protection (spec summary)
Air handler · D5FSAA
The indoor unit runs self diagnostics and shows error messages on the unit. It also protects the indoor coil against freeze-up and high discharge temperature in heat pump mode.
- When an error appears on the unit, note the code and check the fault code table for the unit.
- If the indoor coil freezes or runs too hot in heat pump mode, check airflow and filters first.
- If the cause is not clear, check the refrigerant leak sensor and unit wiring before further repairs.
Applies to: D5FSAA all sizes
Source: D5FSAA product data, p. 30. Written in our own words; check the manual for your exact model.
Indoor unit supply voltage connections
Air handler · D5FUHA
The board detects input voltage automatically. For 208 V or 230 V, connect L1 and L2. For 115 V, connect L1 and L2, where L2 is used as N.
- Connect L1 and L2 for 208 V or 230 V supply.
- For 115 V supply, connect L1 and L2 with L2 used as neutral.
- Use u-lugs or ring terminals on stranded wire.
- Ground the unit according to local codes.
Applies to: D5FUHA indoor unit
Source: D5FUHA Installation Instructions, p. 34. Written in our own words; check the manual for your exact model.
Installation height and room area for refrigerant leak safety
Air handler · D5FUAAH
Air duct outlet height and room size limits apply to systems using a mildly flammable refrigerant.
- Keep the bottom of the duct air outlet in the room above 7.3 ft (2.2 m) from the floor.
- Keep total refrigerant charge within the maximum allowed for the room size served.
- Keep ventilation openings clear of obstructions.
Applies to: D5FUAAH with R454B refrigerant
Source: D5FUAAH Owner's Manual, p. 3-4. Written in our own words; check the manual for your exact model.
Isolate electrical supply before servicing
Air handler · D5FUHA
Main electrical disconnect must be OFF before installing, modifying or servicing. There may be more than one disconnect. Lock out and tag each one.
- Switch off the main electrical disconnect.
- Check for additional disconnects and switch those off too.
- Lock out and tag every disconnect with a warning label.
Applies to: All D5FUHA indoor units
Source: Carrier D5FUHA service manual, p. 1. Written in our own words; check the manual for your exact model.
Jumper removal for ON-OFF and water level switch functions
Air handler · D5FUHA
Two short connectors on the board are removed to enable optional functions.
- For the ON-OFF function, remove the short connector on JR1.
- For the water level switch function, remove the short connector on J7.
Applies to: D5FUHA indoor unit main board
Source: D5FUHA Product Data, p. 26. Written in our own words; check the manual for your exact model.
Keep drain pipe and line set from stressing the unit
Air handler · D5FUAA
Avoid drain and line damage during install.
- Do not pull the drain pipe forcefully; it can disconnect.
- Insulate all piping to prevent condensation damage.
- Install drain traps on horizontal runs ahead of the run to prevent air trapping.
Applies to: D5FUAA drain and refrigerant piping
Source: D5FUAA installation instructions, p. 38. Written in our own words; check the manual for your exact model.
Keep heaters clear of combustibles
Air handler · D5FUHA
For units with an auxiliary electric heater, keep the unit at least 1 m (3 ft) from combustible materials.
- Measure clearance from the unit to combustible materials.
- Keep at least 1 m (3 ft) clear.
Applies to: Units with auxiliary electric heater
Source: Carrier D5FUHA installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Keep tubing bends within limits
Air handler · D5FUAA
Bend tubing only with a properly sized bender. Do not bend the tubing more than 90 degrees or more than 3 times. Use the minimum bend radius shown in the figure.
Applies to: D5FUAA copper tubing
Source: D5FUAA installation instructions, p. 40. Written in our own words; check the manual for your exact model.
Leak detection sensor wiring and fan response
Air handler · D5FULA
Field wiring for the refrigerant leak detection system must meet the minimum wire rules.
- Use critical-to-safety wiring of at least 18 AWG with insulation at least 1.58 mm thick, or protect it from damage.
- Check that the connected inductive electrical load does not exceed the limit calculated from the switched load (Le) formula in the manual.
- Confirm that a leak detection event turns the indoor fan on at the highest speed or at no less than minimum airflow (Qhmin).
Applies to: D5FULA
Source: D5FULA installation instructions, p. 27. Written in our own words; check the manual for your exact model.
Leak detection system must stay powered
Air handler · D5FUAA
Where the unit depends on a leak detection system for mitigation, it must stay powered except during service. Any remote refrigerant sensor must carry the same marking or instructions.
- Keep the unit powered except during service.
- Replace refrigerant sensors only with sensors specified by the manufacturer.
- Verify mitigation actions activate after any sensor replacement.
Applies to: Units with refrigerant detection
Source: D5FUAA installation instructions, p. 8. Written in our own words; check the manual for your exact model.
Leak detection system power
Air handler · D5FUHA
Units with a leak detection system used for leak mitigation must stay powered except during service.
- Keep the unit powered except when servicing.
- Replace refrigerant sensors only with sensors specified by the manufacturer.
Applies to: Flammable refrigerant units with leak detection
Source: Carrier D5FUHA installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Leak mitigation sensor
Air handler · D5FUAA
The unit has a leak mitigation system. The leak sensor does not need re-orientation for different install positions.
Applies to: D5FUAA air handler
Source: Carrier D5FUAA crossover air handler product data, p. 4. Written in our own words; check the manual for your exact model.
LED display behavior
Air handler · D5FUAA
Normally shows the temperature setpoint. When a fault is active, the display flashes the fault code. Fault code details are in the troubleshooting section.
- Check the LED display for a flashing fault code.
- Refer to the troubleshooting fault code table for the code meaning.
Applies to: D5FUAA indoor unit
Source: D5FUAA installation instructions, p. 25. Written in our own words; check the manual for your exact model.
LED display behaviour
Air handler · D5FUHA
Normally the LED shows the current temperature setpoint. When a fault is active, it flashes the fault code quickly. The fault code table is in the troubleshooting section, not on these pages.
- If the display shows a setpoint, the unit is running normally.
- If the display flashes a code, look it up in the troubleshooting section's fault code table.
Applies to: D5FUHA with LED display
Source: Carrier D5FUHA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Location restrictions
Air handler · D5FUAA
Do not install in areas with oil drilling or fracking, coastal salt air, caustic or corrosive gases, hot-spring gases, power fluctuations (such as factories), enclosed cabinets, strong electromagnetic fields, or where flammable materials or gas are stored. Avoid high-humidity rooms such as bathrooms and laundry rooms. Keep the unit at least 3 ft (1 m) from TVs and radios. Keep units with auxiliary electric heat at least 3 ft (1 m) from combustible materials.
- Pick a location that meets all listed restrictions.
- Keep the cables and unit at least 3-1/5 ft (1 m) from televisions and radios.
- Keep units with auxiliary heat 3 ft (1 m) from combustibles.
Applies to: Indoor unit site selection
Source: D5FUAA installation instructions, p. 8, p. 14, p. 15. Written in our own words; check the manual for your exact model.
Main board jumpers and dip switch notes
Air handler · D5FUHA
Wiring diagram notes for the indoor main control board. Jumper and switch changes are only made for specific functions.
- Remove the short connector on JR1 when using the ON-OFF function.
- Remove the short connector on J7 when using the water-level switch function.
- Leave the other dip switches at their default OFF setting unless the manual calls for a change.
- Refer to the installation manual for the use of each dip switch.
- Power must be off before changing the ENC1 capacity dip switch.
Applies to: D5FUHA indoor main control board
Source: D5FUHA installation instruction, p. 31. Written in our own words; check the manual for your exact model.
Meaning of unit symbols
Air handler · D5FULA
Symbols on the indoor or outdoor unit mean: flammable refrigerant is used (risk of fire if leaked and ignited); read the operation manual; service personnel must handle the equipment with the installation manual; information is available in the operating or installation manual.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 3. Written in our own words; check the manual for your exact model.
Metering devices
Air handler · DLFULA
The outdoor unit uses an electronic metering device (EEV) in heating. The indoor evaporator coil uses a TXV in cooling.
Applies to: DLFULA evaporator coil with outdoor unit
Source: DLFULA product data, p. 7. Written in our own words; check the manual for your exact model.
Minimum line length and suction line insulation
Air handler · D5FSAA, D5FLAA
Minimum refrigerant line length between indoor and outdoor units is 10 ft (3 m). The suction line must be insulated.
- Keep the line set at or above 10 ft (3 m).
- Insulate the suction line.
- Check the outdoor unit manual for allowed length and height difference.
Applies to: D5FSAA / D5FLAA with matching outdoor unit
Source: Carrier D5FSAA/D5FLAA installation manual, p. 24. Written in our own words; check the manual for your exact model.
Model number breakdown
Air handler · D5FUHA
D5 is the indoor unit, FU is unitary, H is air handler, Q is heat pump, 24/36/60 is nominal capacity (2, 3 or 5 ton), A is crossover, X is indoor unit, and K is 208/230-1-60 voltage (can be configured for 115 V).
Applies to: D5FUHA
Source: D5FUHA product data, p. 3. Written in our own words; check the manual for your exact model.
OFF mode controller
Air handler · D5FS(L)AAH
When the controller is turned off, the unit turns off and stays off until the controller is turned back on.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Operating mode priority
Air handler · D5FUAAH
The unit has five modes: FAN Only, AUTO, HEATING (heat pumps only), COOLING, and DEHUMIDIFICATION (DRY). HEATING has priority, and simultaneous heating and cooling is not allowed. DRY dehumidifies but does not replace a dehumidifier.
Applies to: D5FUAAH
Source: D5FUAAH Owner's Manual, p. 2. Written in our own words; check the manual for your exact model.
Outdoor unit power below freezing
Air handler · D5FUHAQ
Units with an auxiliary electric heater on the outdoor unit need protection in cold weather.
- When outdoor temperature is below 0°C (32°F), keep the outdoor unit powered at all times to prevent equipment damage.
Applies to: Outdoor units with auxiliary electric heater
Source: D5FUHAQ Owner's Manual, p. 7. Written in our own words; check the manual for your exact model.
Outdoor-to-indoor signal wire
Air handler · D5FULA
Signal wire choice for communication between the indoor and outdoor units.
- Use shielded 16 AWG wire for the outdoor/indoor signal wire to reduce noise, especially in high EMF areas.
- Use the gauge shown in Fig. 24 for the signal wire line.
Applies to: D5FULA
Source: D5FULA installation instructions, p. 28. Written in our own words; check the manual for your exact model.
Parts, access and qualified service
Air handler · D5FUAA
Who may service the unit and which parts may be fitted.
- Only trained, qualified installers and service technicians should install, start up and service the unit.
- Use only the included accessories and manufacturer-specified parts.
- On units with wireless network function, USB device access and replacement must be done by professional staff.
- Relocating the unit requires experienced service technicians to disconnect and reinstall it.
Applies to: All service work
Source: D5FUAA Installation Instructions, p. 2. Written in our own words; check the manual for your exact model.
Piping joints and burial limits
Air handler · D5FUHA
Only brazed or welded joints may be used on the indoor side. Detachable joints are not allowed there. Do not bury more than 36 in. (914 mm) of refrigerant pipe. Any buried section must rise 6 in. (152 mm) vertically to the outdoor valve connections. Pipe runs must be kept as short as practical and protected from physical damage.
- Use only brazed or welded joints on the indoor side.
- Limit buried refrigerant pipe to 36 in. (914 mm).
- Provide a 6 in. (152 mm) vertical rise to the outdoor valves from any buried section.
- Make sure mechanical connections are accessible for service.
Applies to: Field refrigerant piping
Source: D5FUHA Installation Instructions, p. 2 and p. 6. Written in our own words; check the manual for your exact model.
Power and disconnect requirements
Air handler · D5FSAA
Main power is supplied to the outdoor unit. Disconnecting the outdoor unit also removes power from the indoor unit. A separate disconnect may be required for the indoor unit, and the auxiliary heater needs its own power.
- Size the wires and disconnect using outdoor unit MCA and MOCP.
- Provide a disconnect within sight and readily accessible from the system.
- Provide separate power for any auxiliary electric heater.
Applies to: Electrical installation
Source: D5FSAA Product Data, p. 11. Written in our own words; check the manual for your exact model.
Power wiring for 115 V and 208/230 V
Air handler · D5FUHA
Terminal block wiring depends on supply voltage.
- For 208 V or 230 V supply, connect L1 and L2.
- For 115 V supply, connect L1 and L2, with L2 used as neutral (N).
- Use only the specified wire and make sure the product is grounded.
- Clamp cables securely and make sure the control board cover closes properly.
Applies to: D5FUHA main board power input
Source: D5FUHA installation instruction, p. 31, 2. Written in our own words; check the manual for your exact model.
Purging and breaking vacuum on flammable refrigerant systems
Air handler · D5FUAA
Purging rules for systems with flammable refrigerant.
- Never use compressed air or oxygen to purge the system.
- Break the vacuum with oxygen-free nitrogen and fill to working pressure, then vent to atmosphere.
- Repeat until no refrigerant remains in the system.
- Vent the final nitrogen charge to atmospheric pressure before work starts.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
Applies to: Flammable refrigerant systems
Source: D5FUAA Installation Instructions, p. 6. Written in our own words; check the manual for your exact model.
Purging with oxygen-free nitrogen
Air handler · D5FUHA
Compressed air and oxygen must never be used to purge the system. Purge with oxygen-free nitrogen by breaking vacuum, filling to working pressure, venting to atmosphere, then pulling down to vacuum. Repeat until no refrigerant remains. Vent to atmospheric pressure before opening the circuit.
- Break the vacuum with oxygen-free nitrogen and fill to working pressure.
- Vent to atmosphere.
- Pull down to vacuum again.
- Repeat until no refrigerant remains.
- Vent to atmospheric pressure before work starts.
Applies to: Flammable refrigerant systems
Source: Carrier D5FUHA service manual, p. 6. Written in our own words; check the manual for your exact model.
Qualification for refrigerant circuit work
Air handler · D5FUHA
Only persons with a current valid certificate from an accredited assessment authority may work on or open a refrigerant circuit. Other skilled helpers must work under the supervision of a competent person.
- Confirm the technician holds a current valid refrigerant handling certificate.
- Have helpers work under supervision of a competent person.
Applies to: Refrigerant circuit service
Source: Carrier D5FUHA service manual, p. 4 and p. 5. Written in our own words; check the manual for your exact model.
Recommended spacing between mounted indoor units
Air handler · D5FSAA / D5FLAA
Spacing between units is shown in figures 9 and 10 (horizontal and vertical).
- Mount the indoor unit so the spacing matches the horizontal (Fig. 9) or vertical (Fig. 10) drawing on page 16.
- Use the figure dimensions; the numbers are not printed in the text.
