Carrier · Furnace
45.1 Control failure - flame circuit / memory / sequence
What the control is telling you
Internal control fault: flame circuit fault, memory mismatch or sequence error.
Applies to: Carrier 59SC6A
Likely causes
- Control board internal failure
- Electrical noise or transient
Test and repair steps
- Cycle power to the furnace.
- If code 45 returns, replace the control.
- Before handling the board, discharge static by touching grounded furnace metal.
- Program the new control with the Model Program Number on the rating plate (mobile app via NFC with 115-V removed, or the correct super plug); never use a different program number.
- Confirm program and software in the inF menu, re-enter installer settings, and run a full cycle.
Settings for these units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label Information, p.54. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.