Carrier · Furnace

LED ON Amber LED steady on

Normal status 59TP6A58SB0A/58SB1A

What the display is showing

The amber status LED on the control (visible through the blower door sight glass) is lit and not flashing. It is one of three LED states the control uses, the others being rapid flashing and a two-digit flash code. A steady LED means the control has power and is not reporting a fault; on the 59TP6A it is what you see once the stored-code recall is finished and means normal operation.

Applies to: 59TP6A and 58SB0A/58SB1A furnaces (amber status LED control)

Settings for these units

Filter sizes by casing width and filter cabinet · 59TP6A

LocationSizeSide return filterBottom return filterType
Furnace casing14-3/16 in. wide16 x 25 x 3/4 in.14 x 25 x 3/4 in.Washable
Furnace casing17-1/2 in. wide16 x 25 x 3/4 in.16 x 25 x 3/4 in.Washable
Furnace casing21 in. wide16 x 25 x 3/4 in.20 x 25 x 3/4 in.Washable
Furnace casing24-1/2 in. wide16 x 25 x 3/4 in.24 x 25 x 3/4 in.Washable
Filter cabinet16 in. high(1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in.-Washable or media
Filter cabinet20 in. high(1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in.-Washable or media
Filter cabinet24 in. high(1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in.-Washable or media

No internal filter rack in this furnace - an external filter is required.

Side-return filters can differ in size - measure the existing filter.

Minimum clearances to combustibles · 59TP6A

PositionClearance
Rear0 in. (0 mm)
Front (combustion air openings)1 in. (25 mm)
Front, required for service24 in. (610 mm) - check local code
All sides of supply plenum1 in. (25 mm) - check local code
Sides0 in. (0 mm)
Vent0 in. (0 mm)
Top of furnace1 in. (25 mm)

Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.

Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.

Models that show this code

22 models in 59TP6A, 58SB0A/58SB1A

58SB0A045E14--1258SB0A045E17--1258SB0A070E14--1258SB0A070E17--1258SB0A070E17--1658SB0A070E21--1658SB0A090E17--1458SB0A090E21--1658SB0A090E21--2058SB0A090E24--2058SB0A110E21--2058SB0A110E24--2058SB0A135E24--2058SB0A155E24--2059TP6A040-1059TP6A040-1259TP6A060-1259TP6A060-1459TP6A080-1659TP6A080-2059TP6A100-2059TP6A120-22

Other codes on the same units

  • 33 Limit circuit fault
  • 34 Ignition proving failure
  • 43 Low-heat pressure switch open while high-heat switch closed
  • 45 Control circuitry lockout
  • Component test Component self-test mode
  • LED OFF No amber LED - no power to control
  • Rapid Flash Reversed 115-V polarity (or twinning phasing)
  • Stored codes Recall stored status codes

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59TP6A installation instructions, Troubleshooting / Service and Maintenance, p.76-77; Carrier 58SB0A/58SB1A installation instructions (58SB0A-05SI), p.26 and p.31. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.