Applies to: Indoor air handler
Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 16. Written in our own words; check the manual for your exact model.
Record every INQUIRY and SERVICE change
Air handler · D5FUHA
The remote and indoor unit do not display changed values after exit, and the code shows its default (0) on the next entry. Without a written record, the current setting cannot be confirmed.
- Write down each code number and the value set during the visit.
- If the previous value is unknown, press DOWN to the maximum change range of -6, then press UP back to 0, and set the new value.
- Keep the record with the job documents.
Applies to: D5FUHA remote controller
Source: D5FUHA installation instruction manual, p. 49. Written in our own words; check the manual for your exact model.
Recovery cylinder and refrigerant handling limits
Air handler · D5FULA
Recovery cylinders must be designated for the recovered refrigerant and labeled for it. Do not fill over 80 percent of liquid volume or exceed cylinder maximum pressure. Do not mix refrigerants. Do not recharge recovered refrigerant unless it has been cleaned and checked.
- Confirm the cylinder has a pressure-relief valve and working shut-off valves.
- Weigh the cylinder on calibrated scales during recovery.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 7. Written in our own words; check the manual for your exact model.
Recovery cylinder filling limits
Air handler · D5FUHA
Do not fill recovery cylinders above 80% of volume by liquid, and never exceed the cylinder's maximum working pressure, even briefly. Do not mix refrigerants in recovery units or cylinders. Recovered refrigerant must not be recharged into another system unless cleaned and checked.
- Fill cylinders to no more than 80% liquid volume.
- Keep cylinder pressure below its maximum working pressure.
- Do not mix refrigerants.
- Do not recharge recovered refrigerant unless it has been cleaned and checked.
Applies to: Refrigerant recovery
Source: Carrier D5FUHA service manual, p. 7. Written in our own words; check the manual for your exact model.
Refrigerant detection sensor access and replacement
Air handler · D5FULA
The R454B refrigerant detection sensor sits in the unit near the coil. The removable cover plate gives access for inspection and repair. Only sensors specified by the manufacturer may be used, and the unit must stay powered except for service.
- Turn off power before removing the cover plate.
- Remove the removable cover plate for inspection and repair.
- Check the T2 sensor wire and the R454B sensor wire are connected.
- Replace the sensor only with a manufacturer-specified part.
- Keep the unit powered except during service.
Applies to: D5FULA indoor coil
Source: D5FULA installation instructions, p. 8, 15-16. Written in our own words; check the manual for your exact model.
Refrigerant joint leak testing
Air handler · D5FSAA / D5FLAA
Joints must be tested with detection equipment rated to find 5 g/year of refrigerant or better, with the system at standstill and under operation or pressure. Detachable joints are not allowed on the indoor side. Brazed or welded joints are allowed.
- Test all joints with a detector rated 5 g/year or better after installation.
- Do not use detachable joints on the indoor unit side.
- Use brazed or welded joints on the indoor side.
Applies to: Refrigerant piping joints
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 5. Written in our own words; check the manual for your exact model.
Refrigerant line burial limits
Air handler · D5FULA
Refrigerant pipe must not be buried more than 36 in. If any section is buried, the line must rise at least 6 in to the outdoor unit valve connections. Too much buried line can let refrigerant move into the cold section and cause slugging or compressor damage at startup.
- Keep buried sections within 36 in.
- Provide a 6 in vertical rise to the outdoor valve connections for any buried section.
Applies to: D5FULA refrigerant line runs
Source: Carrier D5FULA installation instructions, p. 23. Written in our own words; check the manual for your exact model.
Refrigerant piping buried underground
Air handler · D5FUAA
Limits for buried refrigerant pipe.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
- Buried pipe that is too long can let refrigerant migrate and cause slugging and compressor damage at startup.
Applies to: Refrigerant piping installation
Source: D5FUAA Installation Instructions, p. 2. Written in our own words; check the manual for your exact model.
Refrigerant safety during piping work
Air handler · D5FSAA, D5FLAA
Refrigerant leaks can cause oxygen-deficiency hazards in small rooms. Contamination from air, dust, moisture or foreign material can reduce capacity, raise high-side pressure, and cause explosion or injury.
- If the system is in a small room, take steps so refrigerant concentration cannot exceed the safety limit during a leak.
- Keep air, dust, moisture and foreign material out of the refrigerant circuit during installation.
- Ventilate the area right away if a refrigerant leak happens during installation.
- Confirm there are no leaks after the installation is complete.
- All field piping must be done by a licensed technician to local and national code.
Applies to: D5FSAA / D5FLAA with R-410A style line set
Source: Carrier D5FSAA/D5FLAA installation manual, p. 24. Written in our own words; check the manual for your exact model.
Refrigerant tubing and replacement parts
Air handler · D5FUHAQ
Safety reminders for field work on the refrigerant side.
- Do not puncture refrigerant tubing.
- Use only manufacturer-approved accessories and replacement parts, or the warranty and safety may be affected.
- Have a qualified installer or service agency make any modifications using factory-authorized kits or accessories.
Applies to: D5FUHAQ units
Source: D5FUHAQ Owner's Manual, p. 2. Written in our own words; check the manual for your exact model.
Remote battery care
Air handler · D5FUAAH
Battery type and replacement rules for the wireless remote.
- Use two AAA 1.5V alkaline batteries. Do not mix old and new or different battery types.
- Average battery life under normal use is about 6 months.
- Replace batteries when the indoor unit no longer gives an audible beep or the Transmission Indicator fails to light.
- Remove the batteries if the remote will not be used for several weeks, to avoid leakage damage.
- Follow the polarity marks inside the battery compartment.
Applies to: Wireless remote RG10F8(2)/BGEFU1
Source: D5FUAAH Owner's Manual, p. 11. Written in our own words; check the manual for your exact model.
Remote battery type and life
Air handler · D5FUH
The remote uses two AAA 1.5 V alkaline batteries. Average life is about 6 months. Remove the batteries if the remote will not be used for several weeks to avoid leakage damage.
- Use two new AAA 1.5 V alkaline batteries, matching the polarity marks.
- Do not mix old and new batteries or different battery types.
- Remove the batteries if the remote will be unused for several weeks.
- Replace the batteries when the unit does not beep on command or the transmission indicator fails to light.
Applies to: Wireless remote
Source: Carrier D5FUHAQ owner's manual, p. 11. Written in our own words; check the manual for your exact model.
Remote condensate overflow switch
Air handler · D5FUHA
The unit accepts a field-supplied condensate overflow switch. When it is used, the overflow device must open its contact during an overflow so the unit switches off.
- Remove jumper J1.
- Connect the installer-supplied condensate overflow device to CN5 as shown in the wiring figure.
- Check that the device opens its contact during an overflow condition so the system turns off.
Applies to: All D5FUHA units with a field overflow switch
Source: Carrier D5FUHA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Remote control range and placement
Air handler · D5FUH
The remote works up to about 26 ft (8 m) with no obstructions. Point it toward the right side of the indoor unit when sending commands. With the timer in use, keep the remote within about 26 ft of the fan coil.
- Point the remote at the right side of the indoor unit.
- Keep the remote within 26 ft (8 m) with no obstructions.
- Keep the remote within this range when timer functions are used.
Applies to: Wireless remote
Source: Carrier D5FUHAQ owner's manual, p. 11. Written in our own words; check the manual for your exact model.
Remote fault alarm output (CN33)
Air handler · D5FUHA
CN33 is a dry (passive) output and does not supply voltage itself, so the installer must provide a voltage signal. The relay is normally open during normal operation and closes when a fault is active.
- Wire the alarm device to CN33 and supply the required voltage from the installer side.
- Confirm the device reacts when a fault closes the relay.
Applies to: D5FUHA with alarm output used
Source: Carrier D5FUHA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Replace the control board fuse
Air handler · D5FULA
The control board has an overcurrent fuse with its rating printed on the board. Only a blast-proof ceramic fuse of the identical rating may be used.
- Turn off the unit and disconnect power.
- Read the fuse rating printed on the control board.
- Replace it only with an identical blast-proof ceramic fuse.
Applies to: D5FULA control board
Source: D5FULA installation instructions, p. 8-9. Written in our own words; check the manual for your exact model.
Replacement of control board fuse
Air handler · D5FSAA / D5FLAA
The control board has an overcurrent fuse. The fuse rating is printed on the board, for example T3.15AL/250VAC, T5AL/250VAC, T5A/250VAC or T10A/250VAC.
- Read the fuse rating printed on the circuit board before replacing it.
- Use only a blast-proof ceramic fuse.
- Replace the fuse only with an identical component.
Applies to: Indoor and outdoor control boards with fuse
Source: D5FSAAH / D5FLAAH Installation Instructions, p. 3 and p. 5. Written in our own words; check the manual for your exact model.
Replacing the circuit board fuse
Air handler · D5FUHA
Only a blast-proof ceramic fuse may be used. Match the rating printed on the circuit board.
- Check the fuse rating printed on the circuit board.
- Replace with an identical blast-proof ceramic fuse.
Applies to: Indoor and outdoor PCB overcurrent fuse
Source: Carrier D5FUHA installation instructions, p. 10. Written in our own words; check the manual for your exact model.
Return air and plenum sealing
Air handler · D5FUAA
There must be an airtight seal between the bottom of the air handler and the return air plenum. Return air must not be drawn from a room with a gas appliance, water heater or carbon monoxide-producing device such as a wood fireplace.
- Seal the plenum-to-cabinet joint with fiberglass sealing strips, foil duct tape, caulking or an equal method.
- Confirm return air is not drawn from a room that contains a gas or CO-producing appliance.
- Apply sealant where wires, refrigerant pipes and condensate pipes enter the cabinet.
- Seal drain line holes with duct tape or flexible sealant so warm air cannot enter.
Applies to: All installations with return air plenum
Source: D5FUAA installation instructions, p. 15, p. 16. Written in our own words; check the manual for your exact model.
Save energy with timers, closed doors and clear airflow
Air handler · D5FUH
Keep doors and windows closed, use the timer functions to limit run time, keep air inlets and outlets clear, and check the filter regularly.
- Keep doors and windows closed while cooling or heating.
- Use TIMER ON and TIMER OFF to limit run time.
- Do not block the air inlet or outlet and do not place objects near them.
- Inspect and clean the air filter regularly.
Applies to: All D5FUH crossover air handler sizes
Source: Carrier D5FUHAQ owner's manual, p. 8. Written in our own words; check the manual for your exact model.
Seal cabinet penetrations
Air handler · D5FUHA
Warm air must not enter through gaps around wires, refrigerant pipes, condensate pipes or drain lines.
- Apply sealant around wires, refrigerant pipes and condensate pipes where they enter the cabinet.
- Seal around drain line holes with duct tape or flexible sealant.
Applies to: Indoor cabinet
Source: Carrier D5FUHA installation instructions, p. 16. Written in our own words; check the manual for your exact model.
Sealed and intrinsically safe components
Air handler · D5FUHA
Sealed electrical components and intrinsically safe components must be replaced with parts specified by the manufacturer. Check that cabling is not worn, corroded, pinched, vibrating or sharp-edged. Only use manufacturer-approved parts.
- Replace sealed or intrinsically safe components only with manufacturer-specified parts.
- Inspect cabling for wear, corrosion, pressure, vibration and sharp edges.
- Use only manufacturer-approved replacement parts.
Applies to: Electrical and sealed component repair
Source: Carrier D5FUHA service manual, p. 3 and p. 6. Written in our own words; check the manual for your exact model.
Secondary drain pan over finished space
Air handler · D5FSAA, D5FLAA
A field-built secondary drain pan with a drain line to the outside is required over a finished living space or any area that overflow could damage. Some local codes require one for any horizontal install.
- Install a field-built secondary drain pan with a drain pipe to the outside where overflow could cause damage.
- Check local code for horizontal installs.
Applies to: D5FSAA / D5FLAA air handler
Source: Carrier D5FSAA/D5FLAA installation manual, p. 17. Written in our own words; check the manual for your exact model.
Sleep function behaviour
Air handler · D5FSAA
Sleep is available in cooling, heating, auto or heat pump plus electric heater modes. In cooling the set point rises 1.8°F (1°C) each hour up to 86°F (30°C), then holds after 2 hours with the indoor fan at low. In heating the set point drops 1.8°F (1°C) each hour down to 60.8°F (16°C), then holds after 2 hours with the fan at low. Anti-cold wind takes priority in heating.
- Select sleep with the remote and confirm the mode is cooling, heating, auto or heat pump plus electric heater.
- Expect the set point to step by 1.8°F (1°C) per hour for 2 hours, then hold.
- In auto mode, after 1 hour the set point moves 1.8°F (1°C) up for cooling or down for heating; in fan mode it does not change.
Applies to: D5FSAA
Source: Carrier D5FSAA product data, p. 4. Written in our own words; check the manual for your exact model.
Technician qualification for refrigerant work
Air handler · D5FULA
Anyone working on or opening a refrigerant circuit must hold a current certificate from an accredited assessment authority for safe refrigerant handling. Maintenance needing other skilled staff must be supervised by a competent person.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
Source: D5FULA installation instructions, p. 5. Written in our own words; check the manual for your exact model.
Three-minute protection
Air handler · D5FS(L)AAH
The unit will not restart for about 3 minutes after running and being restarted immediately.
Applies to: D5FS(L)AAH
Source: D5FS(L)AAH Owner's Manual, p. 20. Written in our own words; check the manual for your exact model.
Timer function (24-hour relative timer)
Air handler · D5FSAA
The timer covers 24 hours and uses relative time, not clock time. It can be set as Timer On, Timer Off, Timer On/Off or Timer Off/On. The timer does not change the running mode. If the unit is off when a timer-off is set, it stays off until the set time is reached.
- Select the timer type you need: On, Off, On/Off or Off/On.
- Set the time; it counts from the moment it is set, not from the clock.
- Expect the timer LED to switch off when the set time is reached, with the running mode unchanged.
Applies to: D5FSAA with wired or wireless remote
Source: Carrier D5FSAA product data, p. 4. Written in our own words; check the manual for your exact model.
Transport, marking and storage of flammable refrigerant units
Air handler · D5FSAA / D5FLAA
Handling rules for units with flammable refrigerant.
- Follow transport rules for flammable gas equipment; the number of units that can ship together is set by those rules.
- Follow local rules for signs and safety labels in work areas.
- Store the unit according to the strictest applicable rule.
- Make sure packed units are protected so damage cannot cause a refrigerant leak.
Applies to: Units with flammable refrigerant
Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 10. Written in our own words; check the manual for your exact model.
Troubleshooting after failed test run
Air handler · D5FULA
If the unit malfunctions or does not run as expected during the test, consult the Troubleshooting section of the Service Manual before contacting customer service.
- Refer to the Service Manual Troubleshooting section before calling customer service.
