Carrier · Furnace
LED OFF No amber LED - no power to control
What the control is telling you
The status LED is dark, meaning the control is not getting 115 V or 24 V, or the control itself has failed.
Applies to: 59TP6A two-stage variable-speed ECM multipoise condensing gas furnace, all sizes (040-10 to 120-22)
Likely causes
- Open circuit breaker or broken supply wiring
- Blower door switch open or faulty
- Failed transformer
- Failed furnace control
Test and repair steps
- Warning: Shut off 115-V power and gas, and lock/tag out before working inside the furnace; there may be more than one power source.
- Check that the circuit breaker is closed and there is continuity in the wire from breaker to furnace.
- Confirm the blower door is on and the door switch is closed; check for 115 V reaching the door switch. Replace the door switch if 115 V arrives but does not pass through.
- Check for 115 V at L1 and L2 on the control.
- Check for 24 V at SEC-1 and SEC-2; if 115 V is present but no 24 V, replace the transformer.
- If 115 V and 24 V are both present but the LED stays off, replace the furnace control.
Settings for these units
Filter sizes by casing width and filter cabinet · 59TP6A
| Location | Size | Side return filter | Bottom return filter | Type |
|---|---|---|---|---|
| Furnace casing | 14-3/16 in. wide | 16 x 25 x 3/4 in. | 14 x 25 x 3/4 in. | Washable |
| Furnace casing | 17-1/2 in. wide | 16 x 25 x 3/4 in. | 16 x 25 x 3/4 in. | Washable |
| Furnace casing | 21 in. wide | 16 x 25 x 3/4 in. | 20 x 25 x 3/4 in. | Washable |
| Furnace casing | 24-1/2 in. wide | 16 x 25 x 3/4 in. | 24 x 25 x 3/4 in. | Washable |
| Filter cabinet | 16 in. high | (1) 16 x 25 x 3/4 in. or (1) 16 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 20 in. high | (1) 20 x 25 x 3/4 in. or (1) 20 x 25 x 4-5/16 in. | - | Washable or media |
| Filter cabinet | 24 in. high | (1) 24 x 25 x 3/4 in. or (1) 24 x 25 x 4-5/16 in. | - | Washable or media |
No internal filter rack in this furnace - an external filter is required.
Side-return filters can differ in size - measure the existing filter.
Minimum clearances to combustibles · 59TP6A
| Position | Clearance |
|---|---|
| Rear | 0 in. (0 mm) |
| Front (combustion air openings) | 1 in. (25 mm) |
| Front, required for service | 24 in. (610 mm) - check local code |
| All sides of supply plenum | 1 in. (25 mm) - check local code |
| Sides | 0 in. (0 mm) |
| Vent | 0 in. (0 mm) |
| Top of furnace | 1 in. (25 mm) |
Keep 1 in. from combustibles to supply duct for 36 in. horizontally from the furnace.
Do not set on carpet or combustible tile; downflow on combustible floor needs the accessory floor base unless on a matching coil casing.
- Filter sizes by casing width · 58SB0A/58SB1A
Models that show this code
22 models in 59TP6A, 58SB0A/58SB1A
Other codes on the same units
- 33 Limit circuit fault
- 34 Ignition proving failure
- 43 Low-heat pressure switch open while high-heat switch closed
- 45 Control circuitry lockout
- Component test Component self-test mode
- LED ON Amber LED steady on
- Rapid Flash Reversed 115-V polarity (or twinning phasing)
- Stored codes Recall stored status codes
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier 59TP6A Installation, Start-up, Operating and Service Instructions, Fig. 66 Troubleshooting Guide, p.88. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.