14.1 Ignition lockout after 4 tries

High severity 59SC6A

What the control is telling you

The furnace failed to light and prove flame on 4 ignition attempts in a row and is locked out.

Applies to: Carrier 59SC6A

Likely causes

  • No gas or low gas supply pressure
  • Manual gas valve closed
  • Faulty hot surface igniter (HSI)
  • Dirty or poorly positioned flame sensor
  • Gas valve not opening
  • Poor ground

Test and repair steps

  1. Warning: If you smell gas, shut off the gas and fix the leak before any ignition attempt.
  2. Know the sequence inducer starts, LPS closes, 15-s prepurge, 17-s igniter warm-up, gas valve opens, then a 2-s flame-proving window starts 5 s after the valve opens. Failure to prove flame repeats for up to 3 more trials (4 total), then lockout.
  3. Confirm the manual gas shutoff is open and natural gas supply pressure is 4.5-14 in. w.c.
  4. Watch a trial does the HSI glow? Check HSI cold resistance across both leads at room temperature: 40-70 ohms. Replace if out of range or damaged.
  5. Does the gas valve open (24 VAC at valve) and burners light? If no gas with 24 VAC present, suspect the valve; check manifold pressure (2.8-3.8 in. w.c. natural gas for 40k-120k models; max 1.8 in. w.c. on 26k model).
  6. If burners light then go out within ~2 s, clean the flame sensor with 0000 steel wool only (no sandpaper or emery cloth) and check its position.
  7. Verify ground the control proves flame through the green/yellow ground to the gas valve and manifold bracket; the flame-sense ground wire must be attached to furnace sheet metal.
  8. Check igniter alignment and orifices for blockage.
  9. Reset the lockout by briefly removing 115 VAC power, or by breaking 24 VAC at SEC1/SEC2 on the control (not at W, G or R); otherwise it auto-resets after 3 hours.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 59SC6A Installation, Start-up, Operating and Service Instructions, Fig. 60 Service Label p.54; Fig. 61 wiring notes p.56; Burner/Igniter service p.66-67; Sequence of Operation p.68-69. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.