Applies to: D5FULA test run
Source: D5FULA Installation Instructions, p. 33. Written in our own words; check the manual for your exact model.
Unit element abbreviations
Air handler · D5FSAA
Reference list of the abbreviations used for temperatures and setpoints.
- T1: indoor room temperature.
- T2: evaporator coil temperature.
- T3: condenser coil temperature.
- T4: outdoor ambient temperature.
- TP: compressor discharge temperature.
- TS: setting temperature.
- Tsc: adjusted setting temperature.
Applies to: D5FSAA
Source: Carrier D5FSAA product data, p. 2. Written in our own words; check the manual for your exact model.
Unit selection for sensible loads
Air handler · DLFULA
Select equipment that matches or slightly exceeds the anticipated peak load. For high sensible load spaces, base the selection on sensible load and adjust for room wet bulb temperature so the equipment is not undersized.
- Match or slightly exceed the peak load.
- For high sensible load spaces, size on sensible load and adjust for room wet bulb temperature.
Applies to: DLFULA evaporator coil
Source: DLFULA product data, p. 7. Written in our own words; check the manual for your exact model.
Use only approved parts and accessories
Air handler · D5FULA
Only the accessories and replacement parts specified by the manufacturer may be used. Non-approved parts can cause leaks, shock, fire and failure, and can void the warranty.
Applies to: D5FULA crossover evaporator coil, sizes 24K - 60K
Source: D5FULA installation instructions, p. 3, 8. Written in our own words; check the manual for your exact model.
UV, fresh air or ion generator on the WORK output
Air handler · D5FUHA
The WORK output follows the fan. The accessory only runs while the fan runs.
- Wire the UV lamp, fresh air damper or ion generator to the WORK output as shown in the accessory wiring figure.
Applies to: D5FUHA with UV, fresh air or ion accessory
Source: Carrier D5FUHA installation instructions, p. 42. Written in our own words; check the manual for your exact model.
Wire and line routing
Air handler · D5FUAA
Keep control wiring separate from refrigerant piping.
- Bundle power cable, signal cable and piping with binding tape only after the copper pipes are connected to the outdoor unit.
- Do not intertwine or cross the signal cable with other wiring.
Applies to: D5FUAA field wiring with line set
Source: D5FUAA installation instructions, p. 40. Written in our own words; check the manual for your exact model.
Wired controller options and limits
Air handler · D5FUAA
KSACN1401AAA and KSACN1701BAA wired controllers are sold separately. The wired controller and a 24 V thermostat cannot be used at the same time. Do not connect power to the communication line; this can damage the system.
- Refer to the wiring template for the chosen controller's wiring method.
- Do not run the 24 V thermostat and the wired controller together.
- Do not connect line power to the communication line.
Applies to: D5FUAA with KSACN1401AAA or KSACN1701BAA wired controller
Source: D5FUAA Crossover Air Handler product data, p. 11. Written in our own words; check the manual for your exact model.
Wiring order and separation
Air handler · D5FUHA
Connect outdoor wires before indoor wires. Keep power and signal wiring separated and do not cross them.
- Connect the outdoor unit wires first, then the indoor wires.
- Keep power supply leads away from communication leads.
- Use strain relief and clamp cables so they do not pull on the terminals.
- Insulate any unused wires with electrical tape.
Applies to: D5FUHA system wiring
Source: D5FUHA Installation Instructions, pp. 33-34. Written in our own words; check the manual for your exact model.
Wiring precautions before connecting power
Air handler · D5FULA
Key electrical rules from the wiring section. Power to the unit must be off before any wiring.
- Turn off main power and lock out the disconnect before any wiring work.
- Connect the outdoor unit wires before the indoor wires.
- Use copper wire only and keep power leads separate from communication leads.
- Keep power supply within 90-110% of rated voltage.
- Use a branch circuit dedicated to this unit; do not share the outlet.
- Use a disconnect or breaker with at least 1/8 in (3 mm) contact separation on all poles.
- Ground the unit properly and tighten every connection.
- Keep wires away from refrigerant tubing, compressor and moving parts.
- Do not cross power wiring with signal wiring.
- Wait 10 minutes after power-off before touching electrical components.
- Do not connect 24 VAC to S1-S2; this will damage the system.
Applies to: D5FULA
Source: D5FULA installation instructions, p. 27. Written in our own words; check the manual for your exact model.
Approved parts only
Heat pump · D5CURA
Only manufacturer-approved accessories and replacement parts may be used. Non-approved parts can void the warranty and cause fire or failure.
- Use only manufacturer-approved accessories and replacement parts.
Applies to: All units
Source: D5CURA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Auxiliary electric heater clearance
Heat pump · D5CURA
Units with an auxiliary electric heater must not be installed within 3 ft (1 m) of combustible materials.
- Keep at least 3 ft (1 m) from combustible materials.
Applies to: Units with auxiliary electric heater
Source: D5CURA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Bending and routing refrigerant pipe
Heat pump · D5CURA
Limits for bending and routing so the pipe is not damaged and the signal cable is not disturbed.
- Do not bend the tubing more than 90° or more than three times.
- Keep the minimum bend radius of 3.9 in (100 mm).
- Do not kink the pipe. Use a proper tubing bender.
- Keep the branch pipe horizontal. An angle over 10° can cause a fault.
- Insulate the liquid line to prevent condensation.
- Wrap insulation around the piping to avoid burns or frostbite.
- Do not cross or intertwine the signal cable with other wiring.
Applies to: Field refrigerant and wiring runs
Source: Carrier D5CURA installation manual, p. 13-14. Written in our own words; check the manual for your exact model.
Built-in protections and delays
Heat pump · D5CURA
The unit has a 3 minute compressor time delay, a 46°F heating setback, auto restart, auto changeover, low voltage and overload protection, compressor over current protection, high discharge temperature protection, and IPM module protection. Condenser high temperature protection in cooling mode is not marked as standard.
- Allow the 3 minute compressor time delay to finish before judging a compressor restart.
- Check the power supply voltage if low voltage protection trips.
Applies to: D5CURA outdoor units
Source: D5CURA Product Data, p. 3. Written in our own words; check the manual for your exact model.
Buried refrigerant piping limits
Heat pump · D5CURA
Do not bury more than 36 in (914 mm) of refrigerant pipe. Any buried section needs a 6 in (152 mm) vertical rise to the outdoor valve connections, or refrigerant can migrate and cause slugging at start-up.
- Limit buried pipe to 36 in (914 mm).
- Provide a 6 in (152 mm) vertical rise to the outdoor valve connections.
Applies to: Field refrigerant piping
Source: D5CURA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Circuit board fuse
Heat pump · D5CURA
The control board has a blast-proof ceramic fuse for overcurrent. The rating is printed on the board (examples: T3.15AL/250VAC, T5AL/250VAC, T20A/250VAC, T30A/250VAC).
- Read the fuse rating printed on the board before replacing.
- Use only a blast-proof ceramic fuse.
Applies to: Control PCB
Source: D5CURA installation manual, p. 3. Written in our own words; check the manual for your exact model.
CN23/CN33 terminal wiring
Heat pump · D5FUAA
CN23 and CN33 connect to the terminals on the left and right sides only.
- Connect wires only to the left and right terminals of CN23 and CN33.
- Do not connect a wire to the middle terminal.
Applies to: D5FUAA indoor main board
Source: D5FUAA service manual, p. 16. Written in our own words; check the manual for your exact model.
Cooling performance tables start on p. 48
Heat pump · D5CURA
Page 48 is only the header for the D5CURA + D5FULA cooling tables. It defines TC (total cooling capacity, BTU/hr), S/T (sensible cooling capacity ratio) and PI (power input, kW). Highlighted data is tested; other data is simulated for reference.
- Use the highlighted values when you need tested data.
- Treat non-highlighted values as simulated reference only.
Applies to: D5CURA + D5FULA cooling performance
Source: D5CURA Product Data, p. 48. Written in our own words; check the manual for your exact model.
Decoding the D5FUAA model number and serial number
Heat pump · D5FUAA
Model letters: FU = unitary model type, A = major series, Q = heat pump, A = air handler. Capacity digits 18, 24, 30, 36, 48 or 60 (K Btu/h). Digit 5 = Puron Advance. K = 208/230 V 1-phase 60 Hz (the manual notes 115 V configuration for some units). Serial number shows year, week of manufacture and a sequential number.
Applies to: D5FUAA model and serial number identification
Source: D5FUAA service manual, p. 8. Written in our own words; check the manual for your exact model.
Discharge capacitors before troubleshooting
Heat pump · D5FUAA
Capacitors keep a charge after the power is removed.
- Shut off all power supplies or disconnect all wires.
- Follow lockout procedures.
- Make sure the capacitors are fully discharged before troubleshooting.
Applies to: D5FUAA indoor and outdoor units
Source: D5FUAA service manual, p. 19. Written in our own words; check the manual for your exact model.
Do not mix refrigerant types
Heat pump · D5CURA
Only use the refrigerant specified for this system. Mixing types is not allowed.
Applies to: Refrigerant charging
Source: D5CURA installation manual, p. 30. Written in our own words; check the manual for your exact model.
Electrical isolation before work
Heat pump · D5CURA
The main disconnect must be off before installing, modifying or servicing. There may be more than one disconnect.
- Switch off all main electrical disconnects.
- Lock out and tag each switch with a warning label.
Applies to: All units
Source: D5CURA installation manual, p. 1. Written in our own words; check the manual for your exact model.
Evacuation and fuse rules
Heat pump · D5FCFA
Rules for vacuum work and the control board fuse.
- Always break a vacuum with dry nitrogen.
- Never use the system compressor as a vacuum pump.
- When the control board fuse is replaced, use only the blast-proof ceramic fuse with the rating printed on the board.
Applies to: All D5FCFAH sizes
Source: D5FCFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Factory safety functions
Heat pump · D5CURA
The unit includes factory-set protection for compressor discharge over-temperature, system low voltage, compressor overload, compressor over-current and IPM module faults.
Applies to: D5CURA outdoor unit
Source: Carrier D5CURA product data, p. 126. Written in our own words; check the manual for your exact model.
Fixed wiring disconnect and RCD
Heat pump · D5CURA
Disconnection must be built into the fixed wiring per NEC, CSA and local codes. An all-pole disconnect with at least 3 mm contact clearance is required, and a residual current device is used where leakage may exceed 10 mA. The RCD rating is cut off in the source.
- Install an all-pole disconnect with at least 3 mm clearance in all poles.
- Fit a residual current device where leakage may exceed 10 mA.
- Confirm the RCD rating from the full manual.
Applies to: Fixed power wiring
Source: D5CURA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Flammable refrigerant R-454B handling
Heat pump · D5FCFA
The outdoor units ship with a full charge of R-454B, a flammable refrigerant. Only trained service personnel should repair the system.
- Do not puncture refrigerant tubing.
- Do not use means to speed defrost or to clean the unit other than those recommended by the manufacturer.
- Store the appliance in a room without continuous ignition sources such as open flames, operating gas appliances or operating electric heaters.
- Remember that refrigerant may have no odor.
- Do not pierce or burn refrigerant components.
Applies to: All D5FCFAH sizes
Source: D5FCFAH service manual, p. 15. Written in our own words; check the manual for your exact model.
Flammable refrigerant service limits
Heat pump · D5CURA
The unit uses flammable R-454B. Only trained service personnel may repair it, and refrigerant tubing must not be punctured.
- Use only trained service personnel for repairs.
- Do not puncture refrigerant tubing.
- Do not use means other than the manufacturer's to speed defrost or to clean.
Applies to: All units
Source: D5CURA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Flammable refrigerant: repair and handling rules
Heat pump · D5FUAA
The system uses a flammable refrigerant. Only trained personnel holding the required certification should open the refrigerant circuit.
- Do not puncture refrigerant tubing.
- Do not use means to speed defrosting or cleaning other than those the manufacturer recommends.
- Store the unit in a room with no continuously operating ignition sources.
- Use only leak detection equipment suitable for flammable refrigerants; do not use a halide torch or naked flame.
- Remove or put out all naked flames if a leak is suspected.
- Keep NO SMOKING signs displayed and a dry powder or CO2 extinguisher near the charging area when hot work is done.
- Work only in an open or adequately ventilated area before breaking into the system.
Applies to: R-flammable refrigerant systems
Source: D5FUAA Service Manual, p. 3-6. Written in our own words; check the manual for your exact model.
Handling the control boards
Heat pump · D5FUAA
Boards can be damaged by static discharge.
- Wear anti-static gloves or a wrist strap when checking the indoor or outdoor PCB.
Applies to: D5FUAA indoor and outdoor PCBs
Source: D5FUAA service manual, p. 19. Written in our own words; check the manual for your exact model.
How to read the cooling and heating capacity grids
Heat pump · D5CURA
Pages 12 to 16 hold the 18K and 24K cooling grids at each airflow. Each block gives total cooling (TC), sensible ratio (S/T) and power input (PI) against outdoor dry bulb, indoor wet bulb and indoor dry bulb.
- Find the airflow block (CFM) for the unit size.
- Pick the outdoor dry bulb row (°F and °C are both printed).
- Read the indoor wet bulb column group, then the indoor dry bulb column in that group.
- Read TC for capacity, S/T for sensible share, and PI for power input in kW.
- Use the highlighted (tested) values for rating checks; other values are simulated.
Applies to: Cooling and heating grids, pages 12 to 16
Source: D5CURA Product Data, p. 12. Written in our own words; check the manual for your exact model.
How to read the heating performance grids
Heat pump · D5CURA
Find the airflow block that matches the indoor unit airflow in CFM, then go down to the outdoor dry bulb temperature. Read across to the indoor dry bulb column for capacity (BTU/hr) and power input (kW). Pick the nearest indoor condition column for the room being checked.
- Select the table for the unit size (Tables 14 to 17 on these pages).
- Choose the airflow block nearest the actual CFM.
- Find the outdoor dry bulb row (-13°F to 75.2°F).
- Read TC (BTU/hr) and PI (kW) for the indoor dry bulb column that matches the room condition.
Applies to: D5CURA + D5FUAA heating performance
Source: D5CURA Product Data, p. 40-47. Written in our own words; check the manual for your exact model.
How to read the mixed-system cooling and heating performance tables
Heat pump · D5CMHA
Pages 104 to 109 hold the 48K and 55K cooling tables for mixed systems, and pages 110 to 112 hold the 18K, 24K heating tables for mixed systems. Each table is split by airflow (CFM) and by outdoor dry bulb temperature. Cooling blocks give TC (total capacity), S/T and PI (power input) against indoor wet bulb and indoor dry bulb. Heating blocks give TC (BTU/hr) and PI (kW) against indoor dry bulb.
- Find the table for the outdoor unit size (48K or 55K for cooling, 18K or 24K for heating shown here).
- Pick the airflow (CFM) block that matches the indoor units in the system.
- Read down to the outdoor dry bulb temperature for your conditions.
- For cooling, match the indoor wet bulb and indoor dry bulb columns, then read TC, S/T and PI.
- For heating, match the indoor dry bulb column, then read TC (BTU/hr) and PI (kW).
Applies to: Mixed-system performance tables on pages 104 to 112 (48K and 55K cooling, 18K and 24K heating)
Source: Carrier D5CMHA product data, p. 104-112. Written in our own words; check the manual for your exact model.
Ignition sources and storage
Heat pump · D5CURA
Store the unit where no continuously operating ignition source is present, such as open flame, gas appliance or electric heater. Refrigerant may have no odor.
- Keep the storage room free of open flames and running heaters.
- Do not pierce or burn the unit.
Applies to: All units
Source: D5CURA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Leak testing: no oxygen-containing gases
Heat pump · D5FUAA
Oxygen-containing air or gas mixtures can explode when pressurized in refrigerant systems.
- Never use air or gases containing oxygen for leak testing or for operating refrigerant compressors.
- Use an inert gas for pressure testing.
Applies to: Refrigerant circuit testing
Source: D5FUAA Service Manual, p. 1. Written in our own words; check the manual for your exact model.
Lift compressor from base pan
Heat pump · D5CURA
Continuation of the compressor removal. Heat the brazed joints before removing the pipes.
- Remove the hex nuts and washers that secure the compressor on the bottom plate.
- Heat the brazed joints, then remove the discharge pipe and the suction pipe.
- Lift the compressor from the base pan assembly with pliers.
Applies to: All sizes
Source: D5CURA service manual, p. 86. Written in our own words; check the manual for your exact model.
Never use air or oxygen-containing gas for leak testing
Heat pump · D5CURA
Pressurized mixtures of air or gases containing oxygen can explode when used with refrigerant systems or compressors.
- Use dry nitrogen or refrigerant-compatible test gas for pressure and leak testing.
- Do not use air or any gas containing oxygen to pressurize the system or run compressors.
Applies to: D5CURA refrigerant circuit
Source: D5CURA service manual, p. 1. Written in our own words; check the manual for your exact model.
Outdoor unit mounting clearances and snow
Heat pump · D5CURA
Clearance figures on the page are 59 in (1500 mm) or more, 23.6 in (600 mm) or more, and 9.8 in (250 mm) or more. Mount the outdoor unit at least 2 in (50 mm) above the maximum expected snow depth.
- Keep the required clearance around the unit as shown in Fig. 6 and Fig. 7.
- Raise the unit at least 2 in (50 mm) above the maximum expected snow depth.
Applies to: D5CURA outdoor units
Source: D5CURA Product Data, p. 6. Written in our own words; check the manual for your exact model.
Power off and check capacitors before troubleshooting
Heat pump · D5CURA
Electricity stays in the capacitors after power is removed. Also protect circuit boards from static.
- Turn off all power supplies or disconnect all wires.
- Make sure the capacitors are fully discharged before testing.
- Wear anti-static gloves or a wrist strap when handling indoor or outdoor PCBs.
Applies to: Indoor and outdoor units
Source: D5CURA service manual, p. 27. Written in our own words; check the manual for your exact model.
Power supply and electrical precautions
Heat pump · D5CURA
Checks to make before and during the electrical work on the outdoor unit.
- Lock out the main disconnect before any work, and tag it. There may be more than one disconnect.
- Confirm supply voltage is within 90 to 110 percent of rated voltage. Stop and refuse to install if the supply is unsafe.
- Provide a switch or breaker that disconnects all poles with at least 3 mm (1/8 in) contact separation.
- Use a dedicated branch circuit. Do not share it with another appliance.
- Size the supply cable from the Minimum Circuit Ampacity on the unit nameplate.
- Ground the unit per local code and make sure every wire is tight.
- Keep power wiring separate from signal wiring to avoid interference and board damage.
- Keep wires away from refrigerant tubing, the compressor, and moving parts.
- After power is off, wait at least 10 minutes before touching electrical components.
- Connect outdoor wires before indoor wires.
- Fit an external surge suppressor at the outdoor disconnect if possible.
Applies to: D5CURA outdoor units
Source: D5CURA installation manual, p. 18. Written in our own words; check the manual for your exact model.
Reading the D5CURA outdoor unit model number
Heat pump · D5CURA
Model code breakdown from the nomenclature figure: D5 = outdoor unit; CU = model; R = outdoor system type; the digit pair after R gives nominal capacity (36 = 3 tons, 48 = 4 tons); A = maximum one indoor unit connected; H = heat pump unit type; A = standard variation; K = 208/230 V, 1-phase, 60 Hz power.
- Read the voltage letter/number to confirm 208/230-1-60 before wiring.
- Read the capacity digits to confirm 3-ton (36) or 4-ton (48) size.
- Confirm the unit type is heat pump (H) and the connection count is one indoor unit (A).
Applies to: D5CURA outdoor heat pump, all sizes
Source: D5CURA service manual, p. 2. Written in our own words; check the manual for your exact model.
Reading the non-ducted cooling performance tables
Heat pump · D5CMHA
Each table is one size at one airflow. Find the outdoor DB row first, then the indoor WB group, then the indoor DB column. TC is total capacity, S/T is sensible-to-total ratio and PI is power input. Highlighted values are tested. Other values are simulated and for reference only.
- Pick the airflow block (CFM) that matches the indoor units installed.
- Find the outdoor dry-bulb row closest to the design condition.
- Go across to the indoor wet-bulb group, then to the indoor dry-bulb column.
- Read TC, S/T and PI from the same column.
Applies to: D5CMHA non-ducted cooling tables, Tables 19-24
Source: D5CMHA Product Data, p. 57. Written in our own words; check the manual for your exact model.
Refrigerant circuit components
Heat pump · D5CURA
The circuit has brass external liquid line service valves and suction line service valves, each with a service gauge port, plus an accumulator (heat pump units), a reversing valve and electronic expansion valves.
Applies to: D5CURA outdoor unit
Source: Carrier D5CURA product data, p. 126. Written in our own words; check the manual for your exact model.
Refrigerant leak detection system operation
Heat pump · D5CURA
When the sensor detects a leak, the indoor unit shows an error code and buzzes, the outdoor compressor stops at once and the indoor fan runs. The unit must stay powered except during service.
- Keep the unit powered except during service.
- Do not disable the leak detection system.
Applies to: Units with refrigerant sensor
Source: D5CURA installation manual, p. 4. Written in our own words; check the manual for your exact model.
Remove compressor (terminal cover and pipes)
Heat pump · D5CURA
Before starting, remove the panel plate and the four-way valve connection on the PCB, using the size-specific panel plate procedures and the electrical parts section, then remove the sound blanket. Explosion risk: evacuate the system and confirm no refrigerant is left before removing the valve or compressor. For R32 and R290, evacuate with a vacuum pump, flush with nitrogen, and repeat before heating brazed parts. Only professionals should do these operations.
- Remove the flange nut of the terminal cover and remove the cover.
- Disconnect the connectors.
Applies to: All sizes
Source: D5CURA service manual, p. 85. Written in our own words; check the manual for your exact model.
Remove electronic control board and 24V board
Heat pump · D5CURA
Removal sequence for the outdoor control board and the 24V board subassembly. Steps 1 to 4 are not visible on the extracted page.
- Remove the 3 screws and take off the bracket.
- Disconnect the connectors from the electronic control board.
- Remove the 3 screws and take out the electronic control board.
- Pull out the connector, remove one screw, then remove the 24V board subassembly from the terminal board.
Applies to: Outdoor unit, size not stated on this page
Source: D5CURA service manual, p. 80. Written in our own words; check the manual for your exact model.
Remove four-way valve
Heat pump · D5CURA
Before starting, remove the panel plate and the four-way valve connection on the PCB, using the size-specific panel plate procedures and the electrical parts section. Remove the sound blanket first. Fire hazard: evacuate the system and confirm no refrigerant is left before removing the valve or compressor. For R32 and R290, evacuate with a vacuum pump, flush with nitrogen, and repeat before heating brazed parts. Only professionals should do these operations.
- Heat the brazed joints and detach the four-way valve and the pipe.
- Remove the four-way valve assembly with pliers.
Applies to: Heat pump models, all sizes
Source: D5CURA service manual, p. 84. Written in our own words; check the manual for your exact model.
Remove outdoor fan and fan nut
Heat pump · D5CURA
Fan removal on all sizes. Use a spanner on the fan nut.
- Remove the nut that holds the fan, using a spanner.
- Remove the fan.
Applies to: All sizes
Source: D5CURA service manual, p. 81. Written in our own words; check the manual for your exact model.
Remove outdoor fan motor
Heat pump · D5CURA
Fan motor removal on all sizes.
- Remove the 4 fixing screws of the fan motor.
- Remove the fan motor.
Applies to: All sizes
Source: D5CURA service manual, p. 82. Written in our own words; check the manual for your exact model.
Remove sound blanket
Heat pump · D5CURA
Sound blanket removal. Applies only to models fitted with a blanket.
- Remove the side sound blanket.
- Remove the top sound blanket.
Applies to: Models with sound blanket
Source: D5CURA service manual, p. 83. Written in our own words; check the manual for your exact model.
Replacing the control board fuse
Heat pump · D5FSFA
The control board has an overcurrent fuse. Its rating is printed on the board.
- Read the fuse rating printed on the board before replacing it. Examples printed include T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC and T30A/250VAC.
- Use only the blast-proof ceramic fuse.
Applies to: D5FSFAH control board
Source: D5FSFAH service manual, p. 2. Written in our own words; check the manual for your exact model.
Room height and room area
Heat pump · D5CURA
The room height must be at least 7.3 ft (2.2 m). The minimum operating or storage room area depends on the charge amount listed in Table 1.
- Confirm the room height is at least 7.3 ft (2.2 m).
- Check the minimum room area for the unit's charge.
Applies to: All units
Source: D5CURA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Routine cleaning and handling
Heat pump · D5FUAA
Basic care rules for the indoor unit.
- Clean with a soft cloth only; do not use harsh detergents or solvents.
- Do not touch the electrostatic filter if one is fitted.
- Do not open the inlet grille while the unit is running.
- Do not block the air inlet or outlet.
- Do not drink or touch drain water; check that the drain hose drains correctly.
- Use a firm step ladder when working on the unit.
- Lift with two or more people.
Applies to: D5FUAA indoor unit
Source: D5FUAA Service Manual, p. 4. Written in our own words; check the manual for your exact model.
Wiring and power supply
Heat pump · D5CURA
Use only the specified wire and ground the product at installation. Connect and clamp cables tightly. Route wiring so the control board cover closes. Do not share the outlet with other appliances. Follow the Electrical Connection Diagram on the unit panels.
- Use the specified wire only.
- Ground the product.
- Clamp cables tightly.
- Route wiring so the board cover closes fully.
- Use a dedicated outlet.
Applies to: All units
Source: D5CURA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Wiring cautions
Heat pump · D5CURA
Wiring mistakes can damage the outdoor and indoor control boards or cause a fire hazard.
- Make every wire connection firm; loose wiring can overheat the terminal.
- Keep all wire away from the refrigerant tubing, the compressor and moving parts.
- Route cable and conduit through the hole in the conduit panel.
- Follow local codes when running wire from the indoor unit to the outdoor unit.
- Provide a disconnect within sight of and readily accessible from the unit.
- Do not connect 24V AC to S1 - S2.
Applies to: D5CURA wiring
Source: D5CURA product data, p. 117. Written in our own words; check the manual for your exact model.
Discharge the inverter capacitors before service
Mini split · Carrier DLCM(R/H)B multi-zone outdoor, Carrier DLFSHB high wall indoor
The big electrolytic capacitors on the outdoor board stay charged after power-off.
- Turn power off and lock out.
- Put a resistor of about 100 ohm 40 W (or a soldering iron plug) across the + and - capacitor terminals before touching the board.
Applies to: DLCM(R/H)B multi-zone outdoor units with DLFSHBH high wall indoor units (Midea, Carrier, Viessmann)
Source: Carrier MS-DLFSHB-01 High Wall Ductless Service Manual (04/2021), Troubleshooting Safety p.16. Written in our own words; check the manual for your exact model.
24V third-party thermostat interface
Mini-split · D5FCFA
The system can be run from a third-party thermostat through the 24V interface.
- Use the 24V interface to control the ductless system from a third-party thermostat.
- Follow the wiring caution for indoor-to-outdoor wiring and wire sizing.
Applies to: Control wiring
Source: D5FCFA Product Data, p. 10. Written in our own words; check the manual for your exact model.
Active Clean function (display CL)
Mini-split · D5FSFA
Freezes and then thaws frost on the evaporator to wash off dust and grease, then blow-dries the coil. The display shows CL. The unit turns off by itself after 20 to 45 minutes and cancels the function. Not available on all models or multi-zone systems.
- Wait for the cycle to finish; the unit turns off automatically after 20 to 45 minutes.
Applies to: Some models, single-zone
Source: Carrier D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Air filter cleaning schedule and filter type
Mini-split · D5FUAAH
Inspect and clean or replace the air filter monthly or as needed. The replacement filter must meet UL900. Ask the manufacturer if you are unsure which filter to use.
- Inspect the air filter monthly or as required.
- Clean or replace it with a UL900 filter.
Applies to: Indoor unit air filter
Source: D5FUAAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Air sweep and refrigerant leak detection
Mini-split · D5FCFA
The fan coil has a motor-driven vertical air sweep that is standard and user selectable. The vertical sweep is adjusted with the remote control and the horizontal air direction is set by hand. The system also includes a refrigerant leak detection and mitigation function.
Applies to: D5FCFA ceiling/floor ductless fan coil
Source: Carrier D5FCFA Product Data, p. 55. Written in our own words; check the manual for your exact model.
Airflow and temperature distribution charts (pages 16 to 24)
Mini-split · D5FCFA
These pages hold only figure captions for airflow velocity and temperature distribution charts (Figs. 27 to 44). The charts cover cooling and heating at 30° and 60° discharge angles for the 18K and 24K ceiling and floor installations. The actual chart values are images and cannot be read from the text.
- Find the figure for the unit size, installation type (ceiling or floor), mode and discharge angle needed.
- Read the velocity and temperature values from the chart image in the original manual.
Applies to: 18K and 24K ceiling and floor indoor units, cooling and heating
Source: Carrier D5FCFA Product Data, p. 16-24. Written in our own words; check the manual for your exact model.
Airflow distribution figures for ceiling and floor installs
Mini-split · D5FCFA
Pages 48 to 54 show cooling and heating airflow velocity and temperature distribution plots for the 18K to 60K sizes, with discharge angles of 30° or 60°. Page 51 is the 60K floor installation, cooling, 30° discharge. The values are in the figure images only and are not written in the text, so no numbers are recorded here.
- Find the figure that matches the size, installation type (ceiling or floor), discharge angle and mode (cooling or heating) you need.
Applies to: D5FCFA ceiling/floor ductless fan coil, sizes 18K to 60K
Source: Carrier D5FCFA Product Data, pp. 48-54. Written in our own words; check the manual for your exact model.
Alarm dry contact CN33
Mini-split · D5FSOA
CN33 provides dry contacts that close when the unit has an alarm. Can drive a pilot relay for an external alarm.
- Wire a pilot relay to the CN33 dry contacts.
- Use the relay to drive an external alarm device.
Applies to: Indoor unit controls
Source: D5FSOA Product Data, p. 15. Written in our own words; check the manual for your exact model.
ALARM dry contact output (CN33)
Mini-split · D5FSCAH, D5FLCAH
Fault alarm output on the indoor unit board. Supplies no voltage of its own.
- Power the alarm from the alarm system, not from the unit.
- Keep the load below 24 V and 0.5 A, as recommended.
- The contacts close when the unit has a fault, which activates the alarm.
Applies to: D5FSCAH / D5FLCAH indoor unit
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 13. Written in our own words; check the manual for your exact model.
Alarm output (CN33) and fan-motor power output (CN8)
Mini-split · D5FSOAH
CN33 is a dry contact that closes when the unit has an alarm, for driving a pilot relay. CN8 carries line voltage (208 or 230 V) while the indoor blower runs, for a relay on an outdoor air fan or other peripheral. CN8 turns off during forced cooling or capacity testing mode.
- Wire a pilot relay to CN33 for external alarm devices.
- Use CN8 only through a relay to switch a separate peripheral circuit.
Applies to: D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
Source: D5FSOAH service manual, p. 11. Written in our own words; check the manual for your exact model.
Auto leak detection behaviour
Mini-split · D5FSHAH
On units with a refrigerant sensor, a detected leak shows an error code, the indoor unit beeps, the outdoor compressor stops immediately and the indoor fan runs. The buzzer beeps for 5 minutes or until any remote button is pressed. Sensor life is 15 years. A failed sensor shows FHCC. Sensors cannot be repaired and must be replaced by the manufacturer with the specified sensor.
- Treat any leak alarm as a refrigerant leak and call a technician.
- Press any remote button to silence the buzzer if needed.
- Replace a faulty refrigerant sensor only with the manufacturer-specified sensor.
Applies to: Units with refrigerant sensor
Source: D5FSHAH Owner's Manual, p. 12. Written in our own words; check the manual for your exact model.
AUTO mode on multi-zone systems
Mini-split · D5FSFAH
AUTO changeover is for single-zone use only. On a multi-zone system, an indoor unit can go to STANDBY and show two dashes (--) until all indoor units run the same mode (COOLING or HEATING). HEATING is the priority mode, and simultaneous heating and cooling is not allowed.
Applies to: Multi-zone ductless systems
Source: Carrier D5FSFAH owner's manual, p. 3. Written in our own words; check the manual for your exact model.
Auto start after power loss
Mini-split · D5FS(L)AAH
If power fails while the unit runs, it stores the operating condition and restarts that operation automatically when power returns.
Applies to: Indoor unit
Source: Carrier D5FS(L)AAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Auto-restart after power failure
Mini-split · D5FCFA
An auto-restart module stores the last settings. After power returns, the unit resumes the previous settings (SWING excluded) after 3 minutes. If forced cooling was stored, the unit runs cooling 30 minutes then AUTO at 75°F (24°C). If the unit was off and must start, the compressor waits 1 minute; otherwise it waits 3 minutes.
- Confirm DIP/menu auto-restart setting is active if the unit must resume after outages.
- Allow 3 minutes after power returns before expecting restart.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 19. Written in our own words; check the manual for your exact model.
Auxiliary heater clearance from combustibles
Mini-split · D5FCFA Ceiling/Floor Ductless
The manual gives two different clearances for the auxiliary electric heater.
- Keep at least 40 in (1 m) from combustible materials, as stated on the wiring page.
- The safety page also says 3 ft (1 m). Use the larger 40 in (1 m) value until the manual is checked.
Applies to: Units with an auxiliary electric heater
Source: Carrier D5FCFA installation manual, p. 2 and p. 19. Written in our own words; check the manual for your exact model.
Board fuse replacement
Mini-split · D5FSOA
The control board has an overcurrent fuse. The rating is printed on the board. Only the blast-proof ceramic type may be used.
- Read the fuse rating printed on the circuit board before replacing it. Examples on the manual include T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC and T30A/250VAC.
- Fit only a blast-proof ceramic fuse of the rating marked on the board.
- Turn off the unit and disconnect power before replacing the fuse.
Applies to: D5FSOAH control board
Source: Carrier D5FSOAH service manual, p. 2. Written in our own words; check the manual for your exact model.
Breeze Away and Active Clean
Mini-split · D5FSOA
Breeze Away lowers fan speed to reduce draft in cooling, fan-only and drying modes. Active Clean freezes and thaws frost on the evaporator to wash away dust and mold, then dries it with the fan. Both are not available on Multi-Zone systems.
Applies to: D5FSOA single-zone units
Source: D5FSOA Product Data, p. 7. Written in our own words; check the manual for your exact model.
Buried refrigerant pipe limits
Mini-split · D5FCFA
Buried refrigerant pipe causes slugging and can damage the compressor at start-up if the limits are exceeded.
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
Applies to: Refrigerant piping installation
Source: D5FCFA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Clean function for heat exchanger
Mini-split · D5FSHA
The remote control Clean function is used to clean a dirty heat exchanger.
- Use the Clean function on the remote control to clean the affected heat exchanger.
Applies to: Indoor or outdoor heat exchanger
Source: Carrier D5FSHA installation manual, p. 26. Written in our own words; check the manual for your exact model.
Clean the indoor unit air filter
Mini-split · D5FUHAQ
Clean the filter monthly or as required. Use a standard filter that meets UL900 when replacing.
- Turn off the unit and disconnect its power supply.
- Remove the filter cover.
- Remove the air filter.
- Clean it by vacuuming the surface or washing in warm water with mild detergent.
- Do not dry the filter in direct sunlight.
- Reinstall the filter and cover.
Applies to: Indoor unit air filter
Source: Carrier D5FUHAQ Owner's Manual, p. 16-17. Written in our own words; check the manual for your exact model.
Clean the outdoor coil from the inside
Mini-split · D5CMHA
The draw-through fan pulls dirt onto the outer face of the coil, so cleaning is done from the inside of the unit.
- Remove the outdoor unit top or access panel.
- Clean the coil from the inside with a pressure hose and detergent.
Applies to: D5CMHA outdoor units
Source: Carrier D5CMHA product data, p. 2. Written in our own words; check the manual for your exact model.
Cleaning the unit safely
Mini-split · D5FUAAH
Only clean the outside of the unit with a soft dry cloth or a cloth dampened with warm water. Never use chemicals, solvents, running water or excessive water. Front panel water must not be hotter than 104 F (40 C).
- Turn off the unit and disconnect power before cleaning.
- Use a soft, dry or lightly damp, lint-free cloth with neutral detergent.
- Dry the unit with a dry, lint-free cloth.
- Do not use benzene, paint thinner, polishing powder or other solvents.
- Do not wash the unit under running water.
Applies to: Indoor unit exterior
Source: D5FUAAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Clearance around the indoor unit
Mini-split · D5FSOAH
Figures 2 and 3 show clearances to ceiling, wall, roof and ground. Legible values are 0.63 in (16 mm), 8.66 in (220 mm), 8.86 in (225 mm), 19.69 in (500 mm) and 98.43 in (2500 mm). The labels do not clearly show which value applies to which surface, so check the figure for each direction.
Applies to: D5FSOAH indoor unit installation
Source: D5FSOAH installation instructions, p. 9. Written in our own words; check the manual for your exact model.
Clearance for units with auxiliary electric heater
Mini-split · D5FCFA
Units with an auxiliary electric heater must be kept clear of combustible materials.
- Keep the unit at least 3 ft (1 m) from any combustible materials.
Applies to: Units with auxiliary electric heater
Source: Carrier D5FCFAH service manual, p. 2. Written in our own words; check the manual for your exact model.
Compressor preheating
Mini-split · D5FSOA
Preheating switches on automatically when the T4 outdoor sensor reads below the set temperature.
Applies to: D5FSOA heat pump units
Source: D5FSOA Product Data, p. 3. Written in our own words; check the manual for your exact model.
Compressor time delay and beep
Mini-split · D5FSFAH
Compressor will not start for 3 to 4 minutes after a quick ON/OFF. The unit beeps only when signals are received correctly.
- Wait 3 to 4 minutes before expecting the compressor to start after a quick restart.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Condensate pump liquid level sensor
Mini-split · D5FSHA
The field installed condensate pump has a liquid level sensor in its reservoir. If the liquid level is unacceptable, the sensor stops cooling operation.
- If cooling stops unexpectedly on a unit with a condensate pump, check the pump reservoir level and the drain path.
Applies to: Indoor units with condensate pump accessory
Source: Carrier D5FSHA High Wall Ductless System Product Data, p. 12. Written in our own words; check the manual for your exact model.
Control board fuse replacement
Mini-split · D5FSCAH / D5FLCAH
The control board uses an overcurrent fuse. Only the specified blast-proof ceramic fuse may be used. The rating is printed on the board, for example T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC.
- Read the fuse rating printed on the control board.
- Disconnect power before replacing the fuse.
- Install only a blast-proof ceramic fuse of the same rating.
Applies to: Indoor and outdoor control boards
Source: D5FSCAH / D5FLCAH service manual, p. 3. Written in our own words; check the manual for your exact model.
Decode the model number
Mini-split · D5FCFA
The model number is read from left to right: D5F = indoor ductless unit, C = model, F = ceiling/floor console, A = major series, H = heat pump, 36 = nominal capacity (3 ton), X = 0 (voltage/system code), K = 208/230-1-60 (voltage), A = standard.
Applies to: D5FCFAH indoor units
Source: Carrier D5FCFAH service manual, p. 8. Written in our own words; check the manual for your exact model.
Decode the serial number
Mini-split · D5FCFA
Serial number format: the first two digits are the week of manufacture, the next two digits are the year, followed by a sequential serial number and a model-family letter.
Applies to: D5FCFAH indoor units
Source: Carrier D5FCFAH service manual, p. 8. Written in our own words; check the manual for your exact model.
Decommissioning and labeling
Mini-split · D5FSOA
Before a unit is decommissioned, the technician must be fully familiar with it. Electrical power must be available for the recovery task.
- Take oil and refrigerant samples before recovery if analysis may be needed.
- Isolate the system electrically and pump it down if possible. If a vacuum is not possible, set up a manifold to recover from several points.
- Place the recovery cylinder on scales before recovery starts. Keep the process supervised by a competent person.
- After decommissioning, label the equipment as emptied of refrigerant, with the date and signature.
- Label equipment that contains flammable refrigerant so it is clearly marked.
Applies to: D5FSOAH systems
Source: Carrier D5FSOAH service manual, p. 7. Written in our own words; check the manual for your exact model.
Discharge electrolytic capacitors before troubleshooting
Mini-split · D5FSOA
Capacitors keep charge after power is off. Discharge them before touching the board. The discharge resistor value is partly garbled in the source, so confirm it against the unit label.
- Turn off all power and lock out the supply.
- Connect a discharge resistor or a soldering iron plug across the + and - terminals of the electrolytic capacitor (see Fig. 33 and 34 on the outdoor PCB).
- Confirm the capacitor is discharged before troubleshooting.
Applies to: D5FSOAH outdoor PCB
Source: D5FSOAH service manual, p. 24. Written in our own words; check the manual for your exact model.
Display and LED indicators
Mini-split · D5FSCAH / D5FLCAH
All cassette sizes have an LED display that shows operation status and error codes. Indicators include Operation, Timer, Alarm, PRE-DEF (preheating/defrost) and a wireless control indicator on some models.
- Read the LED display for the error code.
- Check the PRE-DEF indicator to see if the unit is in preheating or defrost.
Applies to: All 9K~48K units
Source: D5FSCAH / D5FLCAH service manual, p. 23. Written in our own words; check the manual for your exact model.
Display code CP (remote switch off)
Mini-split · D5FSOAH
With the remote ON-OFF input open, the system is off and the display shows CP.
- Close the remote ON-OFF contact to restart the system.
Applies to: D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
Source: D5FSOAH service manual, p. 11. Written in our own words; check the manual for your exact model.
Display panel and remote LCD symbols
Mini-split · D5FSFAH
The indoor display shows temperature and error codes. Symbols show defrost, timer, SWING or SILENCE, Active Clean, 46°F/8°C heating, and ECO on the unit. The remote LCD shows mode, timers, fan speed, humidity, ECO, GEAR, LOCK, low battery and feature icons.
- Read the indoor display for set temperature, error codes and feature symbols.
- Read the remote LCD for mode, timer, fan speed and feature status.
- If the remote low-battery icon flashes, replace the batteries.
Applies to: Indoor display panel and wireless remote LCD
Source: D5FSFAH Owner’s Manual, p. 8, 10. Written in our own words; check the manual for your exact model.
Display panel indicators
Mini-split · D5FSFAH
The display panel shows temperature and error codes. Symbols show defrost on heating units, timer on/off with swing or silence for 3 seconds, Active Clean on, 46°F/8°C heating feature on, and ECO function on.
Applies to: Indoor unit display panel, D5FSFAH
Source: Carrier D5FSFAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.
Downsize D5FSOAH12XAK from 12K to 9K
Mini-split · D5FSOAH
The D5FSOAH12XAK is dual capacity and ships at 12K. ENC1 on the main board sets it to 9K.
- Disconnect power.
- Open the electronic control box.
- Set ENC1 to 2.
- Close the electronic control box.
- Reconnect power. The unit now runs as 9K.
Applies to: D5FSOAH12XAK
Source: D5FSOAH service manual, p. 14. Written in our own words; check the manual for your exact model.
Drainage plug use
Mini-split · D5FSOAH
The drainage plug at the bottom of the unit body drains the drain pan when the unit malfunctions. It must be fully plugged during normal operation to prevent leaks.
- Use it only to remove accumulated water after the unit has been switched off.
- After draining, put the test cap back in its original position.
- Confirm the plug is sealed before normal operation.
Applies to: Indoor unit drain pan
Source: D5FSOAH installation instructions, p. 24. Written in our own words; check the manual for your exact model.
DRYING mode low room temperature protection
Mini-split · D5FSFA
In DRYING mode the compressor stops when room temperature is too low, and it does not restart until the room warms up.
- Compressor stops when room temperature drops below 50 F (10 C).
- Compressor restarts only after room temperature exceeds 53.6 F (12 C).
Applies to: D5FSFAH 9K to 16K
Source: D5FSFAH service manual, p. 15. Written in our own words; check the manual for your exact model.
Drying mode operation and low room temperature protection
Mini-split · D5FCFA
Indoor fan is fixed at BREEZE and cannot be changed. Louver angle matches cooling. If room temperature is below 50°F (10°C) the compressor stops and does not restart until the room exceeds 53.6°F (12°C).
- If the compressor will not restart in drying mode, check room temperature against 53.6°F (12°C).
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 19. Written in our own words; check the manual for your exact model.
Electrical isolation and lockout before service
Mini-split · D5FCFA
Electrical shock hazard. Power must be isolated before any installation or repair work.
- Switch off the main electrical disconnect before installing, modifying or servicing the system.
- Check for more than one disconnect and switch off all of them.
- Lock out and tag each disconnect with a warning label.
- Use a dedicated circuit and do not share the outlet with other appliances.
- Confirm the fixed wiring has an all-pole disconnect with at least 3 mm contact gap and a 30 mA RCD where required.
Applies to: All D5FCFAH indoor and outdoor units
Source: Carrier D5FCFAH service manual, p. 1-2. Written in our own words; check the manual for your exact model.
Electrical safety checks before work on sealed or live electrical parts
Mini-split · D5FSOA
Disconnect power before opening covers. If supply must stay on during service, leak detection must be running at the most critical point.
- Switch off the main electrical disconnect before installing, modifying or servicing. Lock out and tag it. There may be more than one disconnect.
- Discharge capacitors in a safe way that avoids sparks.
- Check that no live parts or wiring are exposed while charging, recovering or purging.
- Check that earth bonding is continuous.
- Check that cables are not worn, corroded, pinched or under vibration stress.
- Replace sealed electrical components and intrinsically safe components only with parts specified by the manufacturer.
- Make sure seals and glands are intact so flammable atmospheres cannot enter the enclosure.
Applies to: D5FSOAH indoor and outdoor units
Source: Carrier D5FSOAH service manual, p. 1, p. 6. Written in our own words; check the manual for your exact model.
Electrical supply and disconnect
Mini-split · D5FSAA, D5FLAA
Supply and disconnect requirements shown on the wiring pages.
- Connect the indoor and outdoor units to 208/230V, 60 Hz as shown in the connection diagram.
- Use a disconnect in the fixed wiring per NEC, CSA and local codes.
- Provide a separate circuit breaker for the electric heater unit power wires as shown in the wiring overview.
- Use the wiring diagram that matches the unit size.
Applies to: Power supply and wiring for 18K to 60K units
Source: D5FSAA and D5FLAA installation instructions, p. 28, 32. Written in our own words; check the manual for your exact model.
Electrical supply and disconnect requirements
Mini-split · D5FCFA
Installation work requires power to be off and locked out. The fixed wiring needs an all-pole disconnect and an RCD.
- Switch the main disconnect OFF before installing or servicing. Lock out and tag it, because there may be more than one disconnect.
- Use an all-pole disconnect with at least 3 mm contact clearance in every pole, as NEC, CSA and local codes require.
- Fit a residual current device (RCD) rated at 30 mA or less for leakage that may exceed 10 mA.
- Do not share the outlet with other appliances.
- Only use the specified wire, and clamp all cables tight. Keep the control board cover able to close properly.
Applies to: Indoor and outdoor units, fixed wiring
Source: D5FCFA installation manual, p. 1 and p. 2. Written in our own words; check the manual for your exact model.
Electronic control box subassembly removal
Mini-split · D5FSOA
Electrical parts are removed after the panel is off. Only the final removal steps are on these pages.
- Remove the panel first.
- Remove the 4 screws holding the electronic control box subassembly.
- Lift out the electronic control box subassembly.
Applies to: D5FSOAH, sizes 06K to 18K
Source: D5FSOAH service manual, p. 56. Written in our own words; check the manual for your exact model.
Evaporator removal
Mini-split · D5FSOA
Remove the panel, water collector and water pump first. The coil temperature sensor T2 is pulled out during this job.
- Remove the panel, water collector and water pump.
- Remove the 2 screws of the pipe clamp board.
- Remove the 2 screws on the left side of the evaporator bracket.
- Remove the 2 screws on the right side of the evaporator.
- Cut the zip tie, pull out the coil temperature sensor (T2) and remove 1 ground screw.
- Remove the evaporator.
Applies to: D5FSOAH, sizes 06K to 18K
Source: D5FSOAH service manual, p. 59-60. Written in our own words; check the manual for your exact model.
Fan motor and fan removal
Mini-split · D5FSOA
Remove the panel, electrical parts, water collector, water pump and evaporator first.
- Remove the panel, electrical parts, water collector, water pump and evaporator.
- Remove the 2 screws of the fan motor base.
- Pull out the fan motor and fan assembly.
- Remove the screw and take off the fan motor.
Applies to: D5FSOAH, sizes 06K to 18K
Source: D5FSOAH service manual, p. 61. Written in our own words; check the manual for your exact model.
Flammable refrigerant and leak sensor handling
Mini-split · D5FCFA Ceiling/Floor Ductless
Rules for working on systems with an R-32 style flammable refrigerant and a leak sensor.
- Only trained service personnel may repair this unit. Do not puncture refrigerant tubing.
- Test joints with a detector rated for 1/8 oz (5 g) per year or better.
- Keep ventilation openings clear of obstruction.
- Replace the refrigerant sensor only with the manufacturer-specified sensor. Sensors cannot be repaired.
- Sensor service life is 15 years.
Applies to: Units with a refrigerant leak sensor
Source: Carrier D5FCFA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Flammable refrigerant: safe work practices
Mini-split · D5FSOA
The unit uses a flammable refrigerant. Only trained technicians holding a current refrigerant-handling certificate may open the refrigerant circuit. Do not pierce or burn refrigerant tubing, and do not use ignition sources near the work area. Refrigerant may have no odour, so detection equipment is needed.
- Check the area with a refrigerant detector before and during work.
- Use only leak detection that is non-sparking and suitable for flammable refrigerant. Never use a halide torch or a naked flame.
- Remove or extinguish all naked flames and ignition sources before opening the system.
- Keep a dry powder or CO2 extinguisher next to the charging area when hot work is planned.
- Ventilate the area before breaking into the system or doing hot work, and keep ventilation running during the job.
- Do not use means to speed up defrosting or cleaning other than those the manufacturer recommends.
- Keep the unit stored in a room without continuously operating ignition sources.
Applies to: All D5FSOAH indoor and outdoor units
Source: Carrier D5FSOAH service manual, p. 3-7. Written in our own words; check the manual for your exact model.
Fresh-air fan output CN8
Mini-split · D5FSOA
CN8 is line voltage (208 or 230 V) while the indoor blower runs. It is off during forced cooling or capacity test mode.
- Use CN8 to power a relay for an outdoor air fan or other peripheral.
- Do not expect CN8 to be live during forced cooling or capacity testing.
Applies to: Indoor unit controls
Source: D5FSOA Product Data, p. 15. Written in our own words; check the manual for your exact model.
Fuse replacement rule
Mini-split · D5FUAAH
Replace a blown fuse only with one of identical rating. A higher or lower amperage fuse can damage the circuit or cause an electrical fire.
- Disconnect power before work.
- Fit a fuse with the same rating as the one removed.
Applies to: Unit power supply
Source: D5FUAAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Handle pipe connectors A and B safely
Mini-split · D5FSHA
Connectors A and B are pressurised and can release on removal.
- Wear work gloves and goggles.
- Do not point connectors A and B toward people.
- Hold the cross-shape part of connector B with a wrench or channel locks for about 5 to 10 seconds until the red point of connector A fully retracts.
- Remove connectors A and B, then make the refrigerant connection.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 21. Written in our own words; check the manual for your exact model.
Heating at 46°F (8°C) mode
Mini-split · D5FCFA
When the compressor runs, the indoor fan runs without anti-cold air. When the compressor is off, the indoor fan is off.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 19. Written in our own words; check the manual for your exact model.
Indoor coil protections and heating setback
Mini-split · D5FSHA
Indoor units include freeze-up protection and cold blow protection on heat pumps. High temperature protection in heating mode detects excessive discharge temperature. A 46°F heating mode (heating setback) is standard. Auto restart returns the unit to its prior operating conditions after a power failure.
Applies to: Indoor units, sizes 06 to 36
Source: Carrier D5FSHA High Wall Ductless System Product Data, p. 4. Written in our own words; check the manual for your exact model.
Indoor unit dimensions
Mini-split · D5FSOAH
Figure 1 gives the indoor unit footprint and ceiling hole sizes. Legible values are 16.65 in (423 mm), 13.19 in (335 mm), 43.5 in (1105 mm), 9.84 in (250 mm), 53.54 in (1360 mm), 18.4 in (475 mm), 8.07 in (205 mm) and 7.87 in (200 mm). The figure labels are partly garbled, so confirm each dimension against the drawing before cutting the ceiling hole.
Applies to: D5FSOAH indoor unit, sizes 6K to 18K
Source: D5FSOAH installation instructions, p. 8. Written in our own words; check the manual for your exact model.
Indoor unit supplied parts and recommended tools
Mini-split · D5FSHA
Parts list (numbering from the figure): wall mounting plate, connection cable (buy separately), remote controller, drain pipe (buy separately), refrigerant piping (buy separately), louver, remote controller holder, air filter (pulls up), front panel, outdoor unit power cable, circuit breaker. Recommended tools: gloves, screwdriver and wrench, goggles and masks, vinyl tape, hammer drill, core drill.
- Confirm all parts listed for the unit are on hand before starting.
- Buy the connection cable, drain pipe and refrigerant piping separately.
- Have a hammer drill and core drill ready for the wall hole.
Applies to: D5FSHA indoor unit installation
Source: Carrier D5FSHA installation manual, p. 10. Written in our own words; check the manual for your exact model.
Indoor wiring diagram legend
Mini-split · D5FSCAH / D5FLCAH
Legend terms used on the indoor unit wiring diagram.
- Y/G: yellow-green conductor (ground).
- PUMP: condensate pump.
- TO CCM Comm. Bus: central controller communication bus.
- T1: indoor room temperature sensor.
- T2: indoor heat exchanger coil temperature sensor.
Applies to: 9K~18K wiring diagram
Source: D5FSCAH / D5FLCAH service manual, p. 17. Written in our own words; check the manual for your exact model.
Indoor-to-outdoor wiring rules
Mini-split · D5FSCAH, D5FLCAH
Rules for connecting the indoor and outdoor units and field wiring.
- Do not use thermostat wire between indoor and outdoor units.
- Wire indoor-to-outdoor connections exactly as shown. Polarity matters, and wrong polarity causes a fault code.
- Use the wire size specified in the product data for each indoor unit.
- Do not connect power wire to a signal terminal.
- Do not splice control wires.
- Keep wiring with different voltages in separate conduits.
- Avoid metal conduit to reduce noise and EMI.
- Make sure each wire lands on the matching terminal on the indoor and outdoor units.
- Ground the equipment and install a current leakage protection switch as required by local rules.
Applies to: D5FSCAH / D5FLCAH
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 15-16. Written in our own words; check the manual for your exact model.
Inquiry codes 12 and 13 - conflicting labels
Mini-split · D5FSFA
Code 12 is labelled Pr (indoor fan speed) in the table, but its description covers the heating frequency lower limit. Code 13 is labelled Lr (EEV opening), but its description covers the T4 cooling-only maximum operating frequency. Confirm the function on the unit before changing either value.
- Verify the displayed function before changing code 12 or 13.
- Do not change these values without confirming the correct function.
Applies to: Inquiry codes 12 and 13
Source: Carrier D5FSFAH service manual, p. 17-18. Written in our own words; check the manual for your exact model.
Installation clearance near auxiliary heater
Mini-split · D5FCFA
Units with an auxiliary electric heater need clearance from combustible materials.
- Do not install the unit within 3 feet (1 meter) of any combustible material.
Applies to: Units with auxiliary electric heater
Source: D5FCFA installation manual, p. 2. Written in our own words; check the manual for your exact model.
Installation clearances and site limits
Mini-split · D5FSOA
Keep clearances from combustibles and keep the unit level, firm and free of obstructions.
- Keep an auxiliary electric heater unit at least 3 ft (1 m) from any combustible materials.
- Confirm the support can hold the unit weight before installing.
- Keep the unit level and secured.
- Keep ventilation openings and air inlets and outlets clear of obstruction.
- Install drain hoses so water drains correctly.
- Use two or more people to lift or move the unit.
- Disconnect power or turn off the breaker when the unit will be idle for a long time.
Applies to: D5FSOAH indoor and outdoor units
Source: Carrier D5FSOAH service manual, p. 2, p. 4. Written in our own words; check the manual for your exact model.
Keep outdoor unit powered in cold weather
Mini-split · D5FS(L)AAH
Below 32 F (0 C) the crankcase heater on the outdoor unit must stay energized to prevent compressor damage.
- Keep the outdoor unit powered at all times when outdoor temperature is below 32 F (0 C).
Applies to: Outdoor units with crankcase heater
Source: Carrier D5FS(L)AAH owner's manual, p. 9. Written in our own words; check the manual for your exact model.
Limits for buried refrigerant piping
Mini-split · D5FSCAH / D5FLCAH
Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any pipe is buried, the pipe must rise at least 6 in. (152 mm) to the outdoor unit valve connections.
- Keep buried refrigerant pipe to 36 in. (914 mm) or less.
- Make a 6 in. (152 mm) vertical rise to the outdoor unit valves if any pipe is buried.
Applies to: Refrigerant piping installation
Source: D5FSCAH / D5FLCAH service manual, p. 1. Written in our own words; check the manual for your exact model.
Lock out power before any install or service
Mini-split · D5FSCAH / D5FLCAH
Turn off the main electrical disconnect before installing, modifying or servicing. There may be more than one disconnect.
- Switch off the main disconnect.
- Check for any additional disconnects.
- Lock out and tag all disconnects before working.
Applies to: All installation and service work
Source: D5FSCAH / D5FLCAH service manual, p. 1. Written in our own words; check the manual for your exact model.
Louver position memory
Mini-split · D5FSFA
On restart the louver returns to the angle the user set, if that angle is within the allowed range. If the angle is out of range, the unit stores the maximum allowed angle. After a power failure or a TURBO shutdown the louver returns to its default angle.
Applies to: D5FSFAH 9K to 16K
Source: D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Louver swing and feature availability
Mini-split · D5FSOAH
The horizontal louver swing is started and stopped with the SWING button. The manual says vertical auto swing is available by holding the same button for 2 seconds on some units.
- Press SWING to start or stop horizontal louver movement.
- On units that support it, hold SWING for 2 seconds for vertical auto swing.
Applies to: Units with louver swing
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Meaning of unit symbols
Mini-split · D5FS(L)AAH
Warning symbol: flammable refrigerant is used, so there is a fire risk if it leaks near an ignition source. Caution symbol: read the operation manual carefully. Caution symbol: service personnel must handle the equipment using the installation manual. Information symbol: the operating or installation manual has more information.
Applies to: Indoor and outdoor units
Source: Carrier D5FS(L)AAH owner's manual, p. 8. Written in our own words; check the manual for your exact model.
Minimum room height and area for flammable refrigerant
Mini-split · D5FCFA
Room height must be at least 7.3 ft (2.2 m). The minimum room area depends on the refrigerant charge and release height, using the tables for the unit.
- Check that the room is at least 7.3 ft (2.2 m) high.
- Find the minimum room area from the charge and release height table for the unit.
- Make sure the room area of operation or storage matches the table.
- Keep ventilation openings clear of obstruction.
Applies to: Indoor units with R-454B refrigerant
Source: D5FCFA installation manual, p. 3 and p. 7. Written in our own words; check the manual for your exact model.
Multi-zone AUTO mode caution
Mini-split · D5FCFAH
AUTO changeover is recommended for single-zone systems only. On multi-zone systems, an indoor unit can drop into STANDBY and show two dashes (--) until all indoor units run in the same mode, either COOLING or HEATING.
Applies to: Multi-zone systems
Source: D5FCFAH Owner's Manual, p. 2. Written in our own words; check the manual for your exact model.
Operating modes
Mini-split · D5FSOAH
Five modes: FAN Only, AUTO, HEATING (heat pumps only), COOLING, and DEHUMIDIFICATION. HEATING is the priority mode, and simultaneous heating and cooling is not allowed. In multi-zone systems, AUTO can put a unit into STANDBY, shown as two dashes (--), until all indoor units run the same mode.
- Use AUTO on single-zone systems only.
- On multi-zone systems, expect '--' on the display when a unit is in STANDBY; all units must be in the same mode, either COOLING or HEATING.
- Dehumidification (DRY) reduces humidity and slightly cools the room. It does not replace a dehumidifier.
Applies to: All operating modes
Source: D5FSOAH Owner's Manual, p. 5. Written in our own words; check the manual for your exact model.
Operating modes overview
Mini-split · D5FSFAH
The unit has five modes: FAN Only, AUTO, HEATING, COOLING and DEHUMIDIFICATION (DRY).
- Use AUTO only on single-zone systems; on multi-zone systems AUTO can put an indoor unit in STANDBY (shown as --).
- HEATING is the priority mode; simultaneous heating and cooling is not allowed.
Applies to: D5FSFAH floor console ductless system
Source: Carrier D5FSFAH owner's manual, p. 2-3. Written in our own words; check the manual for your exact model.
Optional 24V interface for third-party control
Mini-split · D5FSHA
An optional 24V interface lets a third-party thermostat control the ductless system.
- Install the 24V interface if a third-party thermostat must control the system.
Applies to: D5FSHA systems
Source: Carrier D5FSHA product data, p. 10. Written in our own words; check the manual for your exact model.
Optional Wi-Fi kit for smart phone control
Mini-split · D5FSHA
The Wi-Fi kit lets the system be controlled from a connected smartphone app.
- Install the Wi-Fi kit (P/N KSAIF0701AAA) to enable smartphone control.
Applies to: D5FSHA systems
Source: Carrier D5FSHA product data, p. 10. Written in our own words; check the manual for your exact model.
Outdoor heat pump compressor time delay
Mini-split · D5FSHA
The outdoor condensing unit on heat pumps has a three-minute time delay before the compressor starts. Over-current and high temperature protection are also covered by this delay.
- Allow about three minutes before expecting the compressor to start after a restart.
Applies to: Heat pump outdoor units
Source: Carrier D5FSHA High Wall Ductless System Product Data, p. 2. Written in our own words; check the manual for your exact model.
Outdoor unit control compartment and coil cleaning
Mini-split · D5FSHA
Removing the top panel on the outdoor unit gives direct access to the control compartment. The draw-thru design means dirt collects on the outside of the coil.
- Remove the top panel of the outdoor unit to reach the control compartment.
- Clean the coil from the inside using a pressure hose and detergent.
Applies to: Outdoor condensing units
Source: Carrier D5FSHA High Wall Ductless System Product Data, p. 2. Written in our own words; check the manual for your exact model.
Outside air output (CN8)
Mini-split · D5FSCAH, D5FLCAH
Output for energising an outside air fan through a relay.
- Output is 208/230 VAC. Do not exceed 1 A (200 W).
- Power is on when the indoor fan runs and off when the indoor fan stops.
- No power on CN8 during force cooling or capacity test mode.
- Use a separate power supply for the outside air fan. CN8 should only drive a relay coil.
Applies to: D5FSCAH / D5FLCAH indoor unit
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 13. Written in our own words; check the manual for your exact model.
Parts the installer must buy separately
Mini-split · D5FSOAH
Several items are not supplied with the indoor unit: outdoor unit power cable, connection cable, drain pipe, refrigerant piping and the remote controller holder. An additional circuit breaker is also required for the installation.
- Buy the outdoor power cable, connection cable, drain pipe, refrigerant piping and remote controller holder separately.
- Fit an additional circuit breaker for the indoor unit.
Applies to: D5FSOAH indoor unit installation
Source: D5FSOAH installation instructions, p. 10. Written in our own words; check the manual for your exact model.
PCB fuse replacement
Mini-split · D5FSHA
The control board has an overcurrent fuse. Its rating is printed on the board (examples: T3.15AL/250VAC, T5AL/250VAC, T20A/250VAC, T30A/250VAC).
- Replace only with a blast-proof ceramic fuse matching the rating printed on the board.
Applies to: Indoor and outdoor control boards
Source: Carrier D5FSHA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Performance and energy tips for the customer
Mini-split · D5FS(L)AAH
Basic steps that help the unit run efficiently.
- Keep doors and windows closed.
- Use TIMER ON and TIMER OFF to limit energy use.
- Do not block air inlets or outlets.
- Inspect and clean air filters regularly.
- Replace the air filter every 30 to 90 days, depending on thickness and MERV rating.
- Do not set the temperature to excessive levels.
- Close curtains in cooling to block direct sun, and keep them closed in heating to hold heat in.
- Do not place objects near the air inlet or outlet.
Applies to: Indoor unit
Source: Carrier D5FS(L)AAH owner's manual, p. 9-10. Written in our own words; check the manual for your exact model.
Point the remote at the right side of the unit
Mini-split · D5FCFAH
Commands must be sent toward the right side of the indoor unit. The unit confirms receipt with an audible beep. The remote works up to 26 ft (8 m) away without obstructions.
- Point the remote toward the right side of the indoor unit when sending commands.
- Stay within 26 ft (8 m) with no obstructions, and within range of the unit when using the timer.
Applies to: D5FCFAH wireless remote controller
Source: Carrier D5FCFAH owner's manual, p. 12-13. Written in our own words; check the manual for your exact model.
Power supply, wiring and protection requirements
Mini-split · D5FSOA
Fixed wiring needs an all-pole disconnect and a residual current device. Use only the specified wire and dedicated circuit.
- Use only the specified wire. If the wire is damaged, have it replaced by the manufacturer, its service agent or a similarly qualified person.
- Ground the product at installation.
- Use an all-pole disconnect with at least 3 mm contact clearance on all poles, in the fixed wiring.
- Use a residual current device rated at no more than 30 mA where leakage current may exceed 10 mA.
- Use a dedicated circuit and breaker. Do not share the outlet. Do not use defective or under-rated breakers.
- Do not modify or extend the power cable.
- Wire all connections to the Electrical Connection Diagram on the indoor and outdoor unit panels.
- Route wiring so the control board cover closes fully, and clamp cables so the terminals are not stressed.
Applies to: D5FSOAH indoor and outdoor units
Source: Carrier D5FSOAH service manual, p. 2, p. 4. Written in our own words; check the manual for your exact model.
Power-on buzzer check
Mini-split · D5FCFAH
Every time the unit is powered on, it should give a buzzing sound to show it powered on normally. No sound may mean a malfunction.
- If there is no buzz at power-on, power the unit on again or check the circuit.
Applies to: Indoor unit
Source: D5FCFAH Owner's Manual, p. 7. Written in our own words; check the manual for your exact model.
Pre-season inspection checklist
Mini-split · D5FUHAQ
Run this check after long periods of non-use or before frequent use.
- Run the FAN function until the unit dries out completely.
- Clean all filters.
- Check for damaged wires.
- Check for leaks.
- Make sure nothing blocks the air inlets and outlets.
Applies to: Indoor and outdoor units
Source: Carrier D5FUHAQ Owner's Manual, p. 17. Written in our own words; check the manual for your exact model.
Protect piping while bending
Mini-split · D5FSHA
Dents in the refrigerant piping reduce unit performance.
- Grip the pipe at the base of the bend.
- Bend slowly with even pressure toward the hole.
- Do not dent or damage the piping.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 17. Written in our own words; check the manual for your exact model.
R-454B flammable refrigerant (A2L)
Mini-split · D5FCFA
The system uses R-454B, safety group A2L. Follow the handling instructions and national regulations.
- Handle R-454B per the handling instructions.
- Follow national regulations for refrigerant work.
Applies to: D5FCFA system
Source: Carrier D5FCFA product data, p. 2. Written in our own words; check the manual for your exact model.
Recover and purge refrigerant
Mini-split · D5FCFA
Recovery and purging must follow the flammable refrigerant rules. Recovered refrigerant must not be mixed or reused without cleaning and checking.
- Recover the refrigerant into labeled recovery cylinders with a pressure-relief valve.
- Do not fill any cylinder above 80% of its liquid volume.
- Keep cylinders upright and do not exceed their maximum working pressure.
- Purge the circuit with oxygen-free nitrogen. Do not use compressed air or oxygen.
- Vent to atmospheric pressure before opening the circuit to work.
Applies to: All D5FCFAH units
Source: Carrier D5FCFAH service manual, p. 6-7. Written in our own words; check the manual for your exact model.
Refrigerant leak detection codes (Table 4)
Mini-split · D5FSHAH
If you see a refrigerant leak detection code, the unit goes into TURBO mode until the code clears, and a beeping sound from the indoor unit is normal.
- Call a technician as soon as possible.
- Do not be alarmed by the beeping or TURBO operation; both are normal with this code.
Applies to: Units with refrigerant sensor
Source: D5FSHAH Owner's Manual, p. 18. Written in our own words; check the manual for your exact model.
Refrigerant leak detection system
Mini-split · D5FSOAH
The unit has a leak detection system and must stay powered except during service. When a sensor detects a leak, the indoor unit shows an error code and beeps, the outdoor compressor stops immediately and the indoor fan runs. The sensor life is 15 years. A failed sensor shows FHCC and must be replaced by the manufacturer with the specified sensor.
- Keep the unit powered except during service.
- Call a technician as soon as possible if a leak code appears.
Applies to: Units with refrigerant sensor
Source: Carrier D5FSOAH owner's manual, p. 16. Written in our own words; check the manual for your exact model.
Refrigerant leak mitigation sensor
Mini-split · D5FSHA
The indoor unit is equipped with a refrigerant leak detection sensor as standard. Diagnostics warn of possible malfunctions and show error messages on the unit.
Applies to: Indoor units, sizes 06 to 36
Source: Carrier D5FSHA High Wall Ductless System Product Data, p. 4. Written in our own words; check the manual for your exact model.
Refrigerant pipe burial limit
Mini-split · D5FCFA
Burying too much refrigerant pipe lets liquid refrigerant migrate into the buried section during shutdown, which can cause slugging and compressor damage at start-up.
- Do not bury more than 36 in (914 mm) of refrigerant pipe.
- If any section is buried, provide a 6 in (152 mm) vertical rise to the outdoor unit valve connections.
Applies to: Field refrigerant piping
Source: Carrier D5FCFAH service manual, p. 1. Written in our own words; check the manual for your exact model.
Refrigerant removal, purging and recovery
Mini-split · D5FSOA
Recover refrigerant safely before any brazing or opening of the circuit. Purging uses oxygen-free nitrogen only.
- Remove refrigerant safely according to local and national rules, or isolate the leaking section with shut-off valves before brazing.
- Evacuate the circuit, then purge it with oxygen-free nitrogen. Repeat as needed.
- Break the vacuum with OFN, fill to working pressure, vent to atmosphere, then pull a vacuum again. Repeat until no refrigerant remains.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- Use recovery cylinders designated for the refrigerant, with a pressure-relief valve and shut-off valves in good order.
- Do not fill recovery cylinders above 80% liquid volume or beyond their maximum working pressure.
- Weigh the cylinder on calibrated scales during recovery. Do not mix refrigerants in units or cylinders.
- Before removing a compressor or oil, evacuate it to an acceptable level. Do not heat the compressor body with an open flame.
Applies to: D5FSOAH systems using flammable refrigerant
Source: Carrier D5FSOAH service manual, p. 6-7. Written in our own words; check the manual for your exact model.
Refrigerant system sensor and connection locations
Mini-split · D5FSOA
Thermistor T1 measures room temperature. Thermistor T2 measures condenser/evaporator temperature (gas). Connections are flared: a gas pipe connection and a liquid pipe connection. A distributor sits in the refrigerant circuit.
Applies to: D5FSOA indoor unit
Source: Carrier D5FSOA product data, p. 18. Written in our own words; check the manual for your exact model.
Remote battery replacement and life
Mini-split · D5FSHAH
Use two new AAA 1.5V alkaline batteries of the same type. Old or mixed batteries can make the remote malfunction. Batteries last about 6 months. Replace them when the indoor unit no longer beeps or the transmission indicator fails to light. Removing the batteries erases all presets such as Follow Me, which must be set again.
- Slide the back cover off the remote.
- Insert two new AAA alkaline batteries, matching the polarity marks.
- Replace the battery cover.
- If the remote will sit unused for several weeks, remove the batteries to prevent leakage damage.
Applies to: Wireless remote controller
Source: D5FSHAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Remote control battery is low or dead
Mini-split · D5FSHAH
If the indoor unit does not beep or the transmission indicator does not light, the batteries need replacing. Average battery life is about 6 months.
- Replace both AAA batteries with new alkaline cells.
Applies to: Wireless remote control
Source: Carrier D5FSHAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Remote control range
Mini-split · D5FSHAH
The remote works up to about 26 ft (8 m) with no obstructions. When the timer function is used, keep the remote within 26 ft (8 m) of the indoor unit.
Applies to: Wireless remote controller
Source: D5FSHAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Remote features not available on this unit
Mini-split · D5FSOAH
Some functions are not available on this unit, and some are blocked when matched with a multi-zone condenser.
- Intelligence Sensor and Vertical Swing are not available on this unit.
- When matched with multi-zone condensers, Intelligence Sensor, Humidity Control, ECO, Active Clean, Gear and Silent Mode are not available.
- HEAT mode is not supported on cooling-only units.
Applies to: Wireless remote RG10L5(2HS)
Source: D5FSOAH Owner's Manual, p. 8. Written in our own words; check the manual for your exact model.
Remote ON-OFF control on CN23
Mini-split · D5FSOA
Use the remote ON-OFF input on terminal CN23 with the JR6 jumper removed. Open switch turns the system off and shows CP; closed switch turns it on.
- Remove jumper JR6 before using the ON-OFF function.
- Wire the external switch to CN23.
- Open the switch to turn the system off (display shows CP).
- Close the switch to turn the system on; response is within 2 seconds.
Applies to: Indoor unit controls
Source: D5FSOA Product Data, p. 15. Written in our own words; check the manual for your exact model.
Remote ON/OFF input (CN23 / JR6)
Mini-split · D5FSCAH, D5FLCAH
Wiring a remote on/off switch to the indoor unit control board.
- Remove the jumper JR6 to enable ON/OFF control.
- Open contacts on CN23 shut the unit off.
- Closed contacts on CN23 let the unit run.
- When the contacts are open, "CP" shows on the display and wired controller.
- The port provides 12 VDC. Design maximum current is 5 mA.
Applies to: D5FSCAH / D5FLCAH indoor unit
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 13. Written in our own words; check the manual for your exact model.
Remote range, aim and battery life
Mini-split · D5FSFAH
The remote works up to 26 ft (8 m) with no obstructions. A beep confirms each command. Battery life is about 6 months.
- Point the remote toward the right side of the indoor unit when sending commands.
- Keep the remote within 26 ft (8 m) when using the timer.
- Replace batteries when there is no beep from the indoor unit or the transmission indicator does not light.
- Remove batteries if the remote will be unused for several weeks.
Applies to: Wireless remote controller
Source: D5FSFAH Owner’s Manual, p. 9, 11. Written in our own words; check the manual for your exact model.
Remove the display board (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Access to the display board after the installing cover is removed.
- Remove the 2 screws and take off the installing cover.
- Remove the display board subassembly.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 58. Written in our own words; check the manual for your exact model.
Remove the drain pump (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Removes the water pump so the drain line can be freed.
- Pinch the metal wire in the direction shown in the figure to release it.
- Pull out the drain pipe.
- Remove the 2 screws fixing the water pump assembly.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 61. Written in our own words; check the manual for your exact model.
Remove the electrical control box and main control board (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Anti-static gloves must be worn. Disconnect power before starting.
- Remove the 2 screws holding the electronic control box and the 2 screws of the earth wire.
- Disconnect the temperature sensor, pump, fan motor and water level switch connectors.
- Lift out the electronic control box subassembly.
- Release the 3 clasps of the main control board and remove the 1 earth wire screw.
- Remove the main control board subassembly.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 57. Written in our own words; check the manual for your exact model.
Remove the evaporator (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Evaporator removal from the indoor unit.
- Remove the 2 screws of the pipe clamp board.
- Remove the 4 screws of the evaporator connecting board and take it off.
- Remove the 1 screw of the evaporator fixing hanger and take the evaporator out.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 64. Written in our own words; check the manual for your exact model.
Remove the fan wheel and fan motor (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Fan wheel and motor removal for the indoor unit.
- Turn the fan wheel nut anticlockwise, then pull the fan wheel up.
- Remove the 1 screw of the fixing board.
- Turn the three motor nuts anticlockwise.
- Remove the fan motor.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 63. Written in our own words; check the manual for your exact model.
Remove the front panel (continuation of disassembly)
Mini-split · D5FSCAH, D5FLCAH
Continuation of the indoor unit panel removal. The size is not named on this page, so confirm it against the disassembly section before you start.
- Disconnect the connectors for the display board and the stepper motor.
- Squeeze the two clasps with your index finger and thumb and lift off the panel.
Applies to: Size not stated on page 56
Source: D5FSCAH / D5FLCAH service manual, p. 56. Written in our own words; check the manual for your exact model.
Remove the ventilation ring and water collector (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Removes the water collector so the water level switch can be reached. The ion generator is optional and only applies to units that have it.
- Remove the 1 screw of the ventilation ring.
- If fitted, remove the 2 screws of the positive and negative ion generator.
- Remove the 4 screws of the water collector subassembly.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 59. Written in our own words; check the manual for your exact model.
Remove the water level switch from the collector (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Continuation of the water collector removal.
- Turn the water collector subassembly over.
- Remove the water level switch.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 60. Written in our own words; check the manual for your exact model.
Remove the water pump assembly (09K/12K/18K)
Mini-split · D5FSCAH, D5FLCAH
Final step of the water pump removal, shown on this page.
- Remove the 2 screws fixing the water pump assembly.
Applies to: 09K/12K/18K size
Source: D5FSCAH / D5FLCAH service manual, p. 62. Written in our own words; check the manual for your exact model.
Replacing the control board fuse
Mini-split · D5FCFA
The control board has an overcurrent fuse. Its rating is printed on the board. Only the blast-proof ceramic type may be used.
- Read the fuse rating printed on the board (examples: T3.15AL/250VAC, T5A/250VAC, T20A/250VAC).
- Fit only a blast-proof ceramic fuse of the same rating.
- Do not use any other fuse type.
Applies to: Indoor and outdoor control boards
Source: Carrier D5FCFAH service manual, p. 2. Written in our own words; check the manual for your exact model.
SILENCE function reduces performance
Mini-split · D5FSHA
The optional SILENCE function lowers operating frequency and can reduce capacity.
- Turn off the SILENCE function if performance is poor.
Applies to: Indoor unit
Source: Carrier D5FSHA installation manual, p. 26. Written in our own words; check the manual for your exact model.
Silence operation
Mini-split · D5FSFA
Press SILENCE on the remote to lower the noise level.
- While SILENCE is active the compressor runs below F2 and the indoor unit gives a faint breeze.
Applies to: D5FSFAH 9K to 16K
Source: D5FSFAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Standard protection and comfort features
Mini-split · D5CMHA
The outdoor unit includes a base pan heater as standard on all sizes, a 3-minute time delay for the compressor, and a 46°F heating setback mode.
Applies to: D5CMHA outdoor units, all sizes
Source: Carrier D5CMHA product data, p. 4. Written in our own words; check the manual for your exact model.
Stepper motor removal
Mini-split · D5FSOA
Remove the panel first. The louver must be opened before the cover comes off.
- Remove the panel.
- Open the louver and push the hooks in the direction shown in the illustration.
- Remove the 2 screws holding the motor cover and take the cover off.
- Remove the 2 screws and take out the stepper motor.
Applies to: D5FSOAH, sizes 06K to 18K
Source: D5FSOAH service manual, p. 62. Written in our own words; check the manual for your exact model.
Turbo mode and beeping during error codes
Mini-split · D5FS(L)AAH
When a leak-detection error appears, the unit goes into turbo mode until the code clears. A beeping sound from the unit is normal. For more diagnostic detail, use the Service Manual.
- Leave the unit in turbo mode until the error clears
- Use the Service Manual for further diagnosis
Applies to: D5FS(L)AAH split-type air handler ductless system
Source: D5FS(L)AAH: Owner's Manual, p. 25. Written in our own words; check the manual for your exact model.
Turn the unit off immediately for these conditions
Mini-split · D5FSHAH
Certain conditions are unsafe and need the unit switched off right away.
- Turn off the unit if the power cord is damaged or abnormally warm.
- Turn off the unit if you smell a burning odor.
- Turn off the unit if it makes loud or abnormal sounds.
- Turn off the unit if a power fuse blows or the breaker often trips.
- Turn off the unit if water or other objects fall into or out of it.
- Do not try to fix these issues yourself; contact an authorized service provider.
Applies to: Indoor and outdoor units
Source: D5FSHAH Owner's Manual, p. 16. Written in our own words; check the manual for your exact model.
Unpacking the indoor unit
Mini-split · D5FSOAH
Remove the carton and packing material without damaging the unit.
- Cut the sealing tape on the carton.
- Remove the sealing nails on the top of the carton.
- Open the carton and remove the middle support plate if fitted.
- Remove the accessory package and any connecting wire.
- Lift the unit out and lay it flat.
- Remove the left and right or upper and lower packaging foam and the packing bag.
Applies to: Indoor unit
Source: D5FSOAH installation instructions, p. 24. Written in our own words; check the manual for your exact model.
Use only approved parts and accessories
Mini-split · D5FSHA
Non-approved parts can void the warranty and create fire, shock or malfunction risk.
- Use only the included accessories and manufacturer-specified replacement parts.
Applies to: All D5FSHA service and installation
Source: Carrier D5FSHA installation manual, p. 3. Written in our own words; check the manual for your exact model.
Vacuum work precautions
Mini-split · D5FSOAH
Always break a vacuum with dry nitrogen. Never use the system compressor as a vacuum pump.
- Break vacuum with dry nitrogen.
- Do not run the compressor to pull vacuum.
Applies to: D5FSOAH06XAK, D5FSOAH12XAK, D5FSOAH18XAK
Source: D5FSOAH service manual, p. 16. Written in our own words; check the manual for your exact model.
Wait before touching electrical parts
Mini-split · D5FSHA
Electrical parts can still carry a charge after power is removed.
- Turn off the power supply before any electrical work.
- Wait at least 10 minutes after power is off before touching electrical components.
Applies to: D5FSHA sizes 6K to 36K
Source: D5FSHA installation manual, p. 19. Written in our own words; check the manual for your exact model.
Wait for capacitors to discharge before service
Mini-split · D5FSCAH / D5FLCAH
Capacitors keep charge after power is off.
- Turn off and lock out all power.
- Wait 10 minutes after turning off power when connected to a multi-zone outdoor unit.
- Confirm capacitors are discharged before working on the boards.
- Wear anti-static gloves or a wrist strap when handling PCBs.
Applies to: Indoor and outdoor units
Source: Carrier D5FSCAH / D5FLCAH service manual, p. 27. Written in our own words; check the manual for your exact model.
Water collector and refrigerant sensor removal
Mini-split · D5FSOA
Remove the water collector first, then the refrigerant sensor. Remove the panel before starting.
- Remove the panel.
- Remove the 5 screws and take out the water collector.
- Remove the 2 screws and take out the refrigerant sensor.
Applies to: D5FSOAH, sizes 06K to 18K
Source: D5FSOAH service manual, p. 57. Written in our own words; check the manual for your exact model.
Water pump removal
Mini-split · D5FSOA
Remove the panel and water collector before the pump.
- Remove the panel and water collector.
- Remove the 2 screws and take out the water pump assembly.
- Loosen the spring.
- Remove the drain pipe.
Applies to: D5FSOAH, sizes 06K to 18K
Source: D5FSOAH service manual, p. 58. Written in our own words; check the manual for your exact model.
Which performance data is tested and which is simulated
Mini-split · D5CMHA
Extrapolated tables mark only the highlighted values as tested. All other values are simulated and are for reference only.
Applies to: D5CMHA non-ducted performance tables
Source: D5CMHA Product Data, p. 73. Written in our own words; check the manual for your exact model.
Wired and third-party control options
Mini-split · D5FSOA
Optional wired controller and 24 V interface are available for control of the indoor unit.
- Use the optional wired controller kit: connect its cable between controller and indoor unit terminal.
- Use the optional 24 V interface to control the ductless system from a third-party thermostat.
Applies to: Indoor unit controls
Source: D5FSOA Product Data, p. 12. Written in our own words; check the manual for your exact model.
Wired and wireless controller options
Mini-split · D5FS(L)AAH
The unit can be run by three methods. The wired controller KSACN1401AAA is included and is non-polarity; it has an infrared receiver and works with the wireless remote. The wireless remote is included and does the same functions as the wired controller. A third-party heat pump thermostat is not included and connects through the built-in 24V interface. Under normal conditions the fan speed, swing and temperature cannot be changed by the remote. Live heating requires a wire controller with the AXU function.
Applies to: Indoor unit controls
Source: Carrier D5FS(L)AAH owner's manual, p. 10. Written in our own words; check the manual for your exact model.
Wired and wireless remote control
Mini-split · D5FCFA
Remote control options for the console units.
- The wireless infrared remote can control more than one unit.
- The optional wired controller connects to the indoor unit terminal and can show °F or °C in 1° steps.
- Use the extension wire (RCD part 17401204000769) to lengthen the wired controller cable.
Applies to: Console indoor units
Source: D5FCFA Product Data, p. 10. Written in our own words; check the manual for your exact model.
Wired controller connection (CN41)
Mini-split · D5FSOAH
CN41 connects to the KSACN1401AAA wired controller only, using field-supplied RS-485 wire.
- Use #16 or #18 AWG shielded stranded wire for the controller link.
- Connect only to CN41.
Applies to: Wired controller KSACN1401AAA
Source: D5FSOAH service manual, p. 12. Written in our own words; check the manual for your exact model.
Wired controller connection (CN45)
Mini-split · D5FCFA
CN45 connects the KSACN1401AAA wired controller using field-provided RS-485 wire only.
- Use #16 or #18 AWG shielded stranded wire.
- Connect to CN45 only with RS-485 wire.
Applies to: D5FCFAH
Source: D5FCFAH service manual, p. 22. Written in our own words; check the manual for your exact model.
Wired controller wiring notes
Mini-split · D5FSHA
The wired controller connects to the indoor unit main board in one of two ways depending on the controller.
- For the KSACN1401AAA, connect to the 12V XYE or CN connection on the indoor main control board (Option A).
- For the KSACN1201AAA, connect to the 5-wire modular whip on the indoor display board CN port.
- Follow the controller's own installation manual for full details.
Applies to: D5FSHA with optional wired controllers
Source: D5FSHA installation manual, p. 23. Written in our own words; check the manual for your exact model.
Work safely on flammable refrigerant systems
Mini-split · D5FCFA
The refrigerant is flammable. Control ignition sources and use approved leak detection.
- Check the work area with a refrigerant detector before and during work.
- Use only detectors suitable for flammable refrigerant that do not spark.
- Do not use a halide torch or any naked flame to find leaks.
- Remove all ignition sources if a leak is suspected.
- Keep a dry powder or CO2 extinguisher near the charging area when hot work is done.
- Keep ventilation open during the work.
Applies to: All D5FCFAH units
Source: Carrier D5FCFAH service manual, p. 5-6. Written in our own words; check the manual for your exact model.
Related
Same tips in your pocket
The HVACopedia app has these tips, every error code and the settings tables offline.
For